PC4020 Maxsys Wiring Uplink’s Cellular Communicators User Manual

June 17, 2024
Uplink

Uplink’s-logo

PC4020 Maxsys Wiring Uplink’s Cellular Communicators

PC4020-Maxsys-Wiring-Uplink’s-Cellular-Communicators-product-
image

Product Information

Specifications :

  • Product Name: DSC PC4020 Maxsys
  • Compatible with Uplink’s Cellular Communicators
  • Programming Capabilities for Alarm Panel

Product Usage Instructions

Wiring Uplink’s Cellular Communicators to DSC PC4020 Maxsys
Follow these steps to wire up Uplink’s Cellular Communicators to the DSC PC4020 Maxsys:

  1. Ensure power is off before wiring.
  2. Connect the communicator’s wiring to the designated ports on the DSC PC4020 Maxsys.
  3. Securely fasten all connections to avoid any loose wiring.

Programming the Panel
To program the DSC PC4020 Maxsys Alarm Panel via the keypad, follow these steps:

  1. Navigate through the keypad menu to reach the programming settings.
  2. Enable Contact ID reporting by following the specific keypad entry instructions provided.
  3. Set communication toggles and DTMF dialing preferences as needed.

Program Keyswitch Zone and Output
For programming keyswitch zone and output, use the following steps:

  1. Access programming mode on the keypad.
  2. Select the appropriate options to set up keyswitch zone assignments.
  3. Edit zones and assign labels as required.

FAQ (Frequently Asked Questions)

  • Q: How do I know if the wiring is correct for the communicators?
    A: Ensure that the communicator’s wiring matches the specified ports on the DSC PC4020 Maxsys. Refer to the user manual for detailed wiring instructions.

  • Q: Can I program multiple keyswitch zones on the panel?

  • A: Yes, you can program multiple keyswitch zones by following the zone assignment procedures in the programming menu.

DSC PC4020 Maxsys

Wiring Uplink’s Cellular Communicators and Programming the Panel

CAUTION:

  • It is advised that an experienced alarm installer programs the panel as further programming may be required to ensure proper performance and use of the full functionality.
  • Do not route any wiring over circuit board.
  • Full panel testing, and signal confirmation, must be completed by the installer.

NEW FEATURE: For Uplink Communicators, the status of the panel can be retrieved not only from the status PGM but now also from the Open/Close reports from the dialer. Therefore, wiring the white wire and programming of the status PGM of the panel is optional.

IMPORTANT NOTE: The Open/Close reporting needs to be enabled during the initial pairing procedure.

Wiring the 5530M communicators to DSC PC4020 Maxsys

PC4020-Maxsys-Wiring-Uplink’s-Cellular-
Communicators-01

Programming the DSC PC4020 Maxsys Alarm Panel via the Keypad

Enable Contact ID reporting:

Keypad Display Keypad Entry Action Description
Date & Time *84020 To enter Programming Mode
Select (00) – System Area 01 To enter Partition Area
Select (00) – Add/Edit Par 00 To enter Add/Edit Partition
Select (00) – Partition 1 01 To enter Partition 1 account number
Select (00) – Partition Acc. # * To select the menu
Partition Acct. # – Enter Hex 1234 Enter the account number (1234 is an

example)
Select (00) – Partition Acc. #| ##| To exit to the main menu
Select (00) – System Area| 00| To enter System Area
Select (00) – Installer Opt’s| 04| To select Communicator
Select (00) – Main Items| 00| To select Main Items
Select (00) – 1st Number| 03| To go to System Account Number
System Account# – Enter Hex| 1234#| Enter the same account number as you entered for Partition 1 above
| 03| To enter Reporting Codes in case of CID format
Select (10) Closings| 10| Define Closing by user
User 001 Closing| 12#| Reporting Code for Closing
Select (11) – Misc Closings| 11| Define Misc Closing for Key switch reporting
Closing|
12#| Reporting Code for Misc Closing
Select (13) Openings| 13| Define Opening by user
User 001 Opening| 12#| Reporting Code for Opening
Select (14) – Misc Opening| 14| Define Misc Opening for Key switch reporting
Opening|
12##| Reporting Code for Misc Opening
Select (00) – 1st Number| 00| To go to Program Telephone Number
Select (00) – Pgm. Tel Number| 00| To select 1st phone number
Enter(31 max) Tel Number| 00| To go to phone number
D __| 123456#| Enter phone number (123456 is an example) # to go back
Select (00) – Pgm. Tel Number| 01| To go to Communicator Format
Select (00) – DTMF Contact ID| 02| To select DTMF Contact ID
Select (00) – Pgm. Tel Number| 02| To go to Dialer Direction
Select Toggle – Alarm/Restore| >| Press until Y (Yes), press > to move to next option
Select Toggle – Open/Close| >| Press until Y (Yes), press > to move to next option
Select Toggle – All Others| # # #| Press until Y (Yes), press # # to go back to Main Items
Select (00) – Main Items| 01| To go to Communication Toggles
---|---|---
Select Toggle – Comms. Enabled| >| Press until Y (Yes), press > to move to next option
Select Toggle – DTMF Dialing| >| Press until Y (Yes), press > until you find “TLM Enabled”
Select Toggle – TLM Enabled| >| Press until N (No), press > until you find “6 Digit account”

Program Key switch zone and output:

| Keypad Display| Keypad Entry| Action Description|
---|---|---|---|---
| Date & Time| 84020| To enter programming mode|
| Select (00) – System Area| 01| To enter Partition area|
| Select (00) – Add/Edit Par| 00| To enter Add/Edit Partition|
| Select (00) – Partition 1| 01| To enter Partition 1|
| Select (00) – Partition Acct. #| 03| To enter Zone Assignment|
| Select (00) – Add New Zone| 01| To Edit Zones (00 to add Zone)|
| Select (001) – Zone 1| 001
| To enter Zone 1|
| Select (00) – Zone Label| 01| To go to Zone type|
| Select (00) – Momentary Arm| 25| To select Momentary Arm|
| Select (00) Zone Label| #####| Press # until you go back to the Main Menu|
| Select (00) – System Area| 00| To enter System Area|
| Select (00) – Installer Opt’s| 02| To go to System Options|
| Select (00) – System Toggles| 04| To go to Zone Supervision|
| Select (01) – Single EOL| 01| To select Single EOL option, press > until you find “Single EOL”|
| Select (00) – System Toggles| ##| To go back to previous section|
| Select (00) – Installer Opt’s| 07| To go to PGM Outputs|
| Select (00) – Main PGM 1 Out| 00| To select PGM 1|
| Select (00) – Inv. Arm Status| 07| To select Inv. Arm Status|
| Select (00) – Partition 1| #| Press until Y (Yes), press # until you exit programming mode|
| Select Toggle| # # #| Press until N (No), press # until you exit the Programming Menu|
NOTE:

  • TO PROGRAM THE DESIRED REPORTING CODES – *84020, 00, 04, 03
  • From programming mode (*84020) type 00 to go to System Area, followed by 04 (Communicator), followed by 03 (Reporting Codes).
  • Program the desired reporting codes in the corresponding fields from 00 to 16.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals