Circutor CVM-C4 Multi Function Panel Mount Multimeter User Guide
- October 27, 2023
- Circutor
Table of Contents
CVM-C4
POWER ANALYZER
CVM-C4 Multi Function Panel Mount Multimeter
Terminal connections designations
1| L/+, Power supply
2| N/-, Power supply
4| I1 S1 , Current input L1
5| I1 S2 , Current input L1
6| I2 S1 , Current input L2
7| I2 S2 , Current input L2
8| I3 S1 , Current input L3
9| I3 S2 , Current input L3
11| U1 , Voltage input L1
12| U2 , Voltage input L2
13| U3 , Voltage input L3
14| UN / U2 , Voltage input N/L2
15| RO1, Relay output 1 (Common)
16| Relay output 1 (NO) / Relay output 2 (Common)
17| RO2, Relay output 2 (NO)
47| +, Impulse output
48| -, Impulse output
49| +, Impulse output
50| -, Impulse output
58| A, RS-485
59| B, RS-485
70| C , Common digital inputs
71| DI1 , Digital input 1
72| DI2 , Digital input 2
Connections
Measuring three-phase networks with a 4-wire connection.
Measuring three-phase networks with a 3-wire connection.
This manual is a CVM-C4 installation guide. For further information, please download the full manual from the CIRCUTOR web site: www.circutor.com
IMPORTANT!
The device must be disconnected from its power supply sources (power supply
and measurement) before undertaking any installation, repair or handling
operations on the device’s connections. Contact the after-sales service if you
suspect that there is an operational fault in the device The device has been
designed for easy replacement in case of malfunction.
The manufacturer of the device is not responsible for any damage resulting
from failure by the user or installer to heed the warnings and/or
recommendations set out in this manual, nor for damage resulting from the use
of non-original products or accessories or those made by other manufacturers.
DESCRIPTION
The CVM-C4 is a device that measures, calculates and displays the main
electrical parameters in single-phase and three-phase mains.
The device has RS-485 communications, relay outputs, impulse outputs and
digital inputs.
Current measurement is indirectly carried out by /5A or /1A transformers.
INSTALLATION
The device should be installed inside an electric panel or enclosure, and panel-mounted.
IMPORTANT!
Take into account that when the device is connected, the terminals may be
hazardous to the touch, and opening the covers or removing elements may
provide access to parts that are dangerous to the touch. Do not use the device
until it is fully installed
To install it, take the following steps:
- Make a cut in the panel, according to the dimensions in Figure 1.
- From outside, insert the device into the panel cut-out (Figure 2).
- Fully insert the device and fasten it securely by using the spring (Figure 3)
CONNECTION
The device should be connected to a power circuit protected by a fuse with a
maximum rated current of 0.25 A.
If the voltage to be measured is higher than the rated input voltage, a
voltage transformer must be connected to the device.
If more than one device is connected to the current transformer, they must be
connected in series.
Before disconnecting the current measurement connection cables, be sure to
disconnect the transformer’s primary cables and bridge the secondary.
The device can operate in three-wire, three-phase mode or four-wire, three-
phase mode, the user selecting the corresponding connection mode according to
the installation. An incorrect type of connection or an error in phase
sequence may cause measurement errors.
Technical features
AC Power supply”|
---|---
Rated voltage| 80 … 270 V –
Frequency| 50/60 Hz
Consumption| 6 … 18 VA
Installation category| CAT III 300V
DC Power supply'”|
Rated voltage| 80 270 V …=| 18 … 36 V
Consumption| 1.5 1.8 W| 1.8 … 2.2 W
Installation category| CAT III 300V
Voltage measurement circuit|
Rated voltage (Un)| 100 277 V, vc, – t 8%
Frequency measurement margin| 45 … 65 Hz
Overload| 1.2Un continuo / continuous,
2Un instantaneo / instantaneous (1min)
Consumption| < 0.2 VA (por fase / per phase)
Impedance| > 1.7 MO
Installation category| CAT III 300V
Current measurement circuit|
Rated current (In)| 1 A/ 5 A –
Frequency measurement margin| 45 … 65 Hz
Overload| 1.2In continuo / continuous,
10In ins tantaneo / instantaneous (55)
Consumption| < 0.2 VA (por fase / per phase)
Impedance| < 20 mO
Installation category| CAT III 300V
Accu racy|
Voltage measurement| 0.2 % t 1 digito / digit
Current measurement| 0.2 % t 1 digito / digit
Active and Reactive Power measurement| 0.5 % t 2 digitos / digits
Relays outputs|
Quantity| 2
Contact capacity (resistive)| CA/AC: 5A / 250V – , CC/DC: 5A / 30V -=
Max. voltage open contacts| 277V – / 30V ..=
Maximum current| 5 A
Maximum switching power| 1385 VA/ 150 W
Electrical life (250V -/ 5A)| 11105
Digital inputs|
Quantity| 2
Type| Contacto libre de potencial / Potential free contact
Insulation| 3.5 kV rms
Maximum short-circuit current| 4 mA
Maximum voltage in open circuit| 30 V
Impulse output|
Type| Pulso pasivo / Passive pulse
Maximum voltage| 27 V
Maximum current| 27 mA
Maximum frequency| 10 Hz
Minimum pulse width| 80 mA
RS-485 communications|
Communications protocol| Mod bus RTU
Baud rate| 2400- 4800 – 9600 -19200 bps
Data bits| 8
Stop bits| 1- 2
Parity| sin, par, impar /without, even, odd
User interface|
Display| LCD
Keyboard| 3 teclas / keys
Environmental features|
Operating temperature| -10°C… +60°C
Storage temperature| -20°C … +70°C
Relative humidity| 5 … 95%
Maximum altitude| 2000 m
Protection degree| Frontal / Front: IP54, Posterior/ Rear case: IP20
Pollution degree|
Mechanical features|
filthening II| | ****
1,2, 4 … 9,11 …18, 47 …50, 58, 59,70 … 72| 2.5 mm?| 0.5 Nm Plano / Flat (SZS
0.6×3.5)
Dimensions| 96 x 96 x 41.5 mm
Weight| 265 g.
Enclosure| pc + abs
Standers
IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC
61000-4-8, IEC 61000-4-11, IEC 61010-1
Depending on model:
Key|
---|---
| Previous screen
| Next screen
| Long keystroke ( >3s): Enter in configuration menu
Note: Device images are for illustrative purposes only and may differ from the actual device.
Technical service
CIRCUTOR SAT: 902 449 459 (SPAIN) / (+34) 937 452 919 (out of Spain)
Vial Sant Jordi, s/n
08232 – Viladecavalls (Barcelona)
Tel: (+34) 937 452 900 – Fax: (+34) 937 452 914
e-mail : sat@circutor.com
M267A01-60-21B
Documents / Resources
|
Circutor CVM-C4 Multi Function Panel Mount
Multimeter
[pdf] User Guide
CVM-C4, Multi Function Panel Mount Multimeter, Panel Mount Multimeter, Multi
Function Mount Multimeter, Mount Multimeter, Multimeter
---|---
References
- Productos y soluciones integrales para la eficiencia energética eléctrica
- Productos y soluciones integrales para la eficiencia energética eléctrica
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>