Circutor line-TCPRS1 Wireless Converter Instructions
- October 27, 2023
- Circutor
Table of Contents
Circutor line-TCPRS1 Wireless Converter
line-TCPRS1
This manual is a line-TCPRS1 installation guide. For further information, please download the full manual from the CIRCUTOR web site: www.circutor.com
|
IMPORTANT!
---|---
The device must be disconnected from its power supply sources (power supply
and measurement) before undertaking any installation, repair or handling
operations on the unit’s connections. Contact the after-sales service if you
suspect that there is an operational fault in the device. The device has been
designed for easy replacement in case of malfunction.
The manufacturer of the device is not responsible for any damage resulting
from failure by the user or installer to heed the warnings and/or
recommendations set out in this manual, nor for damage resulting from the use
of non-original products or accessories or those made by other manufacturers.
DESCRIPTION
The line-TCPRS1 is a gateway designed to convert an RS-485 or RS-232 physical environment to Ethernet and/or Wi-Fi. The device features a Web Server and an app (Android) that uses Bluetooth connectivity, from which the user can completely edit the configuration parameters of the device. The device can be connected via the side bus to the devices of the line range, without the need to cable the communications bus, making it much easier to install. It also has RS-485 and RS-232 communication terminals so that it can be simultaneously connected to other devices not in the line range.
INSTALLATION
The device must be installed on an electric panel or enclosure, attached to a DIN rail (IEC 60715).
|
IMPORTANT!
---|---
Take into account that when the device is connected, the terminals may be
hazardous to the touch, and opening the covers or removing elements may
provide access to parts that are dangerous to the touch. Do not use the device
until it is fully installed.
The device must be connected to a power circuit that is protected with gl (IEC 269) or M type fuses with a rating of 1 to 2 A. It must be fitted with a circuit breaker or equivalent device, in order to be able to disconnect the device from the power supply network. The power and voltage measuring circuit must be connected with cables that have a minimum cross-section of 1mm2. The line-TCPRS1 devices can be connected to other devices in the line range: line- CVM-D32 and the line-M-xxx-xx expansion modules.
|
IMPORTANT!
---|---
Only 2 expansion modules can be directly connect to the right side of the
device. Up to 7 devices can be connected to the right (lineCVM-D32 and line-M
-xxx-xx) in installations that have a line-TCPRS1. View the manuals
M237B01-03-xxx and M239B01-03xxx for further information.
The steps to take to connect the devices are:
-
Remove the protective covers of the expansion connector, which are located on the side of the devices, using a flat-tip screwdriver (Figure 1).
Figure 1 -
Insert the expansion connector and fastening clips into one of the devices (Figure 2).
Figure 2 -
Connect the two devices and fasten them by pushing the front clips down (Figure 3).
Figure 3
Technical features
AC Power supply
Rated voltage| 100 … 264 V~
Frequency| 50 … 60 Hz
Consumption| 3.5 … 7.5 VA
Installation category| 3.5 … 7.5 VA
DC Power supply
Rated voltage| 100 … 300 V⎓
Consumption| 2 … 2.5 W
Installation category| CAT III 300 V
RS-485 interface
Bus| RS-485
Baud rate| 4800 – 9600 – 19200 – 38400 – 57600 – 115200 bps
Data bits| 7 -8
Stop bits| 7 -8
Parity| without – even – odd
RS-232 interface
Bus| RS-232
Baud rate| 4800 – 9600 – 19200 – 38400 – 57600 – 115200
Data bits| 7 -8
Stop bits| 1 -2
Parity| without – even – odd
Ethernet interface
Type| Ethernet 10BaseT – 100BaseTX autodetectable / self-detectable
Connector| RJ45
Protocol| TCP – UDP – Modbus TCP – HTTP (Web server) – REST
Connection mode to Network| DHCP ON/OFF (ON / by default)
Wi-Fi communication
Band| Range : 2.4 … 2.5 GHz)
Standard| IEEE 802.11 b / g , IEEE 802.11 n (hasta / up to 150 Mbps)
Max. Output power| IEEE 802.11 b : 20 dBm
IEEE 802.11 n : 14 dBm
Bluetooth® communication
Protocols| Bluetooth® v4.2 BR/EDR and BLE specification
Radio| NZIF receiver with –97 dBm sensitivity Class-1, class-2 and class-3
transmitter Adaptive Frequency Hopping (AFH) Receiver Sensitivity @30.8% PER
-97 dBm Transmitter RF power control range Min: -12 dBm / Max: +12dBm
User interface
LED| 7 LEDs
Environmental features
Operating temperature| -10ºC… +50ºC
Storage temperature| -20ºC … +70ºC
Relative humidity (non-condensing)| 5 … 95%
Maximum altitude| 2000 m
Protection degree| IP30, Frontal / Front : IP40
Mechanical features
Terminals| | |
9, 11, 19 … 24| 2.5 mm2| ≤ 0.4 Nm, M2.5| flat
Dimensions| 52.5 x 117.85 x 70 mm
Weight| 170 g.
Enclosure| Self-extinguishing V0 plastic
Attachment| DIN rail (1)
Standers
EN 61010-1, EN 61000-6-2, EN 61000-6-4
Minimum recommended distance between DIN rails: 150 mm.
Terminal connections designations
9| Auxiliary power supply
11| Auxiliary power supply
19 (2)| for RS-4232
20 (2)| Rx , RS-232
21 (2)| Tx , RS-232
22 (2)| B- , RS-485
23 (2)| S , for RS-485
24 (2)| A+ , RS-485
Ethernet| Ethernet connection
For the correct operation of serial communications, the RS-485 and RS-232 ports should not be wired at the same time.
Dimension
LEDs
CPU
| Device status
Flashing (White color):
Device powered
WLAN
| Wi-Fi connectivity
ON (Blue color):
Wi-Fi connectivity enabled
LAN
| Ethernet connectivity
ON (Green color):
Ethernet connectivity enabled
Bluetooth| Bluetooth® connectivity
ON (Blue color):
Bluetooth® linked
RX
| RS-485 / RS-232
Flashing (Orange color):
Frame reception
TX
| RS-485 / RS-232
Flashing (Orange color):
Frame delivery
Alarm
| Alarm
ON (Red color):
Frame reception error
Technical service
CIRCUTOR SAT: 902 449 459 (SPAIN) / (+34) 937 452 919 (out of Spain) Vial Sant
Jordi, s/n 08232 – Viladecavalls (Barcelona)
Tel: (+34) 937 452 900 – Fax: (+34) 937 452 914
e-mail : sat@circutor.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>