MEAN WELL DRDN20 DIN Rail Type Redundancy Module Owner’s Manual
- June 1, 2024
- MEAN WELL
Table of Contents
MEAN WELL DRDN20 DIN Rail Type Redundancy Module
Features
- Support 1 + 1 and N+ 1 redundancy system
- 2 channels input and 1 output
- Suitable for red undance operation of 12V/24V/48V system
- Output current up to 20A
- Cooling by free air convection
- -40~+80°C ultra-wide operating temperature ( >+60°C derating)
- 32mm slim width
- Built-in 2 channels DC OK signal and alarm relay contact
- Installed on DIN Rail TS35/7.5 or 15
- 3 years warranty
Applications
- Industrial control system
- Semiconductor fabrication equipment
- Factory automation
- Electro-mechanical apparatus
GTIN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx
Description
The DRDN20 series is a 20A redundancy module that can be used with a power supply to improve overall system operation reliability. Product key features include:12V/24V/48V input voltage for selection, support N+1 and 1 +1 redundancy systems, built-in two rails DC input contacts and single output. The MOSFET technology implemented can reduce heat loss and reduce the voltage difference between the input and output voltages, built-in 2 channels DC OK relay contacts for monitoring output status, ultra-wide operating temperature of -40 to +80°C and narrow width (32mm).
Model Encoding
SPECIFICATION
MODEL | ORON20-▯ |
---|
▯ =12V, 24V. 48V
INPUT| NUMBER OF INPUT| 2 Channels
DC NORMAL VOLTAGE| 12Vdc| 24Vdc| 48Vdc
DC VOLTAGE RANGE| 9-14Vdc| 19- 29Vdc| 36-60Vdc
RATED CURRENT| 0-20A per input Continuous
VOLTAGE DROP (Vin-Vou)t (max.)| 0.25V
PEAK CURRENT| 0-30A per input SSec.
EFFICIENCY (Typ.)| 98%
INPUT REVERSE CURRENT (max.)| 1mA
INPUT REVERSE VOLTAGE (max.)| 40Vdc 40Vdc| 40Vdc| 65Vdc
OUTPUT| RATED CURRENT| 0-20A, Continuous
PEAK CURRENT (max.)| 30A, 5Sec.
CAPACITANCE (Typ.)| 320 uF
STANDBY POWER LOSSES(Typ.)| 1.5W
PROTECTION| OVERLOAD| < 30A,5Sec. No damage
SHORT CIRCUIT| < 30A,5Sec. No damage
FUNCTION| REDUNDANCY| For 1+1 redundancy, and support N+1 redundancy
BOTH INPUTS VOLTAGE ALARM| <8.SVor >14.7V(± 5%)| <18V or >31V (± 5%)|
<34.2Vor >63V ( ± 5%1
RELAY| 30Vdc/1A resistive load
LEO STATUS DISPLAY| Green LED OK
ENVIRONMENT| COOLING| Free air connection
WORKING TEMP .| Note.2| -40 – +ado’s (Referto’ Derating Curve”)
WORKING HUMIDITY| 5- 95%RH non-condensing
STORAGE TEMP.| -40 – +85’C
TEMP. COEFFICIENT| ± 0 03%/’C 10 – 60′ Cl
VIBRATION| Component:10- 500Hz, 5G 10 min./cycle 6,0min.| echelon, Y, Zaxes;
Mounting: Compliance to IEC 61373
OPERATING ALTITUDE| Note.3| 5000 meters/OVC11
SAFETY & EMC (Note. 4)| SAFETY STANDARDS| IEC 6236-81, UL 62368-,1EAC TP TC
004 approved
WITHSTAND VOLTAGE| IP/OP· Chassis: 0.5KVac; IP/OP-Relay: 0.5KVac ; Relay·
Chassis: O.SKVac
ISOLATION RESISTANCE| IP/OP· Chassis, IP/OP-Relay, Relay· Chassis:>10M0Ohms/
500Vdc/ 25″C/ 70% RH
EMC EMISSION| Parameter| Standard| Test Level Note
Conducted| BS EN/EN55032(CISPR 32| Class B
Radiated| BS EN/EN55032t(SCPR32| Class B
Voltage Flicker| —–| —–
Harmonic Current| -··| —–
EMC IMMUNITY| BS EN/EN 55035, BS EN/EN 61000-6-2(BS EN/EN 50082-2)
Parameter| Standard| Test Level Note
ESD| BS EN/EN6100-4-2| Level 4,15KV air; Level 3, 8KV contact; criteria A
Radiated| BS EN/EN 6100-4-3| Level3, 10V/m; criteria A
EFT/ Burst| BS EN/EN 6100-4-4| Level3, 2KV; criteria A
Surge| BS EN/EN6100-4-5| Level 3 1KV/line line; level 3 2KV/line-
Line Chassis; criteria A
Conducted| BS EN/EN 6100-4-6| Level 3, 10V; criteria A
Magnetic Field| BS EN/EN6100-4-8| Level 4 , 30A/m; criteria A
OTHERS| MTBF| 1836.0Khrsmin. Telcordia SR-332 (Bellcore) ; 482.1K hrsmin.
MIL-HDBK-217F(25’C)
DIMENSION| 32’125.21′ 02mm(W’H’ D)
PACKING| 0.35Kg;28ps/1c0.8Kg/1.24 CUT
NOTE|
- All parameters NOT specially mentioned are measured at normal input(12V/24V/48V), rated load and 25″C of ambient temperature.
- Operating may be needed over high ambient temperature. Please check the derating curve for more details.
- The ambient temperature derating of 3.•s cn ooom with fanless models and of 5’C/1000m with fan models for operating altitude higher than 2000m(6500f)t.
- The power supply is considered as an independent nit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.” (as available on https://www.meanwell.com//Upload/POF/EMl_slatement_en.pdf)
※ Product liability Disclaimer: For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
Block Diagram
DC OK Rela Contact
Contact Ratinos (max.) | 30V/1Aresistive load |
---|---|
Contact Close (DCOK) | PSU turns on |
Contact Open (DC Fail) | PSU turns off/ over or under input voltage |
Derating Curve
Output Derating VS Input Voltage
Typical Application Notes
-
1+1 Redundancy:
Using 1 more PSU as the redundant unit -
1+N Redundancy:
Using more PS Us as the redundant units to increase the reliability
-
Single Use:
Connecting only one PSU to one DRDN20 to reduce the stress of the MOSFET and hence increase the reliability
Mechanical Specification
Terminal Pin No. Assignment (TB 1,TB2)
CaseNo. 221 D Unit: mm
Pin No. | Assignment |
---|---|
1,2 | Alarm1 DC OK |
3,4 | Alarm2 DC OK |
5 | FG |
6,7 | DC output +Vout |
8 | DC output •Vout |
Terminal Pin No. Assignment (TB3)
PinNo. | Assignment |
---|---|
1 | DC input +Vint |
2 | DC input -Vinl |
3 | DC input +Vln2 |
4 | DC input -Vin2 |
Installation Instruction
This series fits DIN rail TS35/7.5 or TS35/15. For installation details, please refer to the Instruction manual.
ADMISSIBLE DIN-RAIL:TS35n .5 OR TS35/15 (For retc, once only. Not included with unit.)
Installation Manual
Please refer to: http://www.meanwell.com/manual.html
Customer Support
User Manual
Video
Documents / Resources
| MEAN
WELL DRDN20 DIN Rail Type Redundancy
Module
[pdf] Owner's Manual
DRDN20, DRDN20 DIN Rail Type Redundancy Module, DIN Rail Type Redundancy
Module, Rail Type Redundancy Module, Redundancy Module, Module
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>