MEAN WELL DDRH-15-5P-ST-DR Ultra Wide Input DIN Rail Type DC-DC Converter Installation Guide

August 6, 2024
MEAN WELL

MEAN WELL DDRH-15-5P-ST-DR Ultra Wide Input DIN Rail Type DC-DC Converter

Specifications:

  • Type : DDRH Ultra Wide Input DIN Rail Type DC-DC Converter
  • Input Voltage: 150~1500VDC
  • Output Voltage Options:
    • 5V 2A
    • 12V 1.25A
    • 15V 1A
    • 24V 0.625A
    • 48V 0.625A
    • Other output voltage options available for different models

Product Usage Instructions

Installation:

  1. Ensure good ventilation clearances around the unit: 5mm left and right, 40mm above, and 20mm below. Maintain a 10-15 cm clearance from adjacent heat sources.
  2. Mount the unit vertically with input terminals at the bottom and output terminals at the top. Do not mount upside down, horizontally, or on a tabletop.
  3. Use copper wires of appropriate gauge:
    • AWG 20 for equipment with rated current up to 5A
    • AWG 18 for equipment with rated current up to 7A
    • AWG 16 for equipment with rated current up to 10A
    • AWG 14 for equipment with rated current up to 15A

Notes on Wiring:

  • De-rate the current each wire carries to 80% of the suggested current when using 4-6 wires connected to the unit.
  • Ensure all strands of stranded wire enter the terminal connection and screw terminals are securely fixed to prevent poor contact.
  • If the power supply has multi-output terminals, connect each contact to wires to prevent excessive current stress on a single contact.

Type: DDRH Ultra Wide Input DIN Rail Type DC-DC Converter

  • DDRH-15-5P/ST/DR INPUT: 150~1500VDC OUTPUT: 5V 2A
  • DDRH-15-12P/ST/DR INPUT: 150~1500VDC OUTPUT: 12V 1.25A
  • DDRH-15-15P/ST/DR INPUT: 150~1500VDC OUTPUT: 15V 1A
  • DDRH-15-24P/ST/DR INPUT: 150~1500VDC OUTPUT: 24V 0.625A
  • DDRH-30-12P/ST/DR INPUT: 150~1500VDC OUTPUT: 12V 2.5A
  • DDRH-30-15P/ST/DR INPUT: 150~1500VDC OUTPUT: 15V 2A
  • DDRH-30-24P/ST/DR INPUT: 150~1500VDC OUTPUT: 24V 1.25A
  • DDRH-30-48P/ST/DR INPUT: 150~1500VDC OUTPUT: 48V 0.625A
  • DDRH-45-12P/ST/DR INPUT: 150~1500VDC OUTPUT: 12V 3.75A
  • DDRH-45-15P/ST/DR INPUT: 150~1500VDC OUTPUT: 15V 3A
  • DDRH-45-24P/ST/DR INPUT: 150~1500VDC OUTPUT: 24V 1.87A
  • DDRH-45-48P/ST/DR INPUT: 150~1500VDC OUTPUT: 48V 0.938A
  • DDRH-60-5 INPUT: 150~1500VDC OUTPUT: 5V 10A
  • DDRH-60-12 INPUT: 150~1500VDC OUTPUT: 12V 5A
  • DDRH-60-24 INPUT: 150~1500VDC OUTPUT: 24V 2.5A
  • DDRH-60-48 INPUT: 150~1500VDC OUTPUT: 48V 1.25A
  • DDRH-120-12 INPUT: 250~1500VDC OUTPUT: 12V 8.4A
  • DDRH-120-24 INPUT: 250~1500VDC OUTPUT: 24V 5A
  • DDRH-120-32 INPUT: 250~1500VDC OUTPUT: 32V 3.75A
  • DDRH-120-48 INPUT: 250~1500VDC OUTPUT: 48V 2.5A
  • DDRH-240-12 INPUT: 250~1500VDC OUTPUT: 12V 16.7A
  • DDRH-240-24 INPUT: 250~1500VDC OUTPUT: 24V 10A
  • DDRH-240-32 INPUT: 250~1500VDC OUTPUT: 32V 7.5A
  • DDRH-240-48 INPUT: 250~1500VDC OUTPUT: 48V 5A

NOTE:

  • DDRH-15/30/45-xxP: PCB mounting type
  • Screw terminal type

Introduction

DDRH series is a DIN Rail type DC-DC converter with main features including DIN rail-type easy installation, ultra-wide input voltage, wide range operating temperature, DC OK relay contact and full protective functions…etc. DDRH-15/30/45/60 series has ultra-high input voltage: 150~1500Vdc and various output options: 5V / 12V /24V / 48V. DDRH-120/240 series has ultra-high input voltage: 250~1500Vdc and various output options: 12V / 24V /32V / 48V. DDRH series is suitable for industrial automation, surveillance, and telecommunication and can be widely deployed in the applications of new energy generation such as solar power, and windmill power generation, for instance, photovoltaic power systems, high voltage inverting, and so forth.

Installation

  1. Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit in use to prevent it from overheating. Also, a 10-15 cm clearance must be kept when the adjacent device is a heat source.
  2. The appropriate mounting orientation for the unit is vertical, with the input terminals at the bottom and the output on the top. Mounting orientations other than that, such as upside-down, horizontal, or table-top mounting, is not allowed.
  3. Use copper wire only, and the recommended wires are shown as below.
    AWG| 20| 18| 16| 14
    ---|---|---|---|---
    Rated Current of Equipment

(Amp)

| 5A| 7A| 10A| 15A
Cross-section of Lead(mm2 )| 0.5| 0.8| 1.3| 2.1
Note : The current each wire carries should be de-rated to 80% of the current suggested above when using 4-6 wires connected to the unit.

Make sure that all strands of each stranded wire enter the terminal connection and the screw terminals are securely fixed to prevent poor contact. If the power supply possesses multi-output terminals, please make sure each contact is connected to wires to prevent too much current stress on a single contact.

  1. Use wires that can withstand temperatures of at least 90°C, such as UL1015.
  2. The recommended wire strapping length is 6mm (0.236”).
  3. The recommended screwdriver is 3mm, slotted type.
  4. The recommended torque setting for terminals is shown as below.
    Terminal Screw

Series

| INPUT|

OUTPUT

---|---|---
DDRH-15| 5 kgf-cm (4.4Lb-in)| 5 kgf-cm (4.4Lb-in)
DDRH-30| 5 kgf-cm (4.4Lb-in)| 5 kgf-cm (4.4Lb-in)
DDRH-45| 5 kgf-cm (4.4Lb-in)| 5 kgf-cm (4.4Lb-in)
DDRH-60| 6 kgf-cm (5.2Lb-in)| 5.1kgf-cm (4.42 Lb-in)
DDRH-120| 5.1kgf-cm (4.42 Lb-in)| 5.1kgf-cm (4.42 Lb-in)
DDRH-240| 8.15kgf-cm (7 Lb-in)| 5.1kgf-cm (4.42 Lb-in)
8. External fuse wiring instruction
An external fuse is required. Fuse specification: 4A/1500Vdc.

  *  **The suggested fuse and fuse holder model:  

** For more details about the fuse and fuse holder, please refer to the below links.

  *  **The Walter fuse and fuse holder links:**
  * <http://www.walterfuse.com/pdf/powerfuse/powerfuse_wj30.pdf>
  * <http://www.walterfuse.com/pdf/holder/holder_wj-30h.pdf>
  *  **The Littelfuse fuse and fuse holder links:  

**

  * <https://www.littelfuse.com/media/electrical/datasheets/fuses/solar-fuses/littelfuse-fuse-solar-spxv-datasheet.pdf>
  * <https://www.littelfuse.com/media/electrical/datasheets/fuse-blocks-and-holders/dead-front-fuse-holders/littelfuse-fuse-holder-lfpxv-datasheet.pdf>
  * <https://www.littelfuse.com/media/electrical/datasheets/fuse-blocks-and-holders/Littelfuse-fuse-holder-lpxvdatasheet.pd>
  *  **The Bussmann fuse and fuse holder links:  

**

  * <http://www.cooperindustries.com/content/dam/public/bussmann/Electrical/Resources/Catalogs/bus-ele-cat-1007-flc-2018-sec-06-pv.pdf-ga=2.127114697.571121133.1577416796-883900423.1577416796>
  1. Mounting Instruction:
    Mount, as shown in the figure only, with input terminals down, or else sufficient cooling, will not be possible.
    Admissible DIN rail: TS35/7.5 or TS35/15

    • For rail fastening:
    1. Tilt the unit slightly rearwards.
    2. Fit the unit over the top hat rail.
    3. Slide it downward until it hits the stop.
    4. Press against the bottom for locking.
    5. Shake the unit slightly to check the locking action.
  2. Installation clearances: 40mm on top, 20mm on the bottom, and 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.

  3. The ambient temperature derating of 3.5°C/1000m with fanless models and of 5°C/1000m with fan models for operating altitudes higher than 2000m(6500fit).

  4. Please refer to the warranty statement on MEAN WELL’s website at http://www.meanwell.com

  5. For any application note and IP waterproof function installation caution, please refer to our user manual before using. https://www.meanwell.com/Upload/PDF/LED_EN.pdf

  6. Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

  7. For other information about the products, please refer to www.meanwell.com for details.

Warning/Caution !!

  • CAUTION: FOR USE IN A CONTROLLED ENVIRONMENT. REFER TO THE MANUAL FOR ENVIRONMENTAL CONDITIONS”
  • ATTENTION : A UTILISER DANS UN ENVIRONNEMENT CONTROLE. REFEREZ VOUS AU MANUEL POUR LES CONDITIONS D’ENVIRONNEMENT.
  1. Risk of electrical shock and energy hazard. All failures should be examined by a qualified technician. Please do not remove the case of the power supply by yourself!
  2. Risk of electric arcs and electric shock (danger to life). Connecting both the primary and the secondary sides together is not allowed.
  3. Risk of burn hazard. Do not touch the unit in operation and shortly after disconnection!
  4. Risk of fire and short circuit. The openings should be protected from foreign objects or dripping liquids.
  5. Only install the unit in a pollution degree 2 environment (Note.1).
  6. Please do not install the unit in places with high moisture or near the water.
  7. The maximum operating temperature is 80°C for the DDRH-60, please do not install the unit in places with high ambient temperatures or near fire source.
  8. Output current and output wattage must not exceed the rated value on its specification.
  9. Disconnect system from supply voltage:
    Before commencing any installation, maintenance or modification work: Disconnect your system from supply voltage. Make sure that an inadvertent connection in the circuit will be impossible!

Note 1: Pollution Degree 2 applies where there is only non-conductive pollution that might temporarily become conductive due to occasional condensation. Generally refer to dry, well-ventilated locations, such as control cabinets.

Manufacturer:

  • MEAN WELL ENTERPRISES Co., LTD.
  • No.28, Wuquan 3rd Rd., Wugu Dist., New Taipei City 24891, Taiwan
  • Tel : +886-2-2299-6100
  • Web : www.meanwell.com

Branch Office: China

  • MEAN WELL (GUANGZHOU)
  • ENTERPRISES Co., LTD. No.11, Jingu South Road, Huadong Town, Huadu District, Guangzhou, Guangzhou, China
  • Tel : +86-20-3773-7100
  • Web : www.meanwell.com.cn

U.S.A.

China

  • SUZHOU MEAN WELL
  • TECHNOLOGY Co., LTD. No.269 Changping Rd. , Huangdai Town, Xiangcheng District Suzhou, Jiangsu Province, China
  • Post Code: 215152
  • Tel : +86-512-6508-8600
  • Web : www.meanwell.cc

Europe

  • MEAN WELL EUROPE B.V.
  • Langs de Werf 8, 1185XT Amstelveen, The Netherlands
  • Tel : +31-20-758-6000
  • Web : www.meanwell.eu

Declaration of China RoHS Conformity
In order to reduce the impacts on the environment and take the more responsibility for protecting the earth, MEAN WELL is confirming and announcing the conformity to China RoHS, an Administrative Measures for the Restriction of the Use of Hazardous Substances in Electrical and Electronic Products.

Environment-Friendly Use Period Label

  • Observing SJT 11364-2014, Marking for the Restricted Use of Hazardous
  • Substances in Electronic and Electrical Products
  • Observing SJ/Z 11388-2009, General Guidelines of Environment-friendly
  • Use Period of Electronic Information Products Appendix B, adopting table look-up to verify the Environment-Friendly Use Period

Names and Contents of Hazardous Substances Lists



Part Name

| Hazardous Substances
---|---
Lead



(Pb)

| Mercury



(Hg)

| Cadmium



(Cd)

| Hexavalent chromium

(Cr6+)

| Polybrominated biphenyls

(PBB)

| Polybrominated diphenyl ethers

(PBDE)

PCB and its

components

| X| O| X| O| O| O
Metal structure

parts

| X| O| O| O| O| O
Plastic structure

parts

| O| O| O| O| O| O
Accessories| O| O| O| O| O| O
Cables| X| O| O| O| O| O
O: The concentration of the hazardous substances within the homogeneous material of that product is less than the concentration limits set by GB/T 26572-2011.

X: The concentration of the hazardous substances within the homogeneous material of that product is over the concentration limits set by GB/T 26572-2011; however, it follows the standard advised by 2011/65/EU.

Declaration of China VOC Conformity
In order to reduce the impacts on the environment and take the more responsibility for protecting the earth, MEAN WELL is confirming and announcing the conformity to China’s Standardization Administration Releases VOC Standards

Standard No. Name of the Standard
GB 30981-2020 **Limit of harmful substances of industrial protective

coatings
GB 33372-2020| Limits for volatile organic compounds content in adhesive
GB 38507-2020| Limits for volatile organic compounds (VOCs) In printing ink
GB 38508-2020| Limits for volatile organic compounds content in cleaning agents**

Declaration of Five PBT TSCA Conformity: In order to reduce the impacts on the environment and take the more responsibility for protecting the earth, MEAN WELL hereby confirms that MEAN WELL product series comply with Use and Risk Management for Five PBT Chemicals under TSCA section 6(h)

CAS No. Substance Name
1163-19- 5 Decabromodiphenyl ether (DecaBDE)
68937-41- 7 Phenol, isopropylated, phosphate (3:1)

PIP (3:1)

732-26- 3| 2,4,6-Tris (tert-butyl) phenol (2,4,6-TTBP)
133-49- 3| Pentachlorothiophenol (PCTP)
87-68- 3| Hexachlorobutadiene (HCBD)

MEAN WELL ENTERPRISES CO., LTD.

FAQ

Q: What are the typical applications of the DDRH series DC-DC converters?
A: The DDRH series is suitable for industrial automation, surveillance, and telecommunication, and can be widely deployed in new energy generation applications such as solar power and windmill power generation.

Q: What is the input voltage range for the DDRH-120/240 series?
A: The input voltage range for DDRH-120/240 series is 250~1500VDC.

Q: How should I mount the DDRH DC-DC converter for optimal performance?
A: Mount the unit vertically with input terminals at the bottom and output terminals at the top. Ensure proper ventilation clearances are maintained to prevent overheating.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

MEAN WELL User Manuals

Related Manuals