MEAN WELL SDR-480 Series 480W Single Output DIN RAIL with PFC Function Owner’s Manual

August 15, 2024
MEAN WELL

MEAN WELL SDR-480 Series 480W Single Output DIN RAIL with PFC Function

Product Specifications

  • Model: SDR-480-24
  • Output: 24V
  • Rated Current: 20A
  • Rated Power: 480W
  • Peak Current: 30A
  • Peak Power: 720W (3sec.)
  • Input Voltage Range: 90 ~ 264VAC
  • Frequency Range: 47 ~ 63Hz
  • Power Factor (Typ.): 0.94/230VAC
  • Efficiency (Typ.): 94%
  • Working Temp.: -25 ~ +70 (Refer to Derating Curve)
  • Working Humidity: 20 ~ 95% RH non-condensing
  • Safety Standards: UL508, TUV BS EN/EN62368-1, AS/NZS 62368.1, EAC TP TC 004, BSMI CNS14336-1 approved
  • Dimension: 85.5125.2128.5mm (WHD)

Product Usage Instructions

Installation:
The SDR-480 series power supply can be installed on DIN rail TS-35/7.5 or TS-35/15.

Connection:

  • Connect the input voltage within the range of 90 ~ 264VAC and ensure the frequency is between 47 ~ 63Hz.
  • Connect the output DC voltage to your device ensuring it does not exceed the rated current of 20A.

Safety Precautions:

  • Ensure the working temperature is within the specified range of -25 ~ +70 degrees Celsius.
  • Avoid exposing the power supply to high humidity levels above 95% RH.

Frequently Asked Questions (FAQ)

  • What are the main protections provided by the SDR-480 series power supply?
    The main protections include Short Circuit, Overload, Over Voltage, and Over Temperature protection.

  • How can I check if the power supply is functioning correctly?
    The SDR-480 series has a built-in DC OK relay contact that can indicate the status of the power output.

  • Is the power supply suitable for industrial use?
    Yes, the SDR-480 series is UL508 approved for industrial control equipment and complies with various industrial immunity standards.

Features

  • High efficiency 94% and low power dissipation
  • 150% peak load capability
  • Built-in active PFC function, PF>0.94
  • Protections: Short circuit / Overload / Over voltage / Over temperature
  • Cooling by free air convection
  • Built-in constant current limiting circuit
  • Can be installed on DIN rail TS-35/7.5 or 15
  • UL 508(industrial control equipment) approved
  • BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level
  • Built-in DC OK relay contact
  • 100% full load burn-in test
  • 3 years warranty

SPECIFICATION

MODEL SDR-480-24 SDR-480-48








OUTPUT

| DC VOLTAGE| 24V| 48V
RATED CURRENT| 20A| 10A
CURRENT RANGE| 0 ~ 20A| 0 ~ 10A
RATED POWER| 480W| 480W
PEAK CURRENT| 30A| 15A
PEAK POWER Note.6| 720W (3sec.)
RIPPLE & NOISE (max.) **Note.2| 100mVp-p| 120mVp-p
VOLTAGE ADJ. RANGE| 24 ~ 28V| 48 ~ 55V
VOLTAGE TOLERANCE Note.3| ±1.2%| ±1.0%
LINE REGULATION| ±0.5%| ±0.5%
LOAD REGULATION| ±1.0%| ±1.0%
SETUP, RISE TIME| 1500ms, 150ms/230VAC          3000ms, 150ms/115VAC at full load
HOLD UP TIME (Typ.)**| 14ms/230VAC at full load





INPUT

| VOLTAGE RANGE Note.7| 90 ~ 264VAC         127 ~ 370VDC
FREQUENCY RANGE| 47 ~ 63Hz
POWER FACTOR (Typ.)| 0.94/230VAC          0.99/115VAC at full load
EFFICIENCY (Typ.)| 94%
AC CURRENT (Typ.)| 5A/115VAC         2.5A/230VAC
INRUSH CURRENT (Typ.)| 40A/115VAC          80A/230VAC
LEAKAGE CURRENT| <0.8mA / 240VAC




PROTECTION

| ****

OVERLOAD

| Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut down o/p voltage with auto-recovery

150% rated power, constant current limiting with auto-recovery within 2 seconds and may cause to shut down if over 2 seconds


OVER VOLTAGE

| 29 ~ 33V| 56 ~ 65V
Protection type : Shut down o/p voltage with auto-recovery or re-power on to recovery
OVER TEMPERATURE| Shut down o/p voltage, recovers automatically after temperature goes down
FUNCTION| DC OK REALY CONTACT RATINGS (max.)| 60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load




ENVIRONMENT

| WORKING TEMP. Note.5| -25 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)
VIBRATION| Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6



SAFETY & EMC

(Note 4)

| SAFETY STANDARDS| UL508, TUV BS EN/EN62368-1, AS/NZS 62368.1, EAC TP TC 004 , BSMI CNS14336-1 approved ; (meet BS EN/EN60204-1)
WITHSTAND VOLTAGE| I/P-O/P:3KVAC  I/P-FG:2KVAC  O/P-FG:0.5KVAC  O/P-DC OK:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION| Compliance to BS EN/EN55032 (CISPR32), BS EN/EN61204-3 Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020, CNS13438


EMC IMMUNITY

| Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN61000-6-2 (BS EN/EN50082-2),

BS EN/EN61204-3, heavy industry level, EAC TP TC 020, SEMI F47 approved


OTHERS

| MTBF| 964.2K hrs min.      Telcordia SR-332 (Bellcore) ; 91.9K hrs min.      MIL-HDBK-217F (25℃)
DIMENSION| 85.5125.2128.5mm  (WHD)
PACKING| 1.6Kg; 8pcs/13.8Kg/0.9CUFT
NOTE| 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.

2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.

3. Tolerance : includes set up tolerance, line regulation and load regulation.

4.  The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. (as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )

5.  Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.

6. 3 seconds peak power max. and the average output power should not exceed the rate power.

7. Derating may be needed under low input voltage. Please check the derating curve for more details.

8. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).

※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Mechanical Specification

Block Diagram

DC OK Relay Contact

Contact Close PSU turns on / DC OK.
Contact Open PSU turns off / DC Fail.
Contact Ratings (max.) 30V/1A resistive load.

Peak Loading

Derating Curve

Output derating VS input voltage

Documents / Resources

| MEAN WELL SDR-480 Series 480W Single Output DIN RAIL with PFC Function [pdf] Owner's Manual
SDR-480-24, SDR-480-48, SDR-480 Series 480W Single Output DIN RAIL with PFC Function, SDR-480 Series, SDR-480 Series Single Output DIN RAIL with PFC Function, 480W Single Output DIN RAIL with PFC Function, Single Output DIN RAIL with PFC Function, 480W Single Output DIN RAIL, 480W DIN RAIL, DIN RAIL, Single Output DIN RAIL
---|---