Circutor TD6 Current Transformer Narrow Section Instruction Manual
- June 3, 2024
- Circutor
Table of Contents
TD6
TRANSFORMADOR DE CORRIENTE
CURRENT TRANSFORMER
Instruction Manual
TD6 Current Transformer Narrow Section
This manual is a TD6 installation guide. For further information,please
download the full manual from the CIRCUTOR web site:
www.circutor.com
Note: Device images are for illustrative purposes only and may differ
from the actual device.
IMPORTANT!
The device must be disconnected from its power supply sources (power supply
and measurement) before undertaking any installation, repair or handling
operations on the unit’s connections. Contact the after-sales service if you
suspect that there is an operational fault in the device.
The device has been designed for easy replacement in case of malfunction.
The manufacturer of the device is not responsible for any damage resulting
from failure by the user or installer to heed the warnings and/or
recommendations set out in this
manual, nor for damage resulting from the use of non-original products or
accessories or those made by other manufacturers.
DESCRIPTION
The TD6 is a current transformer, which allows current measurement in electrical installations from 150 to 800 A.
INSTALLATION
The TD6 must be installed on an electric panel or enclosure.
TD6 is designed for wall-mounting or DIN-rail assembly with an accessory for
installation.
IMPORTANT!
Take into account that when the device is connected, the terminals may be
hazardous to the touch, and opening the covers or removing elements may
provide access to parts that are dangerous to the touch. Do not use the device
until it is fully installed
Do not expose the TD6 to aggressive or explosive environment.
For measurements on non-insulated conductors, use the appropriate, required
personal protective equipment.
CONNECTION
TD6 is a bar type current transformer, the wire which current must be measured
must pass through the opening of the transformer.
Bridge the S1 and S2 secondary currents using one of the double terminals to
prevent damage during installation.
The conductive cable coming from the connection must be inserted into the
transformer on the P1 side and emerge on the P2 side towards the load of the
installation to be measured.
Once the primary voltage is connected, wire the transformer’s secondary
voltage (S1 and S2) to the measuring device and disconnect the jumper
installed previously.
If no device is connected to the secondary voltage, leave the jumper in place
to avoid damaging the installation.
Technical features
Electrical features
Type| Barra pasante / Bar
Primary current| 150 … 800 A
Secondary current (In)| …/5A
Thermal short-circuit current (Ith)| 60 In
Dynamic current (Idyn)| 2.5 Ith
Fequency| 50 – 60 Hz
Maximum operating voltage| 0.72 kV ~
Insulation voltage| 3 kV
Class| 0.5, 1, 3
Accuracy limit| 1.2 In
Continuous overload| 1.2 In
Precision power| 1 … 10 VA
Environmental features
Operating temperature| – 5 ºC … 40 ºC
Storage temperature| – 40 ºC … 85 ºC
Relative humidity(non-condensing)| 15 … 95 %
Maximum altitude| 2000 m
Thermical class| B (130º)
Protection degree| Bornes / Terminals: IP20
Safety factor| FS5
Mechanical features
Terminals| ****|
| **
S1, S2| 4 mm2| ≤ 0.6 Nm| Pozidriv Z1
Busbar| 30 x 15 mm, 40 x 10 mm, 20 x 25 mm
Max. conductor diameter| 30 mm
Dimensions| 66 x 90.8 x 53 mm
Weight| 256 g.
Enclosure| UL94 Plástico V0 autoextinguible UL94 Self-extinguishing V0
plastic
Normas / Standard**
UNE-EN 61869-1, UNE-EN 61869-2
Dimensions
Connections
Terminal connections designations
S1 | Secondary of the transformer. |
---|---|
S2 | Secondary of the transformer. |
Rango de corriente / Rated current
I (A)| CL 0.5| CL 1| CL 3| I (A)| CL 0.5| CL
1| CL 3
150/5| 1.00| 2.50| 3.50| 500/5| 5.00| 7.50| 7.50
200/5| 1.50| 3.50| 5.00| 600/5| 5.00| 7.50| 7.50
250/5| 2.50| 5.00| 5.00| 750/5| 5.00| 7.50| 10.00
300/5| 2.50| 5.00| 5.00| 800/5| 5.00| 7.50| 10.00
400/5| 2.50| 5.00| 5.00| | | |
Technical service
CIRCUTOR SAT: 902 449 459 (SPAIN) / (+34) 937 452 919 (out of Spain)
Vial Sant Jordi, s/n
08232 – Viladecavalls (Barcelona)
Tel: (+34) 937 452 900 – Fax: (+34) 937 452 914
e-mail : sat@circutor.com
M283A01-44-22A