MEAN WELL DR-15 DR Family with Class II Installation Guide
- September 17, 2024
- MEAN WELL
Table of Contents
MEAN WELL DR-15 DR Family with Class II
Product Information
Specifications
- Type: DR Family with Class II
- Series: DR-15, DR-30, DR-60, DR-100
Product Usage Instructions
Mounting Instructions
- Mount the unit with input terminals down to ensure sufficient cooling.
- Admissible DIN rail: TS35/7.5 or TS35/15
- For rail fastening:
- Tilt the unit slightly rearwards.
- Fit the unit over the top hat rail.
- Slide it downward until it hits the stop.
- Press against the bottom for locking.
- Shake the unit slightly to check the locking action.
Wire Connection Instructions
- Use stranded copper wire only with recommended wire sizes based on the rated current of equipment.
- Recommended wire strapping length: 7mm/0.275inch.
- Ensure that all strands of each stranded wire enter the terminal connection securely to prevent poor contact.
- If using multiple wires, de-rate the current each wire carries to 80% of the suggested current.
- If the power supply has multi-output terminals, connect each contact to wires to distribute current stress.
Torque and Fuse Recommendations
- Recommended torque setting for terminals: 5 kgf-cm (4.4 Lb-in).
- Recommended screwdriver: 3mm, slotted type.
- Suggested fuse and maximum number of DR class PSUs that can be connected to a circuit breaker at 230V (See table below).
Model | Circuit breaker | Fuse |
---|---|---|
DR-15 | T2A/L250V | 19 |
DR-30 | F2A/L250V | 7 |
DR-60 | F3.15A/L250V | 3 |
DR-100 | F3.15A/L250V | 3 |
FAQ
-
Q: Where can I find more information about the products?
A: For more details about the products, please visit www.meanwell.com. -
Q: How should I disconnect the system from the supply voltage?
A: Before commencing any installation, maintenance, or modification work, disconnect your system from the supply voltage to ensure safety and prevent inadvertent connections in the circuit. -
Q: What locations are suitable for installing the product?
A: Pollution Degree 2 applies where there is only non-conductive pollution that might temporarily become conductive due to occasional condensation. Generally, refer to dry, well-ventilated locations such as control cabinets for installation.
Type
DR Family with Class II (Series:DR-15, DR-30, DR-60, DR-100)
- DR-15-5 INPUT: 100 -240VAC 0.88A 50/60Hz OUTPUT: 5V 2.4A
- DR-15-12 INPUT: 100 -240VAC 0.88A 50/60Hz OUTPUT: 12V 1.25A
- DR-15-15 INPUT: 100 -240VAC 0.88A 50/60Hz OUTPUT: 15V 1A
- DR-15-24 INPUT: 100 -240VAC 0.88A 50/60Hz OUTPUT: 24V 0.63A
- DR-30-5 INPUT: 100 -240VAC 1.1A 50/60Hz OUTPUT: 5V 3A
- DR-30-12 INPUT: 100 -240VAC 1.1A 50/60Hz OUTPUT: 12V 2A
- DR-30-15 INPUT: 100 -240VAC 1.1A 50/60Hz OUTPUT: 15V 2A
- DR-30-24 INPUT: 100 -240VAC 1.1A 50/60Hz OUTPUT: 24V 1.5A
- DR-60-5 INPUT: 100 -240VAC 1.8A 50/60Hz OUTPUT: 5V 6.5A
- DR-60-12 INPUT: 100 -240VAC 1.8A 50/60Hz OUTPUT: 12V 4.5A
- DR-60-15 INPUT: 100 -240VAC 1.8A 50/60Hz OUTPUT: 15V 4A
- DR-60-24 INPUT: 100 -240VAC 1.8A 50/60Hz OUTPUT: 24V 2.5A
- DR-100-12 INPUT: 100 -240VAC 3A 50/60Hz OUTPUT: 12V 7.5A
- DR-100-15 INPUT: 100 -240VAC 3A 50/60Hz OUTPUT: 15V 6.5A
- DR-100-24 INPUT: 100 -240VAC 3A 50/60Hz OUTPUT: 24V 4.2A
Introduction
DR with class II is a double insulated DIN rail power supply series, meaning it is ungrounded. Like other Mean Well’s DIN series, they can be mounted on a TS35 Standard DIN rail.
Installation
- Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit in use to prevent it from overheating. Also a 10-15 cm clearance must be kept when the adjacent device is a heat source.
- The appropriate mounting orientation for the unit is vertical, the input terminals at the bottom and output on the top for DR-15, the input terminals on the right and output on the left for DR-30, DR-60, and DR-100. Mounting orientations other than that, such as upside down, horizontal, or table-top mounting, is not allowed.
- Use stranded copper wire only, and recommended wires are shown as below.
AWG| 18| 16| 14| 12
---|---|---|---|---
Rated Current of Equipment (Amp)| 6A| 6-10A| 13-16A| 16-25A
Cross-section of
Lead(mm2 )
| 0.75| 1.00| 1.5| 2.5
Note:Current each wire carries should be de-rated to 80% of the current
suggested
above when using 5 or more wires connected to the unit.
Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are securely fixed to prevent poor contact. If the power supply possesses multi-output terminals, please make sure each contact is connected to wires to prevent too much current stress on a single contact.
-
Use wire that can withstand temperatures of at least 80°C such as UL1007.
-
Recommended wire strapping length is 7mm/0.275inch.
-
Recommended torque setting for terminals is 5 kgf-cm (4.4 Lb-in).
-
The recommended screwdriver is 3mm, slotted type.
-
The suggested fuse and maximum number of the DR classⅡ PSUs that can be connected to a circuit breaker at 230V are shown as below.
Model| Fuse| Circuit breaker
---|---|---
C16| D16
DR-15| T2A/L250V| 19| 22
DR-30| F2A/L250V| 7| 15
DR-60| F3.15A/L250V| 3| 7
DR-100| F3.15A/L250V| 3| 6 -
Mounting Instruction:
Mount, as shown in figure only, with input terminals down, or else sufficient cooling, will not be possible.
Admissible DIN rail:TS35/7.5 or TS35/15
For rail fastening:- a: Tilt the unit slightly rearwards.
- b: Fit the unit over top hat rail.
- c: Slide it downward until it hits the stop.
- d: Press against the bottom for locking.
- e: Shake the unit slightly to check the locking action.
-
For other information about the products, please refer to www.meanwell.com for details.
Warning & Caution
-
Risk of electrical shock and energy hazard. All failure should be examined by a qualified technician. Please do not remove the case of the power supply by yourself!
-
Risk of electric arcs and electric shock (danger to life). Connecting both the primary and the secondary sides together is not allowed.
-
Risk of burn hazard. Do not touch the unit in operation and shortly after disconnection!
-
Risk of fire and short circuit. The openings should be protected from foreign objects or dripping liquids.
-
Only install the unit in a pollution degree 2 environment (Note.1).
-
Please do not install the unit in places with high moisture or near the water.
-
The maximum operating temperatures is 50°C for DR-15 and DR-30 series and 40°C for DR-60 and DR-100 series, please do not install the unit in places with high ambient temperature or near fire source.
-
Output current and output wattage must not exceed the rated values on its specification.
-
Disconnect system from supply voltage:
Before commencing any installation, maintenance or modification work: Disconnect your system from supply voltage. Make sure that inadvertent connection in circuit will be impossible! -
For continued protection against risk of fire, replace only with same type and rating of fuse.
Note.1: Pollution Degree 2 applies where there is only non-conductive pollution that might temporarily become conductive due to occasional condensation. Generally refer to dry, well-ventilated locations, such as control cabinets.
Manufacturer:
MEAN WELL ENTERPRISES Co., LTD.
No.28, Wuquan 3rd Rd., Wugu Dist.,
New Taipei City 24891, Taiwan
Tel: +886-2-2299-6100
Web: www.meanwell.com
Branch Office:
-
China
MEAN WELL (GUANGZHOU)
ENTERPRISES Co., LTD.
2F, A Building, Yuean lndustry Park, Huangcun,Dongpu Yown, Tianhe District, Gungzhou, China
Post Code: 510660
Tel: +86-20-2887-1200
Web: www.meanwell.com.cn -
U.S.A.
MEAN WELL USA, INC.
44030 Fremont Blvd., Fremont,
CA 94538, U.S.A.
Tel: +1-510-683-8886
Web: www.meanwellusa.com -
Europe
MEAN WELL EUROPE B.V.
Langs de Werf 8, 1185XT
Amstelveen, The Netherlands
Tel: +31-20-758-6000
Web: www.meanwell.eu
Declaration of Conformity
Declaration of China RoHS Conformity
In order to reduce the impacts on the environment and take the more
responsibility for protecting the earth, MEAN WELL is confirming and
announcing the conformity to China RoHS, an Administrative Measures for the
Restriction of the Use of Hazardous Substances in Electrical and Electronic
Products.
- Environment Friendly Use Period Label
- Observing SJT 11364-2014, Marking for the Restricted Use of Hazardous Substances in Electronic and Electrical Products
- Observing SJ/Z 11388-2009, General Guidelines of Environment-friendly Use Period of Electronic Information Products Appendix B, adopting table look-up to verify the Environment Friendly Use Period
- Names and Contents of Hazardous Substances Lists****
Part Name| Hazardous Substances
---|---
Lead (Pb)| Mercury (Hg)| Cadmium (Cd)| Hexavalent chromium (Cr6+)| Polybrominated biphenyls (PBB)| Polybrominated diphenylethers (PBDE)
PCB and its components| X| O| O| O| O| O
Metal structure parts| X| O| O| O| O| O
Plastic structure parts| O| O| O| O| O| O
Accessories| O| O| O| O| O| O
Cables| X| O| O| O| O| O
O: The concentration of the hazardous substances within the homogeneous material of that product is less than the concentration limits set by GB/T 26572-2011.
X: The concentration of the hazardous substances within the homogeneous material of that product is over the concentration limits set by GB/T 26572-2011; however, it follows the standard advised by 2011/65/EU.
Declaration of China VOC Conformity
In order to reduce the impacts on the environment and take the more
responsibility for protecting the earth, MEAN WELL is confirming and
announcing the conformity to China’s Standardization Administration Releases
VOC Standards
Standard No. | Name of the Standard |
---|---|
GB 30981-2020 | Limit of harmful substances of industrial protective coatings |
GB 33372-2020 | Limits for volatile organic compounds content in adhesive |
GB 38507-2020 | Limits for volatile organic compounds (VOCs) In printing ink |
GB 38508-2020 | Limits for volatile organic compounds content in cleaning |
agents
Declaration of Five PBT TSCA Conformity
In order to reduce the impacts on the environment and take more
responsibility for protecting the earth, MEAN WELL hereby confirms that MEAN
WELL product series comply with Use and Risk Management for Five PBT Chemicals
under TSCA section 6(h).
CAS No. | Substance Name |
---|---|
1163-19-5 | Decabromodiphenyl ether (DecaBDE) |
68937-41-7 | Phenol, isopropylated, phosphate (3:1) |
PIP (3:1)
732-26-3| 2,4,6-Tris (tert-butyl) phenol (2,4,6-TTBP)
133-49-3| Pentachlorothiophenol (PCTP)
87-68-3| Hexachlorobutadiene (HCBD)
MEAN WELL ENTERPRISES CO., LTD.
No.28, Wuquan 3rd Rd., Wugu Dist., New Taipei City 24891, Taiwan (R.O.C.)
Tel: + 886-2-2299-6100
Fax: +886-2-2299-6200
E-mail: info@meanwell.com
http://www.meanwell.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>