BEGA 33046 Recessed Luminaire Owner’s Manual

June 1, 2024
BEGA

BEGA 33046 Recessed Luminaire

BEGA-33046-Recessed-Luminaire-product

Instructions for use

BEGA-33046-Recessed-Luminaire-fig-1

Application

  • Recessed luminaire for walls and staircases for flush or surface-mounted installation.
  • With asymmetrical flat beam light distribution for the wide beam and uniform illumination of floor spaces.
  • The colour temperature of the luminaire can be set optionally to 3000K and 4000K.

Product Description

  • Luminaire made of aluminium alloy, aluminium and stainless steel
  • BEGA Tricoat® coating technology
  • Colour graphite or silver
  • Safety glass with optical structure
  • Silicone gasket
  • Reflector made of pure anodised aluminium
  • Fixing is achieved by using two adjustable wedge-shaped claws
  • Required recessed opening 245 x 60mm
  • Recessed depth 70mm
  • 2 cable entries for through-wiring of mains supply cable ø 7-10.5mm
  • Connection terminal 2.5
  • Earth conductor connection
  • BEGA Ultimate Driver
  • Complies with flicker requirements by IEEE 1789, DIN IEC/TR 63158, DIN IEC/TR 61547-1
  • LED power supply unit
  • 220-240 V x 0/50-60 Hz
  • DC 176-280 V
  • BEGA Thermal Control®
  • Temporary thermal regulation to protect temperature-sensitive components without
  • switching off the luminaire
  • Safety class I
  • Protection class IP 65
  • Dust-tight and protection against water jets
  • Impact strength IK07
  • Protection against mechanical
  • impacts < 2 joule
  • Safety mark
  • Conformity mark
  • Weight: 0.85 kg
  • This product contains light sources of energy efficiency class(es) C

Safety
The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician. The manufacturer accepts no liability for damage caused by improper use or installation.
If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

The electronic components installed in the luminaire are protected against overvoltage by DIN EN 61547. To achieve additional protection against e.g. transients, etc. we recommend separate overvoltage protection components. You can find them on our website at
www.bega.com. The ideal protection of all electronic components installed in the luminaires is achieved by using bounce-free switching contacts such as an electronic relay (solid-state relay), e.g. BEGA 71320.

Please note

  • This luminaire is coated with BEGA Tricoatb. BEGA Tricoatb is a registered trademark for a technology that we use to achieve optimal corrosion resistance.
  • Even the best possible surface protection and the highest corrosion resistance can be rendered almost ineffective in some cases by aggressive media caused by the leaching of building materials.
  • Where such media are suspected, a material analysis must be carried out before installation.
  • Always avoid excessive use of chemical cleaning agents in the vicinity of the luminaire.

Installation

  • The recessed opening will be covered by the frame of the luminaire housing.
  • Fixing of the luminaire is achieved by using two adjustable wedge-shaped claws.

Installation in solid, plastered walls
The installation housing 10 425 is available for this purpose. If this is not used, an exact recessed opening of 245 x 60mm with a minimum depth of 70mm is required.

Installation in exposed brickwork
The construction of an on-site recessed opening with the exact installation dimensions of 245 x 60mm with a minimum depth of 70mm is required. An installation housing cannot be used.

Installation in drywalling

  • A recessed opening of 245 x 60mm with a minimum depth of 70mm is required.
  • The claws grip behind drywall.

Installation into insulated façades

  • For installation in EWIS external wall insulation systems please use install housing 13 520 in combination with a plaster frame 10 025 or 13 504.

Open luminaire

  • Undo hexagon socket screws (SW 3) and remove the housing cover.
  • Disconnect the plug-connection of the LED connecting cable.
  • Disconnect the earth conductor connection
  • from the plug connection.
  • Lead the main supply cable through the cable entry into the luminaire housing.
  • Make an earth conductor connection.
  • Push silicone sleeves over the lines and make electrical connections.
  • To guarantee the maximum service life of the electrical components, the enclosed desiccant pouch must be placed in the luminaire.
  • Remove the desiccant pouch from the foil packaging and place it in the position marked by the red information label immediately before finally closing the luminaire.
  • The LED module can optionally be operated with a colour temperature of 3000 K or 4000 K.
  • Check the labelling to ensure a correct socket match when connecting the plug-in device to the LED connecting cable.
  • Switching may only be carried out when disconnected from the power supply!
  • Put on earth conductor connection of the housing cover. Assemble the housing cover.
  • Make sure that the gasket is positioned correctly.
  • Tighten the screws evenly.
  • Insert luminaire housing into the recessed opening.
  • Hand-tighten the screws of the claw fastener (torx drive T10) evenly. Do not use an electric screwdriver!

Lamp

  • Module connected wattage 6 W
  • Luminaire connected wattage 7.2 W
  • Module designation LED-1543/83040
  • Colour rendering index CRI >80
  • Rated temperature ta=25 °C
  • Ambient temperature ta max=55 °C
  • When installed in heat-insulating material ta max=45 °C
  • Operation at colour temperature 3000 K
  • Module luminous flux 1045 lm
  • Luminaire luminous flux 550 lm
  • Luminaire luminous efficiency 76,4 lm/W
  • Operation at colour temperature 4000 K
  • Module luminous flux 1060 lm
  • Luminaire luminous flux 558 lm
  • Luminaire luminous efficiency 77,5 lm/W

Cleaning · Maintenance

Clean the luminaire regularly with solvent-free cleansers from dirt and deposits. Do not use high-pressure cleaners

Replacing the LED module

  • The designation of the LED module is noted on a label in the luminaire.
  • The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted.
  • The module can be replaced by qualified persons using standard tools.
  • Disconnect the system and open the luminaire.
  • Please follow the installation instructions for the LED module.
  • Inspect and, if necessary, replace the luminaire gaskets.
  • The defective glass must be replaced.
  • Close the luminaire.

Accessories

  • 10 425 Installation housing
  • 13 520 Installation housing for installation in insulated façades (EWIS)
  • 10 025 Plaster frame
  • 13 504 Plaster frame flush
  • Separate instructions for use can be provided upon request.

Spares

  • LED power supply unit DEV-0451/350
  • LED module LED-1543/83040
  • Reflector 76 001 440
  • Gasket 83 001 526

References