Circutor line-TCPRS1 Wireless Converter Instructions

October 27, 2023
Circutor

Circutor line-TCPRS1 Wireless Converter

line-TCPRS1

This manual is a line-TCPRS1 installation guide. For further information, please download the full manual from the CIRCUTOR web site: www.circutor.com

|

IMPORTANT!

---|---
The device must be disconnected from its power supply sources (power supply and measurement) before undertaking any installation, repair or handling operations on the unit’s connections. Contact the after-sales service if you suspect that there is an operational fault in the device. The device has been designed for easy replacement in case of malfunction.
The manufacturer of the device is not responsible for any damage resulting from failure by the user or installer to heed the warnings and/or recommendations set out in this manual, nor for damage resulting from the use of non-original products or accessories or those made by other manufacturers.

DESCRIPTION

The line-TCPRS1 is a gateway designed to convert an RS-485 or RS-232 physical environment to Ethernet and/or Wi-Fi. The device features a Web Server and an app (Android) that uses Bluetooth connectivity, from which the user can completely edit the configuration parameters of the device. The device can be connected via the side bus to the devices of the line range, without the need to cable the communications bus, making it much easier to install. It also has RS-485 and RS-232 communication terminals so that it can be simultaneously connected to other devices not in the line range.

INSTALLATION

The device must be installed on an electric panel or enclosure, attached to a DIN rail (IEC 60715).

|

IMPORTANT!

---|---
Take into account that when the device is connected, the terminals may be hazardous to the touch, and opening the covers or removing elements may provide access to parts that are dangerous to the touch. Do not use the device until it is fully installed.

The device must be connected to a power circuit that is protected with gl (IEC 269) or M type fuses with a rating of 1 to 2 A. It must be fitted with a circuit breaker or equivalent device, in order to be able to disconnect the device from the power supply network. The power and voltage measuring circuit must be connected with cables that have a minimum cross-section of 1mm2. The line-TCPRS1 devices can be connected to other devices in the line range: line- CVM-D32 and the line-M-xxx-xx expansion modules.

|

IMPORTANT!

---|---
Only 2 expansion modules can be directly connect to the right side of the device. Up to 7 devices can be connected to the right (lineCVM-D32 and line-M -xxx-xx) in installations that have a line-TCPRS1. View the manuals M237B01-03-xxx and M239B01-03xxx for further information.

The steps to take to connect the devices are:

  1. Remove the protective covers of the expansion connector, which are located on the side of the devices, using a flat-tip screwdriver (Figure 1).
    Figure 1

  2. Insert the expansion connector and fastening clips into one of the devices (Figure 2).
    Figure 2

  3. Connect the two devices and fasten them by pushing the front clips down (Figure 3).
    Figure 3

Technical features

AC Power supply


Rated voltage| 100 … 264 V~
Frequency| 50 … 60 Hz
Consumption| 3.5 … 7.5 VA
Installation category| 3.5 … 7.5 VA

DC Power supply

Rated voltage| 100 … 300 V⎓
Consumption| 2 … 2.5 W
Installation category| CAT III 300 V

RS-485 interface

Bus| RS-485
Baud rate| 4800 – 9600 – 19200 – 38400 – 57600 – 115200 bps
Data bits| 7 -8
Stop bits| 7 -8
Parity|  without – even – odd

RS-232 interface

Bus| RS-232
Baud rate| 4800 – 9600 – 19200 – 38400 – 57600 – 115200
Data bits| 7 -8
Stop bits| 1 -2
Parity| without – even – odd

Ethernet interface

Type| Ethernet 10BaseT – 100BaseTX autodetectable / self-detectable
Connector| RJ45
Protocol| TCP – UDP – Modbus TCP – HTTP (Web server) – REST
Connection mode to Network| DHCP ON/OFF (ON / by default)

Wi-Fi communication

Band| Range : 2.4 … 2.5 GHz)
Standard| IEEE 802.11 b / g , IEEE 802.11 n (hasta / up to 150 Mbps)
Max. Output power| IEEE 802.11 b : 20 dBm

IEEE 802.11 n : 14 dBm

Bluetooth® communication

Protocols| Bluetooth® v4.2 BR/EDR and BLE specification
Radio| NZIF receiver with –97 dBm sensitivity Class-1, class-2 and class-3 transmitter Adaptive Frequency Hopping (AFH) Receiver Sensitivity @30.8% PER -97 dBm Transmitter RF power control range Min: -12 dBm / Max: +12dBm

User interface

LED| 7 LEDs

Environmental features

Operating temperature| -10ºC… +50ºC
Storage temperature| -20ºC … +70ºC
Relative humidity (non-condensing)| 5 … 95%
Maximum altitude| 2000 m
Protection degree| IP30, Frontal / Front : IP40

Mechanical features

Terminals| | |
9, 11, 19 … 24| 2.5 mm2| ≤ 0.4 Nm, M2.5|  flat
Dimensions| 52.5 x 117.85 x 70 mm
Weight| 170 g.
Enclosure| Self-extinguishing V0 plastic
Attachment| DIN rail (1)

Standers

EN 61010-1, EN 61000-6-2, EN 61000-6-4

Minimum recommended distance between DIN rails: 150 mm.

Terminal connections designations

9|  Auxiliary power supply
11|  Auxiliary power supply
19 (2)|  for RS-4232
20 (2)| Rx , RS-232
21 (2)| Tx , RS-232
22 (2)| B- , RS-485
23 (2)| S ,  for RS-485
24 (2)| A+ , RS-485
Ethernet|  Ethernet connection

For the correct operation of serial communications, the RS-485 and RS-232 ports should not be wired at the same time.

Dimension

LEDs


CPU

| Device status
Flashing (White color):
Device powered


WLAN

| Wi-Fi connectivity
ON (Blue color):
Wi-Fi connectivity enabled


LAN

| Ethernet connectivity
ON (Green color):
Ethernet connectivity enabled
Bluetooth| Bluetooth®   connectivity
ON (Blue color):
Bluetooth® linked


RX

| RS-485 / RS-232
Flashing (Orange color):
Frame reception


TX

| RS-485 / RS-232
Flashing (Orange color):
Frame delivery


Alarm

| Alarm
ON (Red color):
Frame reception error

Technical service

CIRCUTOR SAT: 902 449 459 (SPAIN) / (+34) 937 452 919 (out of Spain) Vial Sant Jordi, s/n 08232 – Viladecavalls (Barcelona)
Tel: (+34) 937 452 900 – Fax: (+34) 937 452 914
e-mail : [email protected]

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals