Installation

  1. Ensure the power source is turned off before installation.
  2. Mount the Ultra Slim Step Shape DIN Rail securely in the desired location using appropriate fasteners.
  3. Connect the input voltage within the specified range (85-264VAC).

Operation

  1. After installation, turn on the power source.
  2. The Ultra Slim Step Shape DIN Rail should now be operational.

Maintenance

Regularly check for any signs of damage or wear and tear. If any issues are detected, disconnect the power source and seek professional assistance for repair or replacement.

FAQ

Q: What should I do if the Ultra Slim Step Shape DIN Rail stops working?

A: Check the power source, connections, and ensure the input voltage is within the specified range. If issues persist, contact customer support for further assistance.

Q: Can I use the Ultra Slim Step Shape DIN Rail in outdoor environments?

A: It is recommended to use the product in indoor environments to prevent exposure to harsh weather conditions.

Features

  • Ultra slim design with 17.5mm(1SU) width
  • Universal input 85~264VAC(277VAC operational)
  • No load power consumption<0.3W
  • Isolation class II
  • Pass LPS (Limited power source)
  • DC output voltage adjustable
  • Protections : Short circuit / Overload / Over voltage
  • Cooling by free air convection (working temperature:-30~+70°C)
  • DIN rail TS-35/7.5 or 15 mountable
  • LED indicator for power on
  • 3 years warranty.

Applications

  • Household control system
  • Building automation
  • Industrial control system
  • Factory automation
  • Electro-mechanical apparatus

GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx

Description

HDR-15 is one economical ultra slim 15W DIN rail power supply series, adapted to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 17.5mm(1SU) in width, which allows space saving inside the  cabinets. The entire series adopts the full range AC input from 85 VAC to 264 VAC(277 VAC operational) and conforms to BS EN/EN61000-3-2, the norm the European Union regulates for harmonic current. HDR-15 is designed with plastic housing that it can effectively prevent user from electric hazards. With working efficiency up to 87%, the entire series can operate at the ambient temperature between -30°C and 70°C under air convection. The complete protection functions and relevant certificates for home automations and industrial control apparatus (IEC62368-1, UL508, UL62368-1, BS EN/EN61558-2-16) make HDR-15 a very competitive power supply solution for household and industrial applications.

Model Encoding

SPECIFICATION

MODEL| HDR-15-5| HDR-15-12| HDR-15-15| HDR-15-24| HDR-15-48
---|---|---|---|---|---








OUTPUT

| DC VOLTAGE| 5V| 12V| 15V| 24V| 48V
RATED CURRENT| 2.4A| 1.25A| 1A| 0.63A| 0.32A
CURRENT RANGE| 0 ~ 2.4A| 0 ~ 1.25A| 0 ~ 1A| 0 ~ 0.63A| 0 ~ 0.32A
RATED POWER| 12W| 15W| 15W| 15.2W| 15.4W
RIPPLE & NOISE (max.) Note.2| 80mVp-p| 120mVp-p| 120mVp-p| 150mVp-p| 240mVp-p
VOLTAGE ADJ. RANGE| 4.5 ~ 5.5V| 10.8 ~ 13.8V| 13.5 ~ 18V| 21.6 ~ 29V| 43.2 ~ 55.2V
VOLTAGE TOLERANCE Note.3| ±2.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LOAD REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
SETUP, RISE TIME| 2000ms, 80ms/230VAC  2000ms, 80ms/115VAC at full load
HOLD UP TIME (Typ.)| 30ms/230VAC       12ms/115VAC at full load




INPUT

| VOLTAGE RANGE| 85 ~ 264VAC (277VAC operational )        120 ~ 370VDC (390VDC operational )
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 80%| 85%| 85.5%| 86%| 87%
AC CURRENT (Typ.)| 0.5A/115VAC      0.25A/230VAC
INRUSH CURRENT (Typ.)| COLD START 25A/115VAC         45A/230VAC




PROTECTION

| ****

OVERLOAD

| 110 ~ 145% rated output power
Hiccup mode when output voltage <50%, recovers automatically after fault condition is removed

Constant current limiting within 50% ~100% rated output voltage, recovers automatically after fault condition is removed


OVER VOLTAGE

| 5.75 ~ 6.75V| 14.2 ~ 16.2V| 18.8 ~ 22.5V| 30 ~ 36V| 56.5 ~ 64.8V
Protection type : Shut off o/p voltage, clamping by zener diode





ENVIRONMENT

| WORKING TEMP.| -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃) RH non-condensing
VIBRATION| 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
OPERATING ALTITUDE| 2000 meters
OVER VOLTAGE CATEGORY| Ⅲ; According to EN61558, EN50178,EN60664-1, EN62477-1; altitude up to 2000 meters











SAFETY & EMC

(Note 4)

| SAFETY STANDARDS| UL62368-1, UL508, TUV BS EN/EN61558-2-16, BS EN/EN61558-1, IEC62368-1, EAC TP TC 004, BSMI CNS14336-1 approved;

Design refer to TUV BS EN/EN62368-1

WITHSTAND VOLTAGE| I/P-O/P:4KVAC
ISOLATION RESISTANCE| I/P-O/P:100M Ohms / 500VDC / 25℃/ 70% RH




EMC EMISSION

| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032(CISPR32), CNS13438| Class B
Radiated| BS EN/EN55032(CISPR32), CNS13438| Class B
Harmonic Current| BS EN/EN61000-3-2| Class A
Voltage Flicker| BS EN/EN61000-3-3| ——-







EMC IMMUNITY

| BS EN/EN55035,  BS EN/EN61000-6-2, BS EN/EN61204-3
Parameter| Standard| Test Level /Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air; Level 2, 4KV contact, criteria A
Radiated Susceptibility| BS EN/EN61000-4-3| Level 3, criteria A
EFT/Burest| BS EN/EN61000-4-4| Level 3, criteria A
Surge| BS EN/EN61000-4-5| Level 4,2KV/L-N, criteria A
Conducted| BS EN/EN61000-4-6| Level 3, criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4, criteria A
Voltage Dips and interruptions| BS EN/EN61000-4-11| >95% dip 0.5 periods, 30% dip 25 periods,

>95% interruptions 250 periods


OTHERS

| MTBF| 3724.3K hrs min.      Telcordia SR-332 (Bellcore) ; 1166.1K hrs min.      MIL-HDBK-217F (25℃)
DIMENSION| 17.59054.5mm (WHD)
PACKING| 74g;160pcs/12.9Kg/1.09CUFT
NOTE| 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.

2.  Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.

3.  Tolerance : includes set up tolerance, line regulation and load regulation.

4.  The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”

(as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )

5.  The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).

※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block Diagram

Derating Curve

Output Derating VS Input Voltage

Mechanical Specification

(Unit: mm , tolerance ± 0.5mm)

Installation Manual

Please refer to : http://www.meanwell.com/manual.html

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

MEAN WELL User Manuals

Related Manuals