Product Information

Specifications

  • Product Name: 10W Single Output Industrial DIN Rail Power Supply
  • Series: MDR-10
  • GTIN CODE: [Insert GTIN Code]
  • Features:
    • Universal AC input/Full range
    • Protections: Short circuit / Overload / Over voltage
    • Cooling by free air convection
    • Can be installed on DIN rail TS-35/7.5 or 15
    • Built-in DC OK active signal LED indicator for power on
    • No load power consumption

Product Usage Instructions

Installation

  1. Ensure the power supply is suitable for your application voltage.
  2. Mount the power supply on a compatible DIN rail TS-35/7.5 or 15 securely.
  3. Connect the AC input to the power supply following the provided guidelines.
  4. Connect the load to the output terminals respecting polarity.
  5. Check all connections before applying power.

Operation

  1. Apply power to the unit and verify that the DC OK signal LED indicator lights up.
  2. Monitor the unit for proper operation and check for any abnormal behavior.
  3. In case of overload or short circuit, disconnect power immediately and troubleshoot.

Maintenance

  • Regularly check for dust accumulation and clean the unit using a dry cloth.
  • Ensure proper ventilation around the unit for efficient cooling.

FAQ

  • Q: What should I do if the DC OK signal LED does not light up?
  • A: Check the input connections and ensure the AC input is within the specified range. Verify the load connections and polarity.
  • Q: Can this power supply be used in outdoor environments?
  • A: It is recommended to use this power supply in indoor environments to protect it from environmental elements.

Features

  • Universal AC input/Full range
  • Protections: Short circuit / Overload / Over voltage
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 or 15
  • Built in DC OK active signal
  • LED indicator for power on
  • No load power consumption<0.75W
  • 100% full load burn-in test
  • 3 years warranty

GTIN CODE

SPECIFICATION

MODEL MDR-10-5 MDR-10-12 MDR-10-15 MDR-10-24
OUTPUT DC VOLTAGE 5V 12V 15V
RATED CURRENT 2A 0.84A 0.67A 0.42A
CURRENT RANGE 0 ~ 2A 0 ~ 0.84A 0 ~ 0.67A 0 ~ 0.42A
RATED POWER 10W 10W 10W 10W
RIPPLE & NOISE (max.) **Note.2** 80mVp-p 120mVp-p 120mVp-p 150mVp-p
VOLTAGE TOLERANCE Note.3 ±5.0% ±3.0% ±3.0% ±2.0%
LINE REGULATION ±1.0% ±1.0% ±1.0% ±1.0%
LOAD REGULATION ±5.0% ±3.0% ±3.0% ±2.0%
SETUP, RISE TIME Note.5 500ms, 30ms/230VAC           1000ms,

30ms/115VAC at full load
HOLD UP TIME (Typ.)| 120ms/230VAC           25ms/115VAC at full load
INPUT| VOLTAGE RANGE| 85 ~ 264VAC           120 ~ 370VDC
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 77%| 81%| 81%| 84%
AC CURRENT (Typ.)| 0.33A/115VAC           0.21A/230VAC
INRUSH CURRENT (Typ.)| COLD START 35A/115VAC           70A/230VAC
LEAKAGE CURRENT| <1mA / 240VAC
PROTECTION| ****

OVERLOAD

| Above 105% rated output power
Protection type: Hiccup mode, recovers automatically after fault condition is removed


OVERVOLTAGE

| 5.75 ~ 6.75V| 13.8 ~ 16.2V| 17.25 ~ 20.25V| 27.6 ~ 32.4V
Protection type: Shut down o/p voltage, re-power on to recover
FUNCTION| DC OK ACTIVE SIGNAL (max.)| 3.75 ~ 6V / 50mA| 9 ~ 13.5V / 40mA| 11.5 ~ 16.5V / 40mA| 18 ~ 27V / 20mA
ENVIRONMENT| WORKING TEMP.| -20 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)
VIBRATION| Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, and Z axes; Mounting: Compliance to IEC60068-2-6
SAFETY & EMC **(Note 4)| SAFETY STANDARDS| Ul508, TUV BS EN/EN62368-1, EAC TP TC 004, BSMI CNS15598-1, AS/NZS 62368.1, IS13252(Part1)/IEC60950-1 approved
WITHSTAND VOLTAGE| I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION| Compliance to BS EN/EN55032 (CISPR32), BS EN/EN61204-3 Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020, CNS15936 Class B
EMC IMMUNITY| Compliance to BS EN/EN61000-4-2, 3, 4, 5, 6, 8, 11, BS EN/EN55035, BS EN/EN61000-6-1, BS EN/EN61204-3, light industry level, EAC TP TC 020
OTHERS| MTBF| 3334.7K hrs min.       Telcordia SR-332 (Bellcore); 584.0K hrs min.       MIL-HDBK-217F (25℃)
DIMENSION| 22.590100mm (WHD)
PACKING| 0.15Kg; 72pcs/11.8Kg/1.04CUFT
NOTE**| 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load, and 25℃ of ambient temperature.

2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μF & 47μF parallel capacitor.

3. Tolerance: includes set up tolerance, line regulation, and load regulation.

4. The power supply is considered a component that will be installed into the final equipment. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”

(as available on https://www.meanwell.com//Upload/PDF/EMI_statement_en.pdf )

5. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to an increase in the set-up time.

6. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitudes higher than 2000m(6500ft).

※ Product Liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Dimension

Mechanical Specification

Block Diagram

Application of DC OK Active Signal

Derating Curve

Output Derating VS Input Voltage

Documents / Resources

| MEAN WELL MDR-10 Series 10W Single Output Industrial DIN Rail Power Supply [pdf] Owner's Manual
MDR-10-5, MDR-10 Series 10W Single Output Industrial DIN Rail Power Supply, MDR-10 Series, 10W Single Output Industrial DIN Rail Power Supply, Single Output Industrial DIN Rail Power Supply, Output Industrial DIN Rail Power Supply, Industrial DIN Rail Power Supply, DIN Rail Power Supply, Rail Power Supply, Power Supply, Supply
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

MEAN WELL User Manuals

Related Manuals