MEAN WELL MDR-60-20240219 60W Single Output Industrial DIN Rail Power Supply Owner’s Manual

July 30, 2024
MEAN WELL

MEAN WELL MDR-60-20240219 60W Single Output Industrial DIN Rail Power

Supply

Product Information

Specifications

  • Product Name: 60W Single Output Industrial DIN Rail Power Supply
  • Series: MDR-60
  • GTIN CODE: [GTIN CODE]
  • Input: Universal AC input/Full range
  • Protections: Short circuit / Overload / Over voltage
  • Cooling: Free air convection
  • Installation: DIN rail TS-35/7.5 or 15
  • Hazardous Locations: Class I, Div 2, T4
  • Indicator: LED for power on
  • Additional Feature: DC OK relay contact
  • No load power consumption

Product Usage Instructions

Installation

  1. Ensure the power supply is compatible with DIN rail TS-35/7.5 or 15.
  2. Follow the manufacturer’s guidelines for proper installation on the DIN rail.

Powering On

  1. Connect the universal AC input to the power supply.
  2. Turn on the power source.

Troubleshooting

If the LED indicator does not light up or there is no output, check for proper connections and ensure the input power is within the specified range.

Frequently Asked Questions

Q: What should I do if the power supply overheats?

A: Ensure proper ventilation around the power supply unit and check for any obstructions to airflow.

Q: Can this power supply be used in hazardous locations other than Class I, Div 2?

A: No, this power supply is specifically designed for Class I, Div 2 hazardous locations.

Q: How can I test the DC OK relay contact?

A: Use a multimeter to test for continuity in the relay contact when the power supply is operational.

Features

  • Universal AC input/Full range
  • Protections: Short circuit / Overload / Over voltage
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 or 15
  • Class I, Div 2 Hazardous Locations T4
  • LED indicator for power on
  • DC OK relay contact
  • No load power consumption<0.75W
  • 100% full load burn-in test
  • 3 years warranty

SPECIFICATION

MODEL MDR-60-5 MDR-60-12 MDR-60-24 MDR-60-48
**OUTPUT** DC VOLTAGE 5V 12V 24V
RATED CURRENT 10A 5A 2.5A 1.25A
CURRENT RANGE 0 ~ 10A 0 ~ 5A 0 ~ 2.5A 0 ~ 1.25A
RATED POWER 50W 60W 60W 60W
RIPPLE & NOISE (max.) **Note.2** 80mVp-p 120mVp-p 150mVp-p 200mVp-p
VOLTAGE ADJ. RANGE 5 ~ 6V 12 ~ 15V 24 ~ 30V 48 ~ 56V
VOLTAGE TOLERANCE Note.3 ±2.0% ±1.0% ±1.0% ±1.0%
LINE REGULATION ±1.0% ±1.0% ±1.0% ±1.0%
LOAD REGULATION ±1.5% ±1.0% ±1.0% ±1.0%
SETUP, RISE TIME Note.5 500ms, 30ms/230VAC            500ms,

30ms/115VAC at full load
HOLD UP TIME (Typ.)| 50ms/230VAC            20ms/115VAC at full load


**INPUT**

| VOLTAGE RANGE| 85 ~ 264VAC           120 ~ 370VDC
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 78%| 85%| 87%| 87%
AC CURRENT (Typ.)| 1.8A/115VAC            1A/230VAC
INRUSH CURRENT (Typ.)| COLD START 30A/115VAC           60A/230VAC
LEAKAGE CURRENT| <1mA / 240VAC
**PROTECTION| ****OVERLOAD| 105 ~ 150% rated output power
Protection type: Constant current limiting, recovers automatically after fault condition is removed
****
OVERVOLTAGE| 6.25 ~ 7.25V| 15.6 ~ 18V| 31.2 ~ 36V| 57.6 ~ 64.8V
Protection type: Shut down o/p voltage, re-power on to recover
FUNCTION| DC OK SIGNAL| Relay contact rating(max.): 30V/1A resistive
****
ENVIRONMENT| WORKING TEMP.| -20 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)
VIBRATION| Component : 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, and Z axes; Mounting: Compliance to IEC60068-2-6
****
SAFETY & EMC **(Note 4)| SAFETY STANDARDS| Ul508, UL62368-1, TUV BS EN/EN62368-1, Class I, Div. 2 Group A, B, C, D Hazardous Locations T4, EAC TP TC 004, BSMI CNS14336-1, AS/NZS 60950.1, IS13252(Part1)/IEC60950-1(except 48V) approved
WITHSTAND VOLTAGE| I/P-O/P:3KVAC  I/P-FG:2KVAC  O/P-FG:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION| Compliance to BS EN/EN55032 (CISPR32), BS EN/EN61204-3 Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020, CNS13438 Class B


EMC IMMUNITY

| Compliance to BS EN/EN61000-4-2, 3, 4, 5, 6, 8, 11, BS EN/EN55035, BS EN/EN61000-6-2, BS EN/EN61204-3, heavy industry level, EAC TP TC 020


OTHERS

| MTBF| 2355.2K hrs min.       Telcordia SR-332 (Bellcore); 489.9K hrs min.        MIL-HDBK-217F (25℃)
DIMENSION| 4090100mm (WHD)
PACKING| 0.33Kg; 42pcs/14.8Kg/0.82CUFT
NOTE| 1.  All parameters NOT specially mentioned are measured at 230VAC input, rated load, and 25℃ of ambient temperature.

2.  Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.

3.  Tolerance: includes set up tolerance, line regulation, and load regulation.

4.  The power supply is considered a component that will be installed into the final equipment. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on https://www.meanwell.com//Upload/PDF/EMI statement en.pdf )

5.  Length of set up time is measured at the first cold start. Turning ON/OFF the power supply may lead to an increase in the set-up time.

6.  The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitudes higher than 2000m(6500ft).

※ Product Liability Disclaimer For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Mechanical Specification

Case No.962A Unit: mm

Block Diagram

DC OK Relay Contact

Contact Close PSU turns on / DC OK.
Contact Open PSU turns off / DC fails.
Contact Ratings (max.) 30V/1A resistive load.

Derating Curve

Output Derating VS Input Voltage

GTIN CODE

MW Search: https://www.meanwell.com/serviceGTIN.aspx

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

MEAN WELL User Manuals

Related Manuals