Circutor CEM-C12 Multifunctional Energy Meter Instruction Manual

June 4, 2024
Circutor

circutor-logo

Circutor CEM-C12 Multifunctional Energy Meter

Circutor-CEM-C12-Multifunctional-Energy -Meter-product-
image

SAFETY PRECAUTIONS

Follow the warnings described in this manual with the symbols shown below.

DANGER
Warns of a risk, which could result in personal injury or material damage.

ATTENTION
Indicates that special attention should be paid to a specific point.

If you must handle the unit for its installation, start-up or maintenance, the following should be taken into consideration:

Incorrect handling or installation of the unit may result in injury to personnel as well as damage to the unit. In particular, handling with voltages applied may result in electric shock, which may cause death or serious injury to personnel. Defective installation or maintenance may also lead to the risk of fire.

Read the manual carefully prior to connecting the unit. Follow all installation and maintenance in-structions throughout the unit’s working life. Pay special attention to the installation standards of the National Electrical Code.

Refer to the instruction manual before using the unit
In this manual, if the instructions marked with this symbol are not respected or carried out correctly, it can result in injury or damage to the unit and /or installations.

CIRCUTOR, SA reserves the right to modify features or the product manual without prior notification.

DISCLAIMER

CIRCUTOR,   SA reserves the right to make modifications to the device or the unit specifications set out in this instruction manual without prior notice.
CIRCUTOR, SA on its web site, supplies its customers with the latest versions of the device specifications and the most updated manuals.

www.circutor.com

CIRCUTOR, recommends using the original cables and accessories that are supplied with the device.

REVISION LOG

Table 1: Revision log

Date Revision Description
03/22 M336B01-03-21A Initial Version
SYMBOLS
Symbol Description
CE In compliance with the relevant European directive.
**** Device covered by European directive 2012/19/EC. At the end of its

useful life, do not leave the unit in a household waste container. Follow local regulations

on electronic equipment recycling.

~| AC current

VERIFICATION UPON RECEPTION

Check the following points upon receiving the device:

  • The device meets the specifications described in your order.
  • The device has not suffered any damage during transport.
  • Perform an external visual inspection of the device prior to switching it on.
  • Check that it has been delivered with the following:
    – An installation guide,

If any problem is noticed upon reception, immediately contact the transport com-pany and/or CIRCUTOR’s after-sales service.

PRODUCT DESCRIPTION

The CEM-C12 static single-phase energy meter measures class 1 (IEC 62053-21) / class B (EN50470), with multifunction, RS-485 communications and DIN rail standard installations. It is the ideal solution for residential and commercial installations.Circutor-CEM-C12-Multifunctional-Energy -Meter-
product-image

The device features:

  • Only 18 mm wide, can up to 100A.
  • RS-485 communication, protocol: IEC1107 or Modbus-TRU Mode.
  • Device has 3.6V Lithium battery. The precision of RTC is better that 0.5s/day.
  • Blue LCD backlight allows the device to be read in low light conditions.
  • 1 key, to move between the different display screens and be able to configure the communications.

DEVICE INSTALLATION

PRELIMINARY RECOMMENDATIONS

In order to use the device safely, it is critical that individuals who handle it follow the safety measures set out in the standards of the country where it is being used, use the necessary personal protective equipment, and pay attention to the various warnings indicated in this instruction manual.

The CEM-C12 device must be installed by authorised and qualified staff.

The measuring systems switched off before handling, altering the connections or replacing the device. It is dangerous to handle the unit while it is powered.

Also, it is critical to keep the cables in perfect condition in order to avoid accidents, personal injury and damage to installations.

The manufacturer of the device is not responsible for any damage resulting from failure by the user or installer to observe the warnings and/or recommendations set out in this manual, nor for damage resulting from the use of non-original products or accessories or those made by other manufacturers.

If an anomaly or malfunction is detected in the device, do not use the device to take any measurements.

Inspect the work area before taking any measurements. Do not take measurements in dangerous areas or where there is a risk of explosion.

Disconnect the device from the power supply before maintaining, repairing or handling the device’s connections.
Please contact the after-sales service if you suspect that there is an operational fault in the device.

INSTALLATION

Terminals, opening covers or removing elements can expose parts that are hazardous to the touch while the device is powered. Do not use the device until it is fully installed.

Installation instruction:
  1. Choose 35mm standard DIN rail (the length is confirmed by yourself), fixed them in the location which are waiting for installation.

  2. Push down the clip under the bottom of the meter for a gear, see Figure 1
    Figure 1:Push down the clip

  3. Put the meter into the DIN rail as per Figure 2, then push up the clip for a gear, install meter to the DIN rail, see Figure 3.Circutor-CEM-C12-Multifunctional-Energy -Meter-05 Figure 2:Put the meter into the DIN railCircutor-CEM-C12-Multifunctional-Energy -Meter-06 Figure 3: Install meter to the DIN rail

  4. Making the connection according to the wiring diagram.

  5. After connection, use lead sealing to seal terminal cover.

DEVICE TERMINALS

Table 3: List of CEM-C12 terminals

Device terminals

1 : L , Input, connected to the mains phase| B-: B-, RS-485 connection
3: LOAD , Output| S: S, RS-485 connection
N: N , Input, connected to neutral| A+: A+, RS-485 connection

Circutor-CEM-C12-Multifunctional-Energy -Meter-07Figure 4: Terminals of the CEM-C12

Note: The Neutral wire can be connected to one of N ports or both.
Note: If RS-485 installation does not have S port, it is not necessary to connect it.

CONNECTION DIAGRAM

Figure 5: Connection diagram, CEM-C12

OPERATION

The CEM-C12 measures in the 4 quadrants (consumption and generation ).Circutor-CEM-C12-Multifunctional-Energy -Meter-09 Figure 6: Sign convention

Table 4: CEM-C12 Measurement parameters

Parameter Display RS-485
Instantaneous Maximum Minimum
Voltage ü ü
Current ü ü
Frequency ü ü
Active Power ü ü
Reactive Power ü ü
Inductive Reactive Power ü
Capacitive Reactive Power ü
Apparent Power ü ü
Power Factor ü ü
Maximum Active Power Demand ü
Active Energy Consumed ü
Active Energy Generated ü
Total Active Energy ü ü
Inductive Reactive Energy Consumed ü ü
Inductive Reactive Energy Generated ü
Capacitive Reactive Energy Consumed ü
Capacitive Reactive Energy Generated ü
Reactive Energy Consumed ü
Reactive Energy Generated ü
Total Reactive Energy ü

Maximum demand
The maximum demand is the average instantaneous power over a specific time interval, usually 15 minutes. There are several ways to calculate this parameter:

Fixed Window (by block)
This is the calculation of maximum demand in a specific interval (usually every 15 minutes). Once the number is calculated, the value is saved and a new calculation for the next 15 minutes begins. The result would be 4 values per hour.

Circutor-CEM-C12-Multifunctional-Energy -Meter-10 Figure 7: Fixed Window.

Figure 8: Sliding Window.

The CEM-C12 calculates the Maximum demand with a fixed window and a 15-minute integration period

KEYBOARD FUNCTIONS

The CEM-C12 has one key to move around the different screens and configure the communications (Figure 9). Figure 9: CEM-C12, description

DISPLAY

The device has an LCD where all parameters are displayed (Figure 9).

LED INDICATORS

The device has one verification LED, to verify the active energy The weight of the LED is 1000 imp/kWh (Figure 9).

DISPLAY

The data can be displayed through 2 methods:

  • Automatically, the device automatically switches screens every 5 seconds.
  • Pressing the key.
Screen Parameters

123450
KWH| Total Active Energy (consumed + generated) (kWh)
1200
kVArh| Inductive Reactive Energy consumed (kVArh)
2300V| Voltage (V)
005.0A| Current (A)
F 50.00| Frequency (Hz)
PF 1.00| Power factor (cos Φ)
11.50
kW| Active power (kW)
00.00kVAr| Reactive power (kVAr)
115.0 kVA| Apparent power (kVA)

CONFIGURING RS-485 COMMUNICATIONS

To go into the communications configuration menu, press > 5 seconds while in any display screen.

Figure 10: Communications menu

If the key is not pressed for 10 seconds, the device skips to the display screens.

PERIPHERAL NUMBER

This screen enables peripheral number configuration. To go into the configuration screen, press > 3 seconds.Circutor-CEM-C12-Multifunctional-
Energy -Meter-14Press  to change the digit value.
Press > 3 seconds to change digits.
Press > 6 seconds to save the change. The screen shown in Figure 11 indicates that the changes have been saved correctly.

Figure 11:Done screen

Configuration values

Table 6: Configuration values: Peripheral nº

| Peripheral
---|---
Minimum value| 1
Maximum value| 247

Press to skip to the next programming step.

MODBUS BAUD RATE

This screen is used to configure the Baud Rate. Press > 3 seconds to open the configuration screen.

Circutor-CEM-C12-Multifunctional-Energy -Meter-16

Press to change options.
Press > 6 seconds to save the change. The screen shown in Figure 11 indicates that the changes have been saved correctly.

Configuration values

Table 7:Configuration values: Baud rate

| Baud Rate
---|---
Possible values| 9600| 9600 bps
19200| 19200 bps
38400| 38400 bps

Press to skip to the next programming step.

DATA BITS

This screen shows the number of data bits. Press > 3 seconds to open the configuration screen.

Circutor-CEM-C12-Multifunctional-Energy -Meter-17

Note: This parameter cannot be modified.
Press to skip to the next programming step.

PARITY

This screen is used to configure the parity. Press > 3 seconds to open the configuration screen.Circutor-CEM-C12-Multifunctional-Energy
-Meter-18Press  to change options.
Press > 6 seconds to save the change. The screen shown in Figure 11 indicates that the changes have been saved correctly.

Configuration values

Table 8: Configuration values: Parity

| Parity
---|---
Possible values| MOME| No parity
Odd| Odd parity
EUEM| Even parity

Press  to skip to the next programming step.

STOP BITS

This screen is used to configure the number of stop bits. Press > 3 seconds to open the configuration screen.

Circutor-CEM-C12-Multifunctional-Energy -Meter-19Press to change options.

Press > 6 seconds to save the change. The screen shown in Figure 11 indicates that the changes have been saved correctly.

Configuration values

Table 9: Configuration values: Stop bits

| Stop bits
---|---
Possible values| 1| 1 stop bit
2| 2 stop bit

Press  to skip to the next programming step.

RS-485 COMMUNICATIONS

The CEM-C12 has one RS-485 communications port to view the measurement data and configure the devices. The visualization and configuration can also be done through the CIRCUTOR PowerStudio software.

Note: Default values of RS-485 communication: No. of peripheral 1, 9600 bps, No parity, 8 data bits and 1 stop bit.

MODBUS PROTOCOL

In the Modbus protocol, the CEM-C12 device uses the RTU (Remote Terminal Unit) mode.
The Modbus functions implemented in the device are as follows:

Function 0x03: Reading integer registers
Function 0x10: Writing multiple registers

READING EXAMPLE:
Function 0x03
Question: Voltage value

Address| Function| Initial register| No   of registers| CRC
---|---|---|---|---
01| 03| 0000| 0002| C40B

Address: 01, Peripheral number: 1 in decimals.
Function: 03, Read function.
Initial Register: 0000, register on which the reading will start. (Modbus address).
No of registers: 0002, number of registers read.
CRC: C40B, CRC Character.

Response:

Address| Function| No of Bytes| Register no 1| Register no 2| CRC
---|---|---|---|---|---
01| 03| 02| 0000| 091F| 359A

Address: 01, Responding peripheral number: 10 in decimals.
Function: 03, Read function.
No of bytes: 02, No. of bytes received.
Register: 091F, value of the voltage :0000091F : 2335 → 233.5V CRC: 359A, CRC Character.

WRITING EXAMPLE: Function 0x10.
Question: Modify the Modbus baud rate to 9600 bps

Address| Function| Initial Register| No of Registers| No of Bytes| Value| CRC
---|---|---|---|---|---|---
01| 10| 0064| 0001| 02| 0004| xxxx

Address: 01, Peripheral number: 1 in decimals.
Function: 10, Writing function.
Initial Register: 0064, Address of the Baud rate parameter. No of registers: 0001, number of registers write.
No of bytes: 02, number of bytes write.
Value: 0004, 0004 → 9600 bps.
CRC: xxxx, CRC Character.

MODBUS COMMANDS

Note: The waiting time of a Modbus query can exceed 200 ms, depending on the number of registers requested.

All the addresses of Modbus memory are in Hexadecimal.

Table 10: Modbus memory map (Table 1)

Parameter Function Modbus address Units
Instantaneous Maximum Minimum
Voltage 03 00 – 01 32 – 33
Current 03 02 – 03 34 – 35
Active Power 03 04 -05 36 – 37
Reactive Power 03 06 – 07 38 – 39
Inductive Reactive Power 03 08 – 09 3A – 3B
Capacitive Reactive Power 03 0A – 0B 3C – 3D
Apparent Power 03 0C – 0D 3E – 3F
Power Factor 03 0E – 0F 40 – 41
Maximum demand of the Active Power 03 10 – 11 42 – 43

Table 11: Modbus memory map (Table 2)

Parameter Function Modbus address Units
Consumed Active Energy Total 03 12 – 13 kWh x 100
Consumed Inductive Reactive Energy Total 03 14 – 15 kvarh x 100
Consumed Capacitive Reactive Energy Total 03 16 – 17 kvarh x 100
Consumed Reactive Energy Total 03 18 -19 kvarh x 100
Consumed Active Energy Partial 03 1A – 1B kWh x 100
Consumed Inductive Reactive Energy Partial 03 1C – 1D kvarh x 100
Consumed Capacitive Reactive Energy Partial 03 1E – 1F kvarh x 100
Consumed Reactive Energy Parcial 03 20 – 21 kvarh x 100
Generated Active Energy Total 03 22 – 23 kWh x 100
Generated Inductive Reactive Energy Total 03 24 – 25 kvarh x 100
Generated Capacitive Reactive Energy Total 03 26 – 27 kvarh x 100
Generated Reactive Energy Total 03 28 – 29 kvarh x 100
Generated Active Energy Partial 03 2A – 2B kWh x 100
Generated Inductive Reactive Energy Partial 03 2C – 2D kvarh x 100
Generated Capacitive Reactive Energy Partial 03 2E – 2F kvarh x 100
Generated Reactive Energy Partial 03 30 – 31 kvarh x 100
Frequency 03 5A Hz x 100
Parameter Function Modbus address Units
--- --- --- ---
Total active Energy (Consumed + Generated) 03 5B – 5C kWh x 100
Total reactive energy (Consumed + Generated) 03 5D – 5E kvarh x 100

Table 12: Modbus memory map (Table 3)

Parameter Function Modbus address
Reset of maximum values 05 5F
Reset of minimum values 05 60
Maximum Demand Reset 05 61
Reset of Partial Energies 05 62
Total reset (Maximum and minimum values, Maximum demand and Partial Energies)
05 63

Table 13: Modbus memory map (Table 4)

Parameter Modbus address Function Data format
Date and time 56 … 59 03 / 10 YY YY MM DD WW hh mm ss (1)
Serial number 69 … 6C 04

(1)Data format :

Table 14: Data format

Parameter Data format Description



Date and time

| YY YY (decimal value)| Year
MM (decimal value)| Month
DD (decimal value)| Day
WW (decimal value)| Weekday number
hh (decimal value)| Hour
mm (decimal value)| Minutes
ss (decimal value)| Seconds

Table 15: Modbus memory map (Table 5)

Parameter| Modbus address| Function| Default values| Data format
---|---|---|---|---
Baud Rate| 64| 04 / 10| 04| 04: 9600 bps|
05: 19200 bps, 06: 38400 bps
ID (peripheral number)| 65| 04 / 10| 1| 1 – 247
Parity| 66| 04 / 10| 0| 0: none, 1: odd, 2: even
Data bits| 67| 04| 0| 0: 8 bits
Stop bits| 68| 04 / 10| 0| 0: 1 stop bit, 1: 2 stop bit

TECHNICAL FEATURES

Power supply

Mode| Self-powered

Voltage Measurement

Connection| Single-phase
Reference voltages| 230 V ~
Frequency| CEM-C12| 50 / 60 Hz
CEM-C12-MID| 50 Hz
Power consumption| ≤ 10 VA, ≤ 0.4 Wh

Current measurement

Current| 0.25 … 5 A
Maximum current (Imax)| 100 A
Starting current| 0.004 Ib

Accuracy

Accuracy| CEM-C12| Class 1 (IEC 62053-21)
CEM-C12-MID| Class B (EN50470)

RS-485 Communications

Bus| RS-485
Protocol| Modbus RTU
Baud rate| 9600 – 19200 – 38400

User interface

Display| LCD
Maximum counter value| 99999.9 kWh
Keys| 1 key
LED (kWh)| 1000 imp/kWh ( width: 90 ms)

Environmental features

Operating temperature| CEM-C12| -20ºC… +65ºC
CEM-C12-MID| -25ºC… +55ºC
Relative humidity (maximum value)| 95%
Average humidity value of year| 75%

Mechanical features

Dimensions ( Figure 12)| 90 x 18 x 72 mm
Weight| 0.10 kg
Enclosure| ABS, PC alloy material
Protection degree| IP 51 (indoor)
Connections| | |
RS-485 (B-, S, A+)| ≤ 1.5 mm2| 0.4 Nm| Flat, PH2
Neutral (N)| ≤ 1.5 mm2| 0.4 Nm| Flat, PH2
Measure (L, LOAD)| ≤ 22 mm2| ≤ 3 Nm| Flat, PZ2

Standards

Electrical energy metering equipment (AC) Particular requirements Part 21: Static active energy meters (classes 1 and 2)| IEC 62053-21

(Continuation) Standards

Electricity metering equipment (AC) – General requirements, tests and test conditions — Part 11: Metering equipment| IEC 62052-11
Electricity metering equipment (ac) — Part 1: General requirements, tests and test conditions – Metering equipment (class indexes A, B and C)| EN 50470-1
Electricity metering equipment (ac) — Part 3: Particular requirements – Static meters for active energy (class indexes A, B and C)| EN 50470-3
CEM-C12-MID
MID (Measuring Instruments Directive):

EU Directive 2014/32/EU on Measuring Instruments Annex II, Module B

Circutor-CEM-C12-Multifunctional-Energy -Meter-28 Figure 12: Dimensions of the CEM-C12

MAINTENANCE AND TECHNICAL SERVICE

In the case of any query in relation to device operation or malfunction, please contact the CIRCUTOR, SA Technical Support Service.

Technical Assistance Service
Vial Sant Jordi, s/n, 08232 – Viladecavalls (Barcelona)
Tel: 902 449 459 ( España) / +34 937 452 919 (outside of Spain)
email: [email protected]

GUARANTEE

CIRCUTOR guarantees its products against any manufacturing defect for two years after the delivery of the units.
CIRCUTOR will repair or replace any defective factory product returned during the guarantee period.

  • No returns will be accepted and no unit will be repaired or replaced if it is not accompanied by a report indicating the defect detected or the reason for the return.
  • The guarantee will be void if the units has been improperly used or the storage, installation and maintenance instructions listed in this manual have not been followed. “Improper usage” is defined as any operating or storage condition contrary to the national electrical code or that surpasses the limits indicated in the technical and environmental features of this manual.
  • CIRCUTOR accepts no liability due to the possible damage to the unit or other parts of the installation, nor will it cover any possible sanctions derived from a possible failure, improper installation or “improper usage” of the unit. Consequently, this guarantee does not apply to failures occurring in the following cases:
    • Over voltages and/or electrical disturbances in the supply;
    • Water, if the product does not have the appropriate IP classification;
    • Poor ventilation and/or excessive temperatures;
    • Improper installation and/or lack of maintenance;
    • Buyer repairs or modifications without the manufacturer’s authorization.

CE CERTIFICATE

EU DECLARATION OF CONFORMITY

This declaration of conformity is issued under the sole responsibility of CIRCUTOR with registered address at Vial Sant Jordi, s/n – 08232 Viladecavalls (Barcelona) Spain.

Product:
Single-phase energy meter

Series:

CEM-C4-MID, CEM-CG-MID, CEM-CG-MID-ST,
CEM-C12-MID

Brand:
CIRCUTOR

The object of the declaration is in conformity with the relevant EU harmonization legislation, provided that ii is installed , maintained and used for the application for which it was manufactured, in accordance with the applicable installation standards and the manufacturer’s instruction
2014/32/CE: Measuring Instrument Directive 2011/65/EU: RoHS2 Directive
2015/863/EU: RoHS3 Directive

It is in conformity with the following standard(s) or other regulatory document(s):

EN 50470-1:2006 EN 50470-3:200

Year of CE mark:
2022

Viladecavalls (Spain), 30/3/2022
General Manager: Ferran Gil Tome

CIRCUTOR, SA
Vial Sant Jordi, s/n
08232 -Viladecavalls (Barcelona)
Tel.: (+34) 93 745 29 00 – Fax: (+34) 93 745 29 14
www.circutor.com [email protected]..

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals