MISUMI LB6110ER Digital Output with Shutdown Input User Manual
- June 9, 2024
- MiSUMi
Table of Contents
LB6110ER Digital Output with Shutdown Input
User Manual
LB6110ER Digital Output with Shutdown Input
- 4-channel
- Outputs Ex ia
- Installation in Zone 2 or safe area
- Line fault detection (LFD)
- Positive or negative logic selectable
- Simulation mode for service operations (forcing)
- Permanently self-monitoring
- Output with watchdog
- Output with bus-independent safety shutdown
Function
The digital output features 4 independent channels.
The device can be used to drive solenoids, sounders, or LEDs.
Open and short-circuit line faults are detected.
The outputs are galvanically isolated from the bus and the power supply.
The output can be switched off via a contact. This can be used for bus-
independent safety applications.
Connection
Technical Data
Slots
Occupied slots | 2 |
---|---|
Functional safety related parameters | **** |
Safety Integrity Level (SIL) | SIL 2 |
Performance level (PL) | PL d |
Supply
Connection| backplane bus / booster terminals
Rated voltage| Ur 12 V DC , only in connection with the power supplies LB9*
Input voltage range| U18.5 … 32 V DC (SELV/PELV) booster voltage
Power dissipation| 3 W
Power consumption| 0.15 W
Internal bus**
Connection| backplane bus
Interface| manufacturer-specific bus to standard com unit
Digital output
Number of channels 4
Suitable field devices
Field device| Solenoid Valve
Field device [2]| audible alarm
Field device [3]| visual alarm
Connection| channel I: 1+, 2-; channel II: 3+, 4-; channel III: 5+, 6-;
channel IV: 7+, 8-
Internal resistor| Ri| max. 370 Ω
Current limit| Imax| 37 mA
Open loop voltage| Us| 24.5 V
Line fault detection| can be switched on/off for each channel via
configuration tool also when turned off (every 2.5 s the valve is turned on
for 2 ms)
Short-circuit| < 100 Ω
Open-circuit| > 15 kΩ
Response time| 10 ms (depending on bus cycle time)
Watchdog| within 0.5 s the device goes in safe state, e.g. after loss of
communication
Reaction time| 10 s
Indicators/settings
LED indication, Power LED (P) green: supply Status LED (I) red: line fault ,
red flashing: communication error
Coding| optional mechanical coding via front socket
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU| EN 61326-1:2013
Conformity
Electromagnetic compatibility: NE 21
Degree of protection| IEC 60529
Environmental test| EN 60068-2-14
Shock resistance| EN 60068-2-27
Vibration resistance| EN 60068-2-6
Damaging gas| EN 60068-2-42
Relative humidity| EN 60068-2-78
Ambient conditions
Ambient temperature -20 …
60 °C (-4 … 140 °F)
Storage temperature| -25 … 85 °C (-13 … 185 °F)
Relative humidity| 95 % non-condensing
Shock resistance| shock type I, shock duration 11 ms, shock amplitude 15 g,
number of shocks 18
Vibration resistance| frequency range 10 … 150 Hz; transition frequency: 57.56
Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 … 100
Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90
minutes at each resonance
Damaging gas| designed for operation in environmental conditions acc. to
ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protection| IP20 when mounted on backplane
Connection| removable front connector with screw flange (accessory) wiring
connection via spring terminals (0.14… 1.5 mm2) or screw terminals(0.08… 1.5
mm2)
Mass| approx. 150 g
Dimensions| 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch)
Data for application in connection with hazardous areas
EU-type examination certificate: PTB 03 ATEX 2042 X
Marking| 1 II (1)G [Ex ia Ga] IIC
1 II (1)D [Ex ia Da] IIIC
1 I (M1) [Ex ia Ma] I
---|---
Output|
Voltage| Uo| 27.8 V
Current| Io| 90.4 mA
Power| Po| 629 mW
Internal capacitance| Ci| 1.65 nF
Internal inductance| Li| 0 MH
Certificate| PF 08 CERT 1234 X
Marking| 1 II 3 G Ex nab IIC T4 Go
Galvanic isolation|
Output/power supply, internal bus| safe electrical isolation acc. to EN
60079-11, voltage peak value 375 V
Directive conformity|
Directive 2014/34/EU| EN IEC 60079-0:2018+AC:2020 EN 60079-11:2012
EN 60079-15:2010
International approvals
ATEX approval| PTB 03 ATEX 2042 X
IECEx approval| BVS 09.0037X
Approved for| Ex nA [ia Ga] IIC T4 Gc [Ex ia Da] IIIC
[Ex ia Ma] I
General information
System information| The module has to be mounted in appropriate backplanes
(LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding
declaration of conformity. For use in hazardous areas (e. g. Zone 2, Zone 22
or Div. 2) the module must be installed in an appropriate enclosure.
Supplementary information| EC-Type Examination Certificate, Statement of
Conformity, Declaration of Conformity, Attestation of Conformity and
instructions have to be observed where applicable. For information see www
.pepperl-fuchs.com.
Assembly
Front view
Digital Output with Shutdown Input
Load calculation
Road = Field loop resistance
Use = Us – Ri x I.e.
I.e. = Us/(Ri + Road)
Characteristic Curve
Refer to “General Notes Relating to Pepperl+Fuchs Product
Information”.
Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
pa-info@us.pepperl-fuchs.com
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
References
- Pepperl+Fuchs International. Industrial Sensors, Factory Automation, Process Automation, Intrinsic Safety, Explosion Protection
- Pepperl+Fuchs International. Industrial Sensors, Factory Automation, Process Automation, Intrinsic Safety, Explosion Protection
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>