MAICO ECA Series Small Room Fans Instruction Manual

August 13, 2024
MAICO

Installation and operating instructionswww.maico- ventilatoren.com
**ECA 100 ipro ECA 100 ipro VZC
ECA 100 ipro F ECA 100 ipro H
ECA 100 ipro B ECA 100 ipro K
ECA 100 ipro KVZC ECA 100 ipro KF
ECA 100 ipro KH ECA 100 ipro KB

Small room fans**http://maicoventilatoren.qr-infolox.de/open.php?id=1

Unit overview

1 Housing with motor
2 Impeller
3 Cable grommet
4 Electronics cover
5 Internal grille or internal shutter
5.1 Fixed internal grille
5.2 Electrically operated internal shutter
5.3 Bimetal
6 Cover
7 Designer cover
8 Electronic circuit boards
8.1 Standard electronics
8.2 Sensor electronics (only for models F, H and B)
8.3 VZC electronics
9 Sensors
9.1 Motion sensor B
9.2 Light sensor F
9.3 Humidity sensor H

Preface
Please read the instructions carefully before installing and using for the first time. Follow the instructions. Pass these instructions on to the owner for safekeeping.

Scope of delivery

  • Fan
  • Foam strip
  • Installation and operating instructions

Specialist installer qualifications

Installation may only be carried out by trained specialists who have the necessary knowledge and experience in ventilation engineering. The unit must be connected in accordance with the national technical approval.
Only a qualified electrician is permitted to work on the electrics. You are deemed a qualified electrician if you are familiar with the relevant standards and guidelines, can competently and safely connect units to an electrical power supply in line with the Wiring diagrams and are able to recognise and avoid risks and dangers associated with electricity on the basis of your technical training and experience.

Intended use

The unit is used for extracting air from bathrooms, toilets, storage rooms, showrooms, cellars, offices, communal showers in clubhouses, fitness centres, changing rooms and similar rooms.
Operation is only permitted with:

  • a fixed installation within buildings
  • installation on walls or ceilings
  • an air supply via shaft or duct
  • electrical flush-mounted connections

Installation in windows with window installation kit FE 100/1, connection to flat channels with spacing frame ECA-DR permitted.
This unit is only intended for domestic use and similar purposes.

Safety instructions

4.1 General safety instructions
The unit must not be used in the following situations under any circumstances:
DANGER Risk of combustion/fire from flammable materials, liquids or gases in the vicinity of the unit.
Do not place any flammable materials, liquids or gases near the unit, which may ignite in the event of heat or sparks and catch fire.
DANGER Explosive gases and dust may ignite and cause serious explosions or fire. Never use fan unit in an explosive atmosphere (risk of explosion).
WARNING Risk from operating in single air extraction systems in accordance with DIN 18017-3.
Fan does not satisfy the DIN 18017-3 standard.
Do not use fan in systems in accordance with DIN 18017-3.
WARNING Risk to health from chemicals or aggressive gases/vapours.
Chemicals or aggressive gases/vapours may harm health, especially if they are distributed throughout the rooms by the unit.
Never use unit to distribute chemicals or aggressive gases/vapours.
NOTICE Damage to unit due to grease and oil vapours from range hoods.
Grease and oil vapours from range hoods may contaminate the unit and air ducts and reduce efficiency.
Never use unit to convey these substances.
4.2 Safety instructions regarding installation, operation, cleaning and maintenance
DANGER Risks for children and people with reduced physical, sensory or mental capabilities or a lack of knowledge. Unit may only be installed, commissioned, cleaned and maintained by persons who can safely recognise and avoid the  risks associated with this work.
WARNING Risk of injury due to suction from unit and rotating impeller.
Hair, clothing, jewellery etc. may be pulled into the unit if you get too close to it.
During operation, always keep far enough away to prevent this from happening.
**WARNING Risk of injury if foreign objects are inserted into the unit. Do not insert any objects in the unit.
NOTICE A fan that is not installed correctly may result in non-intended operation or impermissible operation. Operation is only permitted with a correct installation position (see TOP on unit), with mounted design cover and outer protective grille. The fan may be operated only if the protection against accidental contact with the impeller is guaranteed to be in accordance with DIN EN ISO 13857.
WARNING Risk of injury and health risk in the event of changes or modifications or if components which are not permitted are used.
The unit may only be operated with original components. Changes and modifications to the units are not permitted and release the manufacturer from any guarantee obligations and liability, e. g. if the housing is drilled at a point which is not permitted.
WARNING Risk of injury when working at heights.
Use appropriate climbing aids (ladders).
Stability should be ensured, if necessary have the ladders steadied by a 2nd person.
Ensure that you are standing securely and cannot lose your balance and that there is no one under the unit.
DANGER Risk of death from carbon monoxide when operating with air- ventilated fireplaces.
The maximum permitted pressure difference per residential unit is 4 Pa. The consent of a professional chimney sweep is needed in all cases.
Ensure sufficient supply air intake during operation with an air-ventilated fireplace.
DANGER Danger of electric shock when operating a fan which is damaged or not fully mounted.
Before taking off the electronics cover, shut down all supply circuits (switch off mains fuse), secure against being accidentally switched back on and position a visible warning sign.
Only operate the fan when it is completely installed. Do not commission a damaged unit.
****
DANGER Danger if the relevant regulations for electrical installations are not observed. Before installing the electrics, shut down all supply circuits, deactivate the mains fuse and secure it so it cannot be switched back on. Attach a warning sign in a clearly visible place. Be sure to observe the relevant regulations for electrical installation; e.g. DIN EN 50110-1. In Germany, particularly observe VDE 0100, with the corresponding sections. A mains isolation device with contact openings of at least 3 mm at each pole is mandatory. Only connect unit to permanently wired electrical installation and with NYM-O or NYM-J cables, depending on the unit type, 3 x 1.5 mm² or 5 x 1.5 mm². The unit may only be operated using the voltage and frequency shown on the rating plate. Unit may be energized even when at a standstill and may be started up automatically by sensors, such as those for time delay or humidity etc. The degree of protection stated on the rating plate is only guaranteed if installation is undertaken correctly and if the connecting cable is correctly guided through the cable grommet. The grommet must tightly seal the cable sheathing. With protection class I, connect the PE conductor and check the connection.
CAUTION** Exercise caution when handling packaging materials. Observe applicable safety and accident prevention regulations. Store packaging material out of the reach of children (risk of suffocation due to swallowing).

Product information

5.1 ECA 100 ipro, ECA 100 ipro K

  • Small room fans for extracting air from rooms.
  • Standard model.
  • ECA 100 ipro with fixed internal grille.
  • ECA 100 ipro K with electrically operated in- ternal shutter.
  • Two performance levels as a standard feature.
  • On/off with light switch or separate switch.
  • Can be operated at two levels with a standard double reversing switch.

5.2 ECA 100 ipro VZC, ECA 100 ipro KVZC

  • Small room fans for extracting air from rooms.
  • Model with start delay and overrun time.
  • ECA 100 ipro VZC with fixed internal grille.
  • ECA 100 ipro KVZC with electrically operated internal shutter.
  • Two performance levels as a standard feature.
  • Further product features → following table.

5.3 ECA 100 ipro F, ECA 100 ipro KF

  • Small room fans for extracting air from rooms.
  • Model with light sensor, start delay and overrun time.
  • ECA 100 ipro F with fixed internal grille.
  • ECA 100 ipro KF with electric electrically oper- ated internal shutter.
  • Two performance levels as a standard feature.
  • Barrier-free product as the fan switches itself on and off via the light sensor.
  • Can only be operated in dark rooms. The light control switches on the fan when the minimum light intensity in the room is exceeded, e.g. when a light is switched on.
  • Min. 30 lux switch-on intensity (on unit).
  • Max. 1.7 lux switch-off intensity (on unit).
  • Further product features → following table.

5.4 ECA 100 ipro B, ECA 100 ipro KB

  • Small room fans for extracting air from rooms.

  • Model with motion detector and overrun time.
    Without start delay.

  • ECA 100 ipro B with fixed internal grille.

  • ECA 100 ipro KB with electrically operated in- ternal shutter.

  • Two performance levels as a standard feature.

  • Barrier-free product as the fan switches itself on and off via the motion sensor.

  • Motion sensor range 5 m, horizontal monitoring range 100°, vertical monitoring range 82°.

  • Further product features → following table.

5.5 ECA 100 ipro H, ECA 100 ipro KH

  • Small room fans for extracting air from rooms.

  • Model with humidity control (fully automatic), start delay and overrun time.

  • ECA 100 ipro H with fixed internal grille.

  • ECA 100 ipro KH with electrically operated internal shutter.

  • Barrier-free product as the fan switches itself on and off via the humidity sensor.

  • Switch-on humidity does not have to be set.
    Fan monitors the room humidity.

  • 2 performance levels as a standard feature.
    Fan extracts air automatically in level 1 or level 2, depending on the room humidity.

  • Further product features → following table.

Automatic humidity function
Once the fan is installed, it adjusts to the room humidity prevailing at that time (relative humidity). This humidity value is saved as the first reference value. The reference value does not have to be specified manually. If the relative humidity falls below the reference value during operation, the newly established reference value is saved. The lowest possible reference value is 48 % relative humidity.
If the room humidity increases by 7%, the fan switches on automatically at power level 1 (78 m³/ h).

  • If the room humidity increases even further, the unit switches to power level 2 (92 m³/h).
  • If there are no further increases, the fan continues to run at power level 1 until the humidity again falls below the saved reference value.

If the humidity falls below the reference value, overrun operation mode starts with the set overrun time. The current reference value is then saved.
If the humidity does not fall below the reference value within 60 minutes, the fan switches to the set overrun mode and then switches off.
Operation with optional light switch H and KH fans can also be operated using the light switch. If Light on is triggered, the set operating program starts. The operating program takes priority over the automatic humidity function. If Light
off is triggered, the fan continues to run until the remaining overrun time has passed. The automatic humidity function is then assigned maximum priority again and controls the fan as described above.
5.6 Unit versions

Unit ver- sions| Start delays [ sec.]| Over- run time [min.]| Mains cable [mm²]| 4 op- erat- ing pro- grams| speed con- trol- lable
---|---|---|---|---|---
ECA 100 ipro| | | 5 x 1.5| | ●
ECA 100 ipro VZC| 0/50/90/ 120| 0/8/17/ 25| 5 x 1.5| ●|
ECA 100 ipro F| 0/50/90/ 120| 0/8/17/ 25| 3 x 1.5| ●|
ECA 100 ipro H| 0/50/90/ 120*| 8/17/2 5*| 3 x 1.5| ■|
ECA 100 ipro B| | 0/8/17/ 25| 3 x 1.5| ●|
ECA 100 ipro K| | | 5 x 1.5| ■| ●
ECA 100 ipro KVZC| 0/50/90/ 120| 0/8/17/ 25| 5 x 1.5| ●|
ECA 100 ipro KF| 0/50/90/ 120| 0/8/17/ 25| 3 x 1.5| ●|
ECA 100 ipro KH| 0/50/90/ 120
| 8/17/2 5**| 3 x 1.5| ■|
ECA 100 ipro KB| | 0/8/17/ 25| 3 x 1.5| ●|

Bold Delivery status
● Standard equipment
■ With optional light switch

  • Start delay available when using an optional switch (e.g. light switch).
    ** Overrun time of 0 min available when using an optional switch (e.g. light switch).

Technical data

6.1 Ambient conditions

  • Permissible maximum temperature of air medium + 40 °C.
  • Resistance to interference according to EN 55014-2 depending on pulse shape and energy component 1000 to 4000 V. If operating with fluorescent tubes, extra interference suppres-sion measures are needed (L or C components or RC modules, protection diodes, varistors) because these values may be exceeded.
  • Recommendation: When operating on switches with a glow lamp, wire an X2 capacitor (220 nF/ 250 V) to zero. The capacitor is to be provided by the customer.
  • Storage: Store unit exclusively in a dry location (-20 to +50 °C).

6.2 Technical data table

Rated voltage 230 V
Power frequency 50 Hz
Sound pressure level Level 1: 27 dB(A) Level 2: 32 dB(A)
Degree of protection IP X5
Weight 0.7 kg

For more technical data → rating plate.
For characteristic curves → www.maico-ventil-atoren.com

Mounting preparations

7.1 Wall
Use mounting material suitable for base and of sufficient dimensions. Ensure sufficient supply air.
**** The prescribed minimum distances to the wall and the ceiling shown in the figure must be observed.

  1. Make sure the housing has a level base.

  2. Fit wall breakthrough or drill core hole. Min- imum diameter, 105 mm.
    Recommendation: Fit WH 100 wall sleeve.
    Fit wall breakthrough with minimum diameter 115 mm.
    Use ZM 11 mounting plate for rectangular wall breakthroughs.

  3. Lay power cable (flush-mounted) up to installation site, see above for spacing. Feed the power cable at least 110 mm out from the wall.

7.2 Ceiling

  1. Perform installation preparations as described in Chapter Wall [} 23].
    NOTICE Danger of short-circuits and damage to unit if condensation builds up in the fan housing.
    Thermally insulate ventilation ducts properly. Allow for a condensation drain or condensate collector in the riser.

7.3 Duct

  1. Deburr edges on the inside of the duct.
  2. Perform installation preparations as described in Chapter Wall [} 23].

Installation and commissioning

Installation video

https://maicoventilatoren.qr-infolox.de/o/qrmaicoventilatoren/851

8.1 Fan

  1. Unpack unit and take off cover.
  2. To release the cover’s locking hook, unlock using a screwdriver.
  3. Fit supplied foam strip centred in socket.
    **** The foam strip must be fitted to the ECA 100 ipro H and KH, so that the units do not draw in any unwanted air from outside.

8.2 Housing installation
NOTICE Damage to unit/functional problems in the event of rubbing impeller.
Do not fit flange sleeve either twisted or crushed.
Make sure that the surface is flat.
**** When installing the FE 100/1 window installation kit or the ECA-DR spacing frame, see the associated installation instructions at www.maico- ventilatoren.com.

  1. Insert housing into wall breakthrough/wall sleeve (TOP). 3 Cable grommet

  2. Align housing horizontally and mark both dowel holes, see arrow.

  3. Drill dowel holes with a Ø of 6 mm and insert dowels.

  4. Push cable grommet carefully out of housing and remove it.
    NOTICE Danger of short-circuits and damage to the unit. Water will penetrate if the power cable is incorrectly fed into the fan housing or if the cable grommet is not fitted correctly. Cut off cable grommet cap such that the cable grommet fits tightly round the power cable. Cut a minimum of 5 mm off the cap (power cable can bend better and electronics cover can be positioned correctly). Fit cable grommet correctly, seal on site if required.

  5. Insert cable grommet into housing.

  6. Feed power cable into the terminal compart- ment such that the cable grommet fits around the cable sheathing completely and does not penetrate too far into the terminal compartment.

  7. Insert housing into wall breakthrough/wall sleeve and secure with two screws. Do not insert the housing such that it is twisted or crushed.
    Make sure you use mounting material which is sized for the purpose.

8.3 Electrical connection
NOTICE Risk of damage to unit in the event of short-circuits.
Insulate PE conductor and individual cable cores that are not required.
Do not touch electric components.

  1. Switch off mains fuse, secure against being accidentally switched back on and position a warning sign.

  2. Only lay single cable cores in the fan. To do this, remove power cable sheathing over a length of 100 mm. Strip single cable cores to 9 to 10 mm. 13 Spring clip
    14 Connection wiring diagram

  3. Connect power cable to spring clip → Wiring diagram ECA 100 ipro.
    **** The standard model of ECA 100 ipro can be operated in two levels with double switches.
    Without a double switch, the fan can be operated either at power level 1 or at power level 2 → Associated switching variants →
    Wiring dia- grams.

  4. Check position of cable grommet. It must be well sealed.

  5. If necessary, connect a speed controller (STX 1,5).
    **** The technology used in the phase angle controller may cause humming noises.

8.4 Operating programs

  • VZC, KVZC, F, KF, B and KB: One of the 4 following operating programs can be set with jumpers J4 and J5.

  • H and KH: One of the 4 following operating programs can be set with jumpers J4 and J5.
    The operating program can only be switched on with a switch (light switch). If this is switched on, it takes priority over the automatic humidity function.

  • Program: Comfort (= ex works), Night, Economy and Power

Set the desired operating program with jumpers J4 and J5.
Comfort program

  • Power level 1 during room use, power level 2 during overrun time.
  • J4 bridged, J5 bridged.

Night program

  • Power level 2 during room use, power level 1 during overrun time.
  • J4 open, J5 open

Economy program

  • Power level 1 during operation and overrun time.
  • J4 open, J5 bridged

Power program

  • Power level 2 during operation and overrun time.
  • J4 bridged, J5 open

8.5 Final mounting
NOTICE Danger of short-circuits and damage to the unit. Humidity will penetrate if electronics cover is not fitted correctly. Press electronics cover firmly onto housing such that it is sealed and flush all the way around. When doing so, do not press setting buttons. 11 Setting button for start delay
12 Setting button for overrun time

  1. Push the electronic cover on the housing cutouts I, II and III onto the 3 locking tabs, until the tabs engage. In addition, press the electronics cover firmly on to the housing at the points indicated by the word “PRESS”.

  2. For device versions F, KF, H, KH, B and KB, insert the supplied sensor in the correct position (→ arrows X), into the connector socket.
    **** H and KH: Do not touch/push on the membrane on the flat side of the sensor wall, otherwise it will be damaged.

  3. Attach housing cover.

  4. Use the setting keys to set the start delay and/ or overrun time → Start delay and overrun time [} 27]. 6 Cover
    7 Designer cover

  5. Fit designer cover.

8.6 Commissioning

  1. Switch the mains fuse on.
  2. Run function test.

8.7 Start delay and overrun time
**** The first time the setting button is pressed, the currently set value is displayed. During operation the LEDs are off.
For delivery status → Product information [} 21].

6 Cover
7 Designer cover

  1. Carefully remove designer cover 11 Setting button for start delay
    12 Setting button for overrun time

  2. Setting the start delay: Press the left setting button repeatedly, until the LED of the desired start delay time lights up. Wait until the LED flashes twice and goes out. The value is now saved.

  3. Setting overrun time: Press the right setting button repeatedly, until the LED of the desired overrun time lights up. Wait until the LED flashes twice and goes out. The value is now saved.
    **** The settings take effect starting with the next switching process (sensor, light switch).

  4. Fit designer cover.

Operation

Fan is turned on/off using a switch (e.g. light switch). Depending on the unit variant with start delay, with H and B units operation is automatic or controlled with an additional switch.

Maintenance

The unit is maintenance-free.

Cleaning

** Clean fan regularly, especially after it has not been used for a long time.
NOTICE Risk of damage to unit if incorrect cleaning agent is used.
Only clean the cover using water.
Do not use aggressive cleaning agents.
NOTICE** Lamellae may break if cleaned incorrectly.
Be careful when cleaning them. Do not open, close or bend the lamellae too much.

  1. If the design cover is very dirty, carefully remove it and clean with water.
  2. Only use a dry cloth to clean the internal parts of the fan.
  3. Attach design cover, switch on mains fuse, remove warning sign and carry out function test.

Fault rectification

Fault finding only by qualified electrician.
Call on the services of a qualified electrician any time there is a fault. Repairs should only be carried out by a qualified electrician. Switch off mains fuse, secure against being accidentally switched back on and position a warning sign.

Fault|

Cause, measures

---|---
Fan does not switch on.| •  Start delay approx (max. 120 seconds). Wait for start delay and reduce if necessary.
•  No mains voltage. Check whether the mains fuse has failed. Switch on if necessary.
•  Impeller blocked. Should only be car- ried out by a trained specialist: Remove cover. Unlock internal grille or internal shutter via locking hooks. Check impeller and clean if necessary.
Fan does not switch off.| •  Overrun time (max. 25 min.). Wait for overrun time and reduce if ne- cessary.
Motor’s thermal over- load protection switches the fan off.| •  Motor too hot. Wait un- til the motor has cooled down. Cool-down time can be up to 10 minutes. Unit switches back on automatically after cooling down.
Lamellae do not open or close for K units.| •  Lamellae very dirty or blocked. Clean lamel- lae.
•  Check whether there are any objects between the lamellae. If so, remove them.
•  Check whether wiring is correct according to wiring diagram 1 (high level). Attach jumper between terminals 1 and 2.
Fan does not switch off or fan switches on when not wanted.| •  A high- impedance voltage is present at terminal L1 due to a glow lamp in the con- trol switch, cables laid in parallel (induction) or transformers or other electrical components. Recommendation: Wire X2 capacitor (220 nF/ 250 V) to zero.

Spare parts

In case of questions, please contact:
Maico Elektroapparate-Fabrik GmbH
Steinbeisstraße 20
78056 Villingen-Schwenningen, Deutschland
Tel. +49 7720 694 445
Fax +49 7720 694 175
E-mail: ersatzteilservice@maico.de
Spare parts can be ordered at www.shop.maicoventilatoren.com.

https://maicoventilatoren.qr-infolox.de/o/qrmaicoventilatoren/172

1 Printed circuit board, PL ABDE ECA 100 ipro E101.1404.0000
2 Electronics cover, ABDE ECA 100 ipro 1 E059.2010.0000
3 Grille, standard 0059.2012.0000
4 Cover, cpl., ABD ECA 100 ipro 1 E059.2022.9000

ECA 100 ipro VZC

1 Printed circuit board, PL ABDE ECA 100 ipro VZC E101.1406.0004
2 Electronics cover, ABDE ECA 100 ipro 1 E059.2010.0000
3 Grille, standard 0059.2012.0000
4 Cover, cpl., ABD ECA 100 ipro 1 E059.2022.9000
5 Cover, cpl., ABD ECA 100 ipro 1 E157.0116.0000

Spare parts: www.shop.maico-ventilatoren.com
ECA 100 ipro F

1 Printed circuit board, PL ABDE ECA 100 ipro F/H/ B E101.1405.0004
2 Sensor – F SE ECA 100 ipro F E157.0140.0000
3 Electronics cover, punched, ABDE ECA 100 ipro 2 E059.2010.9000
4 Grille, standard 0059.2012.0000
5 Cover, cpl. (1 sensor bore) ABD ECA 100 ipro 3 E059.2022.9200
6 Capacitor, KS ECA ER E157.0116.0000

ECA 100 ipro H

1 Printed circuit board, PL ABDE ECA 100 ipro F/H/ B E101.1405.0004
2 Sensor – H SE ECA 100 ipro H E157.0141.0000
3 Electronics cover, punched, ABDE ECA 100 ipro 2 E059.2010.9000
4 Grille, standard 0059.2012.0000
5 Cover, cpl. (1 sensor bore) ABD ECA 100 ipro 3 E059.2022.9200
6 Capacitor, KS ECA ER E157.0116.0000

ECA 100 ipro B

1 Capacitor, KS ECA ER E157.0116.0000
2 Cover, cpl. (2 sensor bores) ABD ECA 100 ipro 2 E059.2022.9100
3 Printed circuit board, PL ABDE ECA 100 ipro F/H/ B E101.1405.0004
4 Sensor – B SE ECA 100 ipro B E157.0139.0000
5 Electronics cover, punched, ABDE ECA 100 ipro 2 E059.2010.9000
6 Grille, standard 0059.2012.0000

Spare parts: www.shop.maico-ventilatoren.com
13.2 Spare parts for ECA 100 ipro K
** Spare parts may only be sourced from and fitted by a specialist installer.
ECA 100 ipro K**

1 Printed circuit board, PL ABDE ECA 100 ipro E101.1404.0000
2 Electronics cover, ABDE ECA 100 ipro 1 E059.2010.0000
3 Shutter frame with bi- metal / VM KR ECA 100 ipro E059.2007.9101
4 Cover, cpl., ABD ECA 100 ipro 1 E059.2022.9000

Spare parts: www.shop.maico-ventilatoren.com
ECA 100 ipro KVZC

1 Printed circuit board, PL ABDE ECA 100 ipro VZC E101.1406.0004
2 Electronics cover, ABDE ECA 100 ipro 1 E059.2010.0000
3 Shutter frame with bi- metal / VM KR ECA 100 ipro E059.2007.9101
4 Cover, cpl., ABD ECA 100 ipro 1 E059.2022.9000
5 Capacitor, KS ECA ER E157.0116.0000

Spare parts: www.shop.maico-ventilatoren.com
ECA 100 ipro KF

1 Printed circuit board, PL ABDE ECA 100 ipro F/H/ B E101.1405.0004
2 Sensor – F SE ECA 100 ipro F E157.0140.0000
3 Electronics cover, punched, ABDE ECA 100 ipro 2 E059.2010.9000
4 Shutter frame with bi- metal / VM KR ECA 100 ipro E059.2007.9101
5 Cover, cpl. (1 sensor bore) ABD ECA 100 ipro 3 E059.2022.9200
6 Capacitor, KS ECA ER E157.0116.0000

Spare parts: www.shop.maico-ventilatoren.com
ECA 100 ipro KH

1 Printed circuit board, PL ABDE ECA 100 ipro F/H/ B E101.1405.0004
2 Sensor – H SE ECA 100 ipro H E157.0141.0000
3 Electronics cover, punched, ABDE ECA 100 ipro 2 E059.2010.9000
4 Shutter frame with bi- metal / VM KR ECA 100 ipro E059.2007.9101
5 Cover, cpl. (1 sensor bore) ABD ECA 100 ipro 3 E059.2022.9200
6 Capacitor, KS ECA ER E157.0116.0000

Spare parts: www.shop.maico-ventilatoren.com

ECA 100 ipro KB

1 Printed circuit board, PL ABDE ECA 100 ipro F/H/ B E101.1405.0004
2 Sensor – B SE ECA 100 ipro B E157.0139.0000
3 Electronics cover, punched, ABDE ECA 100 ipro 2 E059.2010.9000
4 Shutter frame with bi- metal / VM KR ECA 100 ipro E059.2007.9101
5 Cover, cpl. (2 sensor bores) ABD ECA 100 ipro 2 E059.2022.9100
6 Capacitor, KS ECA ER E157.0116.0000

Dismantling

Dismantling only permitted by a qualified electrician.

  1. Remove covers.
  2. Remove the electronics cover.
  3. Remove power cable.
  4. Remove fan.

Environmentally responsible disposal

Old devices and electronic components may only be dismantled by specialists with electrical training.
Packaging and old appliances contain valuable materials that can be recycled.
According to the Electrical and Electronic Equipment Act and the WEEE Directive, these must not be disposed of in the domestic waste. Dispose of them in an environmentally friendly manner, in compliance with the regulations valid in the country where you are. For more information → https://www.maico- ventilatoren.com/service/entsorgung.

Acknowledgements
© Maico Elektroapparate-Fabrik GmbH. Translation of the original operating instructions. Misprints, errors and technical changes are reserved. The brands, brand names and protected trade marks that are referred to in this document refer to their owners or their products.

Maico Elektroapparate-Fabrik GmbH
Steinbeisstr. 20
78056 Villingen-Schwenningen
Deutschland
Service +49 7720 6940
info@maico.de
7185.1133.0007_RLF.9_01.24_DSW-AS

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals