MEAN WELL SDR-75 Series Rail Power Supply Instruction Manual
- August 6, 2024
- MEAN WELL
Table of Contents
MEAN WELL SDR-75 Series Rail Power Supply
Specifications
- Type: SDR DIN rail power supply Series
- Models: SDR-75, SDR-120, SDR-240, SDR-480, SDR-480P, SDR-960
FAQs
- Q: Can I mount the unit horizontally?
- A: No, the appropriate mounting orientation is vertical with input terminals at the bottom and output on top.
- Q: What is the recommended wire strapping length?
- A: The recommended wire strapping length is 5mm (0.197″).
Power Supply
- Type: SDR DIN rail power supply
- ( Series: SDR-75, SDR-120, SDR-240, SDR-480, SDR-480P, SDR-960)
- SDR-75-12 INPUT: 100-240VAC 1.55A 50/60Hz OUTPUT: 12V 6.3A
- SDR-75-24 INPUT: 100-240VAC 1.55A 50/60Hz OUTPUT: 24V 3.2A
- SDR-75-48 INPUT: 100-240VAC 1.55A 50/60Hz OUTPUT: 48V 1.6A
- SDR-120-12 INPUT: 100-240VAC 1.4A 50/60Hz OUTPUT: 12V 10A
- SDR-120-24 INPUT: 100-240VAC 1.4A 50/60Hz OUTPUT: 24V 5A
- SDR-120-48 INPUT: 100-240VAC 1.4A 50/60Hz OUTPUT: 48V 2.5A
- SDR-240-24 INPUT: 100-240VAC 2.6A 50/60Hz OUTPUT: 24V 10A
- SDR-240-48 INPUT: 100-240VAC 2.6A 50/60Hz OUTPUT: 48V 5A
- SDR-480-24 INPUT: 100-240VAC 5A 50/60Hz OUTPUT: 24V 20A
- SDR-480-48 INPUT: 100-240VAC 5A 50/60Hz OUTPUT: 48V 10A
- SDR-480P-24 INPUT: 100-240VAC 5A 50/60Hz OUTPUT: 24V 20A
- SDR-480P-48 INPUT: 100-240VAC 5A 50/60Hz OUTPUT: 48V 10A
- SDR-960-24 INPUT: 200-240VAC 6A 50/60Hz OUTPUT: 24V 40A
- SDR-960-48 (Note.2) INPUT: 200-240VAC 6A 50/60Hz OUTPUT: 48V 20A
Introduction
- SDR is a DIN rail power supply series with a 150% peak load capability (3 seconds) and high efficiency of up to 94%.
- Like other Mean Well’s DIN series, they can be mounted on a TS35 Standard DIN rail.
Installation
- Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit in use to prevent it from overheating.
- The appropriate mounting orientation for the unit is vertical, with the input terminals at the bottom and the output at the top. Mounting orientations other than that, such as upside-down, horizontal, or table-top mounting, is not allowed.
- Use copper wire only, and the recommended wires are shown below.
AWG| 18| 16| 14| 12| 10
---|---|---|---|---|---
Rated Current of Equipment (Amp)| 6A| 6-10A| 13-16A| 16-25A| 25-32A
Cross-section of
Lead(mm2 )
| 0.75| 1.00| 1.5| 2.5| 4
Note:
1. The current each wire carries should be de-rated to 80% of the current
suggested above when using 5 or more wires connected to the unit.
2. The maximum allowable wire cross-sectional area for the terminal of the
SDR-75 is 12AWG/2.5 mm2.
- Make sure that all strands of each stranded wire enter the terminal connection and that the screw terminals are securely fixed to prevent poor contact. If the power supply possesses multi-output terminals, please make sure each contact is connected to wires to prevent too much current stress on a single contact.
- Use wires that can withstand temperatures of at least 80°C, such as UL1007.
- The recommended wire strapping length is 5mm (0.197”).
- The recommended screwdriver is 4mm, slotted type.
- The recommended torque setting for terminals is shown below.
Model| I/P| O/P
---|---|---
SDR-75| 6.9 kg-cm (6 Lb-in)| 6.9 kg-cm (6 Lb-in)
SDR-120| 10 kgf-cm (9 Lb-in)| 10 kgf-cm (9 Lb-in)
SDR-240| 10 kgf-cm (9 Lb-in)| 10 kgf-cm (9 Lb-in)
SDR-480/480P| 10 kgf-cm (9 Lb-in)| 8 kgf-cm (7 Lb-in)
SDR-960| 10 kgf-cm (9 Lb-in)| 8 kgf-cm (7 Lb-in) - The suggested fuse and the maximum number of SDR PSUs that can be connected to a circuit breaker at 230V are shown below.
Model| Fuse| Circuit breaker
---|---|---
C16| D16
SDR-75| T3.15A/L250V| 10| 12
SDR-120| T4A/L250V| 7| 14
SDR-240| T5A/L250V| 4| 8
SDR-480| T8A/L250V| 4| 4
SDR-480P| T8A/L250V| 4| 4
SDR-960| F10A/H250V| 2| 2 - Mounting Instruction: Mount, as shown in the figure only, with input terminals down, or else sufficient cooling, will not be possible.
- Admissible DIN rail: TS35/7.5 or TS35/15
- For rail fastening:
- (a) Tilt the unit slightly rearwards.
- (b) Fit the unit over the top hat rail.
- (c) Slide it downward until it hits the stop.
- (d) Press against the bottom for locking.
- (e) Shake the unit slightly to check the locking action.
- For SDR-960, if your system must meet EN61204-3 Radiation class B. Then, attaching a ferrite core clamp filter to the AC cable, as close as possible to the AC source, can fulfill the radiated emissions requirements. The wiring is shown below. There are compatible models including ZCAT2235-1030A by TDK, ZCAT12V-BK by TDK, and KCF-130-B by KING CORE.
- For other information about the products, please refer to www.meanwell.com for details.
Warning / Caution!!
- Risk of electrical shock and energy hazard. All failures should be examined by a qualified technician. Please do not remove the case of the power supply by yourself!
- Risk of electric arcs and electric shock (danger to life). Connecting both the primary and the secondary sides is not allowed.
- Risk of burn hazard. Do not touch the unit in operation and shortly after disconnection!
- Risk of fire and short circuit. The openings should be protected from foreign objects or dripping liquids.
- Only install the unit in a pollution degree 2 environment (Note.1).
- Please do not install the unit in places with high moisture or near the water.
- The maximum operating temperature is 50°C for the SDR-960 series and 60°C for the SDR-75/120/240/480/480P series, please do not install the unit in places with high ambient temperature or near a fire source.
- The FG ( ) must be connected to PE (Protective Earth).
- Output current and output wattage must not exceed the rated value on its specification.
- SDR-960 is a class A product. In a domestic environment, this product may cause radio interference in which case the user may be required to take adequate measures.
- Disconnect system from supply voltage: Before commencing any installation, maintenance, or modification work: Disconnect your system from supply voltage. Make sure that an inadvertent connection in the circuit will be impossible!
- For continued protection against risk of fire, replace only with same type and rating of fuse. Pour ne pas compromettre la protection contre les risqué d’incendie, remplacer par un fusible de même type et de memes caractéristiques nominales.
CONTACT INFORMATION
Manufacturer:
- MEAN WELL ENTERPRISES Co., LTD.
- No.28, Wuquan 3rd Rd., Wugu Dist.,
- New Taipei City 24891, Taiwan
- Tel: +886-2-2299-6100
- Web: www.meanwell.com
Branch Office: China
- MEAN WELL (GUANGZHOU)
- ENTERPRISES Co., LTD.
- No.11, Jingu South Road, Huadong
- Town, Huadu District, Guangzhou,
- Guangzhou, China
- Tel: +86-20-3773-7100
- Web: www.meanwell.com.cn
China
- SUZHOU MEAN WELL
- TECHNOLOGY Co., LTD.
- No.269 Changping Rd. , Huangdai
- Town, Xiangcheng District
- Suzhou, Jiangsu Province, China
- Post Code: 215152
- Tel: +86-512-6508-8600
- Web: www.meanwell.cc
U.S.A.
- MEAN WELL USA, INC.
- 44030 Fremont Blvd., Fremont,
- CA 94538, U.S.A.
- Tel: +1-510-683-8886
- Web: www.meanwellusa.com
Europe
- MEAN WELL EUROPE B.V.
- Langs de Werf 8, 1185XT Amstelveen, The
- Netherlands
- Tel: +31-20-758-6000
- Web: www.meanwell.eu.
Declaration of China RoHS Conformity
To reduce the impacts on the environment and take more responsibility for protecting the earth, MEAN WELL is confirming and announcing its conformity to China RoHS, an Administrative Measure for the Restriction of the Use of Hazardous Substances in Electrical and Electronic Products.
Environment-Friendly Use Period Label
- Observing SJT 11364-2014, Marking for the Restricted Use of Hazardous Substances in Electronic and Electrical Products Observing SJ/Z 11388-2009, General Guidelines of Environment-friendlyUse Period of Electronic Information Products Appendix B, adopting table look-up to verify the Environment-Friendly Use Period.
Names and Contents of Hazardous Substances Lists
Part Name | Hazardous Substances |
---|---|
Lead (Pb) | Mercury (Hg) |
Polybrominated biphenyls (PBB) | Polybrominated diphenyl ethers (PBDE) |
PCB and its components | X |
Metal structure parts | X |
Plastic structure parts | O |
Accessories | O |
Cables | X |
O: The concentration of the hazardous substances within the homogeneous
material of that product is less than the concentration limits set by GB/T
26572-2011.
X: The concentration of the hazardous substances within the homogeneous
material of that product is over the concentration limits set by GB/T
26572-2011; however, it follows the standard advised by 2011/65/EU.
To reduce the impacts on the environment and take more responsibility for protecting the earth, MEAN WELL is confirming and announcing the conformity to China’s Standardization Administration Releases VOC Standards
Standard No. | Name of the Standard |
---|---|
GB 30981-2020 | **Limit harmful substances in industrial protective |
coatings
GB 33372-2020| Limits for volatile organic compounds content in
adhesive
GB 38507-2020| Limits for volatile organic compounds (VOCs) In
printing ink
GB 38508-2020| Limits for volatile organic compounds content in
cleaning agents**
To reduce the impacts on the environment and take more responsibility for protecting the earth, MEAN WELL hereby confirms that the MEAN WELL product series complies with Use and Risk Management for Five PBT Chemicals under TSCA section 6(h)
CAS No. | Substance Name |
---|---|
1163-19- 5 | Decabromodiphenyl ether (DecaBDE) |
68937-41- 7 | Phenol, is populated, phosphate (3:1) |
PIP (3:1)
732-26- 3| 2,4,6-Tris (tert-butyl) phenol (2,4,6-TTBP)
133-49- 3| Pentachlorothiophenol (PCTP)
87-68- 3| Hexachlorobutadiene (HCBD)
Documents / Resources
| MEAN
WELL SDR-75 Series Rail Power
Supply
[pdf] Instruction Manual
SDR-75, SDR-120, SDR-240, SDR-480, SDR-480P, SDR-960, SDR-75 Series Rail Power
Supply, SDR-75 Series, Rail Power Supply, Power Supply, Supply
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>