Roth AM-10 Connection Module Heating Cooling 230 V Basicline Instruction Manual

September 9, 2024
Roth

AM-10 Connection Module Heating Cooling 230 V Basicline

“`html

Specifications:

  • Product Name: AM-10 Connection Module Heating/Cooling 230 V
    Basicline

  • Pollution Degree: 2

  • Resistance to Voltage Surges: 2500 V, as per EN 60730

  • Operating Voltage: 230 V

  • Admissible Ambient Temperature: 10-32°C

  • Admissible Ambient Humidity: 10-90% RH

  • IP Rating: IP20

  • Dimensions: 52mm

  • Number of Actuators: 2x

  • Pump Connection: 1x

  • Boiler Connection: 1x

  • Housing Material: Plastic Cover

Product Usage Instructions:

Safety Precautions:

1. Danger of electrocution. Mains powered parts are located
behind the cover. The device may only be opened by a trained
electrician.

2. Disconnect the device from the mains before beginning any
work on the electrical connections.

3. Only re-apply voltage once the housing has been closed and
all installation has been completed.

4. Do not leave the device unattended while the housing is
open.

Installation:

1. Follow the fitting instructions provided for the
electrician.

2. Ensure the device is disconnected from the power supply
before any assembly or disassembly.

Operation:

1. When using the Roth clock thermostat Basicline T, ensure a
bridge is in place between points A and B.

2. Refer to the provided table for shut-down delay settings and
switch configurations.

Maintenance:

1. To replace the fuse, disconnect the device from the power
supply before assembly or disassembly.

Additional Information:

For detailed programming and specific usage scenarios, refer to
the full user manual provided with the product.

FAQ:

Q: What should I do if I encounter an electrical issue while

using the AM-10 Connection Module?

A: In case of any electrical issues, immediately disconnect the
device from the power supply and seek assistance from a qualified
electrician.

Q: Can I leave the device unattended while performing

maintenance?

A: No, it is important to never leave the device unattended
while the housing is open to prevent any accidents or hazards.

“`

AM-10 connection module heating/cooling 230 V Basicline
EN Pollution degree 2; Resistance to voltage surges 2500 V; as per EN 60730

Fitting instructions for the electrician

1135007709

AM-10 230 V Basicline

50 122 °C °F
0 32

10-90%RH

IP20
EN60529

[mm] 52

è

2x

2x

1x

326,5

90

EN DANGER Danger of electrocution. Mains powered parts are located behind the cover. The device may only be opened by a trained electrician. Disconnect the device from the mains before beginning any work on the electrical connections. Only re-apply voltage once the housing has been closed and all installation has been completed. Do not leave the device unattended while the housing is open.

1
2 1
4
2b

2a
3
4

3

Night set-back mode

The bridge between A and B is required when using the Roth clock thermostat Basicline T.

4

NO

NC

Shut-down delay
0min 5min
23 23 10min 15min
23 23

Switch 1 = ON NO Switch 1 = OFF NC

Switch 2 OFF OFF ON ON

Switch 3 OFF ON OFF ON

Time 2 Min 7 Min 12 Min 17 Min

…t

Replacing the fuse

EN DANGER Danger of electrocution Disconnect the device from the power supply before assembly or disassembly
DANGER

1

2

3

4

230 V T4A

1135007863 230 V humidity sensor with monitor functions
7% +

L N PE 230 V ~50 Hz
L N PE
L N PE 230 V ~50 Hz
L N PE

Basicline H 230 V
L NN 12 34 5

Basicline T 230 V
N L SL NSB S1 S2

7% +

Basicline H 230 V
L NN 12 34 5

Basicline H/C 230 V
C/O L N 12 34 5
7% +
WF

max. 18x 230 V, NC

Basicline H/C 230 V
C/O L N 12 34 5

max. 18x 230 V, NC

Heating/Cooling

/

AM-10 230 V

Heating

5 AM-10 230 V

Operating voltage Distributor fuse Circuits/zones
Time channels/set-back Admissible ambient temperature Admissible storage temperature T
Admissible ambient humidity Number of actuators
Pump connection Boiler connection Set-back
Heating/ cooling
TB or dew point
Housing material
Plastic cover
Fitting
Connection terminals
Power cable

230 V~ ±10 % 50…60 Hz 230 V / T4A 10
2 0…50 °C -20…70 °C <80 % rF max. 18 max. 6 (2) A max. 6 (2) A
Potential-free contact input
Potential-free contact input
Potential-free contact input
Flame-retardant plastic, ABS iron-grey RAL7011
Transparent grey
Mounted on wall or 35 mm DIN rail
Terminals with spring technology, for 0.2 to 1.5 mm²
solid: NYM-J/NYM-O (5 × 1.5 mm² max.), flexible: H03V2V2H2-F / H05V2V2H2-F

Cord grip

Integrated in housing

Protection class 230 V
Type of protection
Accessories 1135007863

IP 20 (EN 60529)
III (EN 60730)
230 V humidity sensor with monitor functions

EN QR Code for complete product information
Roth UK Ltd. www.roth-uk.com