SAVANT 028-9395 Current Track Module User Guide
- June 17, 2024
- SAVANT
Table of Contents
- SAVANT 028-9395 Current Track Module
- Product Usage Instructions
- Box Contents
- Accessories
- Specifications
- Descriptions
- Features
- Important Information
- Installation into Breaker Panel
- Install the Current Transformer
- Additional Information
- System Overview
- Hardware Setup Process
- LCD Screen Icon Descriptions
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SAVANT 028-9395 Current Track Module
Specifications
- Environmental:
- Temperature: Up to 90% Relative Humidity (non-condensing)
- Location: Indoor use unless installed in a NEMA 3R rated enclosure
- Dimensions and Weights:
- Module:
- Length: 4.49 in. (11.4 cm)
- Width: 1.97 in. (5.0 cm)
- Height: 2.76 in. (7.0 cm)
- Weight: .5 lbs (.23 kg)
- Shipping:
- Length: 7.48 in. (19.0 cm)
- Width: 4.17 in. (10.60 cm)
- Height: 1.69 in. (4.29 cm)
- Weight: 1.0 lbs. (.45 kg)
- Power:
- Input Power: 120V AC (+/- 10%) @ 60 Hz, 0.1A (max)
- Signal Input: 0.333V AC @ 60Hz
- Standards:
- Wireless:
- ANSI C12.20-2015 – American National Standard for Electricity Meters
- ANSI C12.1-2014 – American National Standard for Electric Meters
- FCC Part 15, UL, ICES 003
Product Usage Instructions
Installation Steps:
- CT Connections: Connect a current transformer to each CT Connection input port labeled 1 and 2, observing polarity.
- Pigtail Neutral: Connect the pigtail type neutral wire to the neutral bar in the electrical service panel.
- 120V AC Connection: Plug the Current Track Module onto the 120V AC bus bar in the electrical panel to power the module.
Safety Instructions:
- Electric Shock Hazard: The 120V AC, 60 Hz source can cause serious injury; always disconnect power before servicing.
- Risk of Electric Shock: More than one disconnect switch may be needed to de-energize the device for servicing.
FAQ
-
Q: What should I do if the module does not power on?
A: Check the power source connection and ensure that the module is securely plugged into the AC bus bar. -
Q: Can I install the module outdoors?
A: The module is designed for indoor use unless installed in a NEMA 3R rated enclosure for outdoor installations.
Current Track Module (Supports Eaton CH Style Load Centers) Quick Reference and Installation Guide
Box Contents
- (1) Current Track Module – GPM-C2SEM-xx w/Pigtail type neutral
- (1) 4-pin screw down plug-in connector (028-9395)
- (1) Product Information and Regulatory Insert (009-1950)
- (1) Quick Reference and Installation Guide (this document)
Accessories
NOTE : Both single and multi-pack current transformers are available. See the Savant Store for details (x = CTs in package).
Specifications
Descriptions
Features
- The GPM-C2SEM is compatible with Eaton CH 3/4 inch load centers.
- Energy monitoring; +/- 0.5% revenue grade accuracy / 1 sec sample time when used with revenue grade current transformers.
- Communication with a Panel Bridge Controller, Director, or Director Lite is achieved over Bluetooth Low Energy (BLE).
- Color LCD display for easy identification.
ELECTRIC SHOCK! The 120V AC, 60 Hz source poses an electrical shock
hazard that has the potential to cause serious injury to installers and end
users.
CAUTION! Risk of Electric Shock – More than one disconnect CAUTION! Risk
of Electric Shock – More than one disconnect
IMPORTANT! A licensed electrician is required to install any of Savant’s
Power and Energy Modules.
Important Information
- Each Current Track Module requires two spaces in an electrical service panel.
- All wiring in the United States must be installed in accordance with the latest adopted edition of the National Electrical Code (ANSI/NFPA 70, NEC)
- All wiring in Canada must be installed in accordance with the latest adopted edition of the Canadian Electrical Code (CSA C222.2 CEC, Part 1) and any provincial or local requirements.
- Use only Savant approved current transformers. A list of supported transformers is available in the Accessories section on the previous page.
- The largest current transformer Savant offers supports wire diameters up to a 750 kcmil conductor (750 kcmil = just under 1 inch).
Installation into Breaker Panel
IMPORTANT! See the Single and Three Phase Electrical Panel Installations section before plugging the module into an electrical panel.
- Remove power from the electrical service panel by switching off the panel’s main breaker.
- Position and install the Current Track Module into the appropriate slots. The neutral clip on the bottom of the module must sit on a portion of the neutral bar where no neutral wire is installed beneath it. With a wire installed in the hole under the neutral clip, the module won’t seat properly.
- Press firmly until fully seated onto the bus bars.
Install the Current Transformer
Up to two current transformers can be connected to a GPM-C2SEM. Information on orienting and connecting the CTs into an electrical panel is described below.
- Toggle the electrical panel’s main breaker Off.
- Remove the panel’s front cover and set it aside. Verify that power was removed from the circuit breakers using a voltage tester.
- Separate the current transformer by squeezing the knurled panel and pulling/rotating the top open.
- Place the current transformers around each of the conductors being monitored.
- Orient the current transformer so the arrow in the middle points towards the source i.e., breaker or utility meter.
- On solar or generator installations, orient the current transformer so the arrow points away from the solar panels or generator.
- Close the current transformer around the conductor. For added security, wrap a cable tie around the CT or run the tie through the loops on the front.
- Route the twisted black and white wires around the breaker panel back to the module. Route the wires so they don’t directly come in contact with a live bus bar or terminal.
- Observing polarity, insert the wires into the supplied 4-pin connector and secure by turning screws clockwise. See the Making Connections section to the right for info on attaching the wires.
- Repeat steps 3-7 to install a second current transformer if needed.
- Ensure the 4-pin connector is fully seated into the module and tighten the connector’s screws to .18 ft-lb (.25 N-m) max.
- Toggle the main breaker back to the On position and re-apply power to the electrical panel. The Current Tracker Module is ready to monitor the circuit the CT is installed over.
Making Connections
- Remove power if power is applied.
- Pull to remove the terminal block from the module’s rear panel.
- With a small flat-bladed screwdriver, turn the screws on the top of the connector counterclockwise until the silver crimps on the front of the connector open enough to slide the wire into the square slot.
- Strip back the insulation of each wire to 1/4 inch (6.5 mm). Insert the stripped wire into the proper port. Do not allow more than 1/8 inch (3.2 mm) of bare wire exposed. See image.
- Turn the screws clockwise until the silver crimps tighten around the wire. Tug on the wire a bit to verify the wire is installed securely.
- Continue until all wires are installed.
- Plug the terminal block into the appropriate port.
- Repeat steps 2-7 to install a second current transformer.
- Reapply power.
Additional Information
- Savant Power Deployment Guide – Sol-Ark
- Savant Power System Deployment Guide – Savant Power & Light App
System Overview
HELPFUL! A Class 2 Surge Protection Device is recommended when installing Savant’s power or energy equipment in areas that experience frequent lightning or other transient voltage and current producing phenomena.
LCD Screen Orientation
During power-up, the text and icons on the LCD screen are oriented so they are
right side up. If the text and icons are upside down, unplug and replug the
Current Track Module to power cycle it. The LCD screen will reorient itself
during boot-up, so the screen becomes right side up.
Single and Three Phase Electrical Panel Installations
In a single-phase electrical panel, phases L1 and L2 alternate slots. In a
three-phase panel, phases L1, L2, and L3 repeat every three spaces. The slot
in the electrical panel that the Current Track Module is plugged into, and the
wire being monitored must be on the same phase. Not doing this will result in
the module’s LCD displaying a negative power. See the diagram below for more
information.
IMPORTANT!
- The Current Track Module is plugged into slots 13 and 15 and is positioned so Port 1 is plugged into the L1 phase in the panel. Therefore, the current transformer wired to Port 1 must monitor a wire connected to the L1 Phase.
- Port 2 on the Current Track Module is plugged into the L2 Phase so the current transformer wired to port 2 must monitor a wire connected to the L2 Phase.
- The same is true for ports connected to the L3 Phase. The wire being monitored must be connected to the L3 Phase.
Hardware Setup Process
Useful Information
- A hardware setup screen opens when the Current Track Module is first powered on. Follow the instructions in the On-Device Setup Process Screens section for information on navigating the setup options.
- During the hardware setup process:
- Press and release the PAIR button to scroll through the menu options.
- Press and hold the PAIR button to save the highlighted menu option and then move to the next screen.
- Select the Exit option to bypass the hardware setup process.
On-Device Setup Process Screens
With the module installed and powered, a series of On-Device setup screens are
made available to configure the type and location of the device being
monitored by the Current Track Module. The progression of screens for this
process is shown below. If a user decides not to use this process, they can
simply |Exit| out of the setup and can instead set up the device using the
Savant Power & Light mobile app.
HELPFUL!
- The screen options differ depending on the selections made.
- After the setup process, if a mistake was made, to clear the labels from the module’s display, scroll to the Gateway screen, press and hold the PAIR button for 1 second, and follow the RESET instructions.
- After configuring the module using the On-Device setup, the module is ready to be paired to a Director or Director Lite. Refer to the Savant Power System Deployment Guide – Power & Light App for pairing instructions.
LCD Screen Icon Descriptions
Reset the Module
From any screen, press and hold the PAIR button for 5 seconds until the Reset
screen opens; then release. A RESET IN screen opens and counts down from 5
seconds and resets. After the reset, any error conditions that exist, such as
an overload, are cleared.
Bluetooth Discovery Mode
From any screen, press and hold the PAIR button for three seconds until the
Bluetooth Discover icon appears, then release. In Discovery Mode, the module
can now be connected to a PBC or Director. Discovery Mode automatically
cancels itself after 5 minutes. At that point the module will need to be put
back into this mode to be discovered.
Power Monitor – QRG | 009-2241-01
Copyright ©2023 Savant Systems, Inc | 230503
45 Perseverance Way, Hyannis MA 02601
savant.com | 508.683.2500