MEAN WELL RID-125 Series 125W Dual Output Switching Power Supply User Guide

June 3, 2024
MEAN WELL

MEAN WELL RID-125 Series 125W Dual Output Switching Power Supply

MEAN WELL RID-125 Series 125W-Dual-Output-Switching-Power-Supply-FIG-
\(2\)

Features

  • Isolated output &GND for CH1,CH2
  • AC input range selectable by switch
  • Withstand 300VAC surge input for 5 seconds
  • Protections: Short circuit/Overload/ Over voltage
  • All using 105C long life electrolytic capacitors
  • Withstand 5G vibration test
  • LED indicator for power on
  • 100% full load burn-in test
  • High realibility
  • 3 years warranty

GTIN CODE

MW Search : https://www.meanwell.com/serviceGTIN.aspx

SPECIFICATION

MODEL RID-125-1224 RID-125-1248 RID-125-2448

OUTPUT

| OUTPUT NUMBER| CH1| CH2| CH1| CH2| CH1| CH2
DC VOLTAGE| 12V| 24V| 12V| 48V| 24V| 48V
RATED CURRENT| 3.7A| 3.7A| 2.3A| 2.3A| 2A| 2A
CURRENT RANGE Note.3| 0 ~ 7A| 0 ~ 5A| 0~ 7A| 0 ~ 2.5A| 0 ~ 4A| 0 ~ 2.5A
RATED POWER Note.6| 133.2W| 138W| 144W
RIPPLE & NOISE (max.) **Note.2| 120mVp-p| 200mVp-p| 120mVp-p| 240mVp-p| 200mVp-p| 240mVp-p
VOLTAGE ADJ. RANGE| CH1: 11.4 ~ 13.2V| CH1: 11.4 ~ 13.2V| CH1: 22.8 ~ 26.4V
VOLTAGE TOLERANCE Note.3| ±2.0%| ±8.0%| ±2.0%| ±8.0%| ±1.0%| ±6.0%
LINE REGULATION Note.4| ±0.5%| ±1.0%| ±0.5%| ±1.0%| ±0.5%| ±1.0%
LOAD REGULATION Note.5| ±1.0%| ±5.0%| ±1.0%| ±5.0%| ±1.0%| ±5.0%
SETUP, RISE TIME| 500ms, 20ms/230VAC           1200ms, 30ms/115VAC at full load
HOLD UP TIME (Typ.)**| 36ms/230VAC           30ms/115VAC at full load

INPUT

| VOLTAGE RANGE| 88 ~ 132VAC / 176 ~ 264VAC selected by switch 248 ~ 373VDC(300VAC peak 5sec. No damage)
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY(Typ.)| 85%| 85%| 86%
AC CURRENT (Typ.)| 3A/115VAC          2A/230VAC
INRUSH CURRENT (Typ.)| COLD START 50A/230VAC
LEAKAGE CURRENT| <2mA / 240VAC

PROTECTION

| OVERLOAD| 110 ~ 150% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
OVER VOLTAGE| CH1: 13.8 ~ 16.2V| CH1: 13.8 ~ 16.2V| CH1: 27.6 ~ 32.4V
Protection type : Hiccup mode, recovers automatically after fault condition is removed

ENVIRONMENT

| WORKING TEMP.| -20 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)on CH1 output
VIBRATION| 10 ~ 500Hz, 5G 10min./1cycle, period for 60min. each along X, Y, Z axes

SAFETY & EMC

(Note 7)

| SAFETY STANDARDS| UL62368-1, TUV BS EN/EN62368-1, EAC TP TC 004 approved
WITHSTAND VOLTAGE| I/P-O/P:3KVAC  I/P-FG:2KVAC  O/P-FG:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION| Compliance to BS EN/EN55032 (CISPR32) Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020
EMC IMMUNITY| Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN61000-6-2 (BS EN/EN50082-2), heavy industry level, EAC TP TC 020

OTHERS

| MTBF| 2755.4K hrs min.      Telcordia SR-332 (Bellcore) ; 425.8K hrs min.    MIL-HDBK-217F (25℃)
DIMENSION| 1999838mm (LWH)
PACKING| 0.7Kg; 20pcs/15Kg/0.85CUFT
NOTE|

  1. All parameters NOT SpECially mentioned are measured at 230VAC Input, rated load and 25 of ambient temperature.

  2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.

  3. Tolerance: includes set up tolerance, line regulation and load regulation.(ln order to meet tolerance, it is recommended that CH1 load > 5% rated current.)

  4. Line regulation is measured from low line to high line at rated load.

  5. Load regulation is measured from 20% to 100% rated load, and other output at 60% rated load.

  6. Each output can work within current range. But total output power can’t exceed rated output power.

  7. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
    a 360mm360mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to
    perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com)

  8. Length of set up time is measured at cold first start. Turning ON/OFF the power supply very quickly may lead to increase of the set up time.

  9. The ambient temperature derating of 3.5 C/1000m with fanless models and of 5C/1000m with fan models for operating altitude higher than 2000m(6500ft)
    Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Features

  • Isolated output & GND for CH1,CH2
  • AC input range selectable by switch
  • Withstand 300VAC surge input for 5 seconds
  • Protections: Short circuit/ Overload /Over voltage
  • 170 % peak load for CH1
  • All using 105C long life electrolytic capacitors
  • Withstand 5G vibration test
  • LED indicator for power on
  • 100% full load burn-in test
  • High realibility
  • 3 years warranty

GTIN CODE

MW Search : https://www.meanwel.com/service.G TIN.aspx

SPECIFICATION

MODEL RID-125-1205 RID-125-2405






OUTPUT

| OUTPUT NUMBER| CH1| CH2| CH1| CH2
DC VOLTAGE| 12V| 5V| 24V| 5V
RATED CURRENT| 9.2A| 3A| 4.6A| 3A
CURRENT RANGE Note.6| 0 ~ 10.5A| 0 ~ 3A| 0 ~ 5.3A| 0 ~ 3A
PEAK LOAD Note.9| 15.6A| 3A| 7.8A| 3A
RATED POWER| 125.4W| 125.4W
RIPPLE & NOISE (max.) **Note.2| 120mVp-p| 80mVp-p| 120mVp-p| 80mVp-p
VOLTAGE ADJ. RANGE| CH1: 11.4 ~ 13.2V| CH1: 22.8 ~ 26.4V
VOLTAGE TOLERANCE Note.3| ±2.0%| ±3.0%| ±2.0%| ±3.0%
LINE REGULATION Note.4| ±0.5%| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION Note.5| ±1.0%| ±2.0%| ±1.0%| ±2.0%
SETUP, RISE TIME| 500ms, 20ms/230VAC           1200ms, 30ms/115VAC at full load
HOLD UP TIME (Typ.)**| 35ms/230VAC           30ms/115VAC at full load



INPUT

| VOLTAGE RANGE| 88 ~ 132VAC / 176 ~ 264VAC selected by switch 248 ~ 373VDC(300VAC peak 5sec., no damage)
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY(Typ.)| 80%| 83%
AC CURRENT (Typ.)| 3A/115VAC          2A/230VAC
INRUSH CURRENT (Typ.)| COLD START 50A/230VAC
LEAKAGE CURRENT| <2mA / 240VAC


PROTECTION

| OVERLOAD| >165% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
OVER VOLTAGE| CH1: 13.8 ~ 16.2V| CH1: 27.6 ~ 32.4V
Protection type : Hiccup mode, recovers automatically after fault condition is removed



ENVIRONMENT

| WORKING TEMP.| -25 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)on CH1 output
VIBRATION| 10 ~ 500Hz, 5G 10min./1cycle, period for 60min. each along X, Y, Z axes


SAFETY & EMC

(Note 7)

| SAFETY STANDARDS| UL62368-1, TUV BS EN/EN62368-1, EAC TP TC 004 approved
WITHSTAND VOLTAGE| I/P-O/P:3KVAC  I/P-FG:2KVAC  O/P-FG:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION| Compliance to BS EN/EN55032 (CISPR32) Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020
EMC IMMUNITY| Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN61000-6-2 (BS EN/EN50082-2), heavy industry level, EAC TP TC 020


OTHERS

| MTBF| 218.2Khrs min.       MIL-HDBK-217F (25℃)
DIMENSION| 1999838mm (LWH)
PACKING| 0.7Kg; 20pcs/15Kg/0.85CUFT
NOTE|

  1. All parameters NOT SpECially mentioned are measured at 230VAC Input, rated load and 25 of ambient temperature.

  2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.

  3. Tolerance: includes set up tolerance, line regulation and load regulation.(ln order to meet tolerance, it is recommended that CH1 load > 5% rated current.)

  4. Line regulation is measured from low line to high line at rated load.

  5. Load regulation is measured from 20% to 100% rated load, and other output at 60% rated load.

  6. Each output can work within current range. But total output power can’t exceed rated output power.

  7. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on
    a 360mm360mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to
    perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com)

  8. Length of set up time is measured at cold first start. Turning ON/OFF the power supply very quickly may lead to increase of the set up time.

  9. The ambient temperature derating of 3.5 C/1000m with fanless models and of 5C/1000m with fan models for operating altitude higher than 2000m(6500ft)
    Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

**Mechanical Specification

MEAN WELL RID-125 Series 125W-Dual-Output-
Switching-Power-Supply-FIG- \(4\)**

**Block Diagram

MEAN WELL RID-125 Series 125W-Dual-Output-Switching-
Power-Supply-FIG- \(5\)**

**Derating Curve

MEAN WELL RID-125 Series 125W-Dual-Output-Switching-
Power-Supply-FIG- \(6\)**

Static Characteristics

File Name: RID-125-SPEC  2022-09-20

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

MEAN WELL User Manuals

Related Manuals