Product Information and Regulatory Statement
**** Important Safety Information – Read First!
Before installing, configuring, or operating any equipment, all relevant technical documentation must be read, understood, and followed. Savant technical documentation may contain important product-specific installation, mounting, and safety instructions, and can be accessed through the Savant Store.
https://dealers.savantav.com/redirector.php?id=1289
Scan the QR code or visit the URL below, enter the relevant product name or SKU in the Search Savant prompt, and select the product purchased to find documents, specifications, and more. https://store.savant.com/DefaultStore/ccrz__HomePage
Safety Statements
All safety instructions below must be read, understood, and carefully followed under all applicable circumstances when working with any Savant equipment.
- Follow all input power ratings marked on the product near the power input!
- If fuse replacement is required, the replacement fuse should match the fuse rating marked on the product.
- Do not use equipment near water.
- Clean only with a dry cloth.
- Do not block any ventilation openings or install them near any heat sources such as heat registers, stoves, radiators, amplifiers, etc.
- Refer all servicing to qualified service personnel. Servicing is required when any part of the apparatus has been damaged in any way or fails to operate normally for any reason.
- Use only attachments/accessories specified by the manufacturer, following all relevant safety precautions for any such attachments/accessories.
- For applicable equipment, use the included power cord with the grounding prong intact to ensure proper grounding of the device.
- If the provided plug does not fit the desired outlet, contact a licensed electrician to replace the obsolete outlet.
- Protect any power cord from being walked on, pinched, strained, or otherwise potentially damaged, especially at the outlet or device connections.
- Disconnect any outlet-powered apparatus from its power source during lightning storms or when unused for long periods of time.
- To completely disconnect the equipment from AC mains power, disconnect the power supply cord plug from the AC receptacle on the device.
- For any hardwired or fixed in-wall apparatus, carefully follow all wiring diagrams and instructions. All electrical wiring and servicing should be performed by a properly licensed electrician.
IMPORTANT NOTES:
- For product mounting, installation, safety instructions, technical specifications, and more, refer to the product Quick Reference Guide, available via the link or QR code noted above.
- For regulatory and compliance information, see the reverse of this sheet and/or product packaging.
FCC Regulations
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
- This device may not cause harmful interference, and
- This device must accept any interference received, including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits for CLASS B
digital devices, pursuant to Part 15 of FCC Rules.
These limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a residential installation.
This equipment generates, uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the instructions, may cause harmful
interference to radio communications. If this equipment does cause harmful
interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try correcting the
interference with one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and the receiver.
- Connect this equipment to an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
FCC Caution
Any changes or modifications not expressly approved by the party responsible
for compliance could void the user’s authority to operate this equipment. This
transmitter must not be co-located or operating in conjunction with any other
antenna or transmitter.
Radiation Exposure Statement – Wireless and Handheld Devices Only
This equipment complies with FCC and IC radiation exposure limits set forth
for an uncontrolled environment. This equipment should be installed and
operated with a minimum distance of 20 cm between the radiator and your body.
FCC and IC Identifier – Devices with Integrated Screen or User Interface
Only
This device electronically displays the FCC declaration of conformity logo as
well as the FCC and IC identifiers. This information can be found on the
device by accessing:
(Service menu) > About (A propos de)
IC Statement
This device complies with Industry Canada license-exempt RSS standard(s).
Operation is subject to the following two conditions:
- This device may not cause interference, and
- This device must accept any interference, including interference that may cause undesired operation of the device.
This Class B digital apparatus complies with Canadian ICES-003/NMB-003.
This device complies with RSS-247 of Industry Canada. Operation is subject to
the condition that this device does not cause harmful interference.
This device and its antenna(s) must not be co-located or operating in
conjunction with any other antenna or transmitter, except tested built-in
radios. The Country Code Selection feature is disabled for products marketed
in the US/Canada.
Smart Energy Monitor Module (Supports 1-inch On-Center Load Centers) Quick Reference and Installation Guide
Box Contents
(1) Smart Energy Monitor Module (SEM)
– GPM-H2SEM-xx w/Pigtail type neutral
(1) 4-pin screw-down plug-in connector (028-9395)
(1) Product Information and Regulatory Insert (009-1950)
(1) Quick Reference and Installation Guide (this document)
Current Transformers
Accessories
– ACTL-1250-250 Opt CO.2 250 Amp
– ACTL-1250-400 Opt CO.2 400 Amp
– ACTL-1250-600 Opt CO.2 600 Amp
Specifications
Environmental
Temperature | 32° to 104° F (0° to 40° C) |
---|---|
Humidity | 5% to 85% Relative Humidity (non-condensing) |
Location | Indoor Use Only |
Dimensions and Weights
Length | Width | Height | Weight |
---|---|---|---|
Module | 4.49 in. | ||
(11.41 cm) | 1.98 in. | ||
(5.03 cm) | 2.78 in. | ||
(7.06 cm) | .54 lbs |
(.24 kg)
Shipping| 7.48 in.
(19.0 cm)| 4.17 in.
(10.6 cm)| 1.69 in.
(4.29 cm)| 1.0 lbs.
(.45 kg)
Power
Input Power (powers the module)
Signal Input| 0.333V AC @ 60Hz
Type of Action| Type 1 action
Standards
Wireless| Bluetooth 5 Low Energy (BLE) – 2.4 GHz radio frequency
This meter will be tested and certified to the following standards:
ANSI C12.20-2015| American National Standard for Electricity Meters – 0.5
Accuracy Class
ANSI C12.1-2014| American National Standard for Electric Meters – Code of
electricity Metering
Regulatory
Safety and Emissions | FCC Part 15 | ICES 003 |
---|---|---|
Contains FCC ID: | PUU-HQC2SEM | |
Contains IC: | 10798A-HQC2SEM | |
RoHS | Compliant |
Recommended Load Center Types
Refer to the Features section to the right for compatibility.
Electrical and Safety Characteristics
Pollution Degree | 2 |
---|---|
Purpose of Control | Energy Monitoring |
Software | Class A |
Impulse Voltage | 2500V |
Construction of Control
Open Type| Independently mounted for flush mounting
Minimum Supported Release
Savant OS| da Vinci 10. x
Descriptions
A: Multi-Page LCD screen that offers the following information:
-
Real-time energy usage.
-
Firmware and Mac Address of the module.
-
UID of the connected Host
-
Real-time Bluetooth status connectivity icon.
-
Module set-up and calibration screens.
B: PAIR Button – The PAIR button is a multi-use button. The
the duration that the button is pressed and held determines the function that gets initiated: -
Press and Release – Cycles through the screens available on the LCD (POWER > POWER > INFO 1 > INFO 2).
-
Press and hold – Press and hold for 2 seconds to put the module into pairing mode. Press and hold for greater than 5 seconds to reset the module.
C: CT Connections -
Connect a current transformer to each CT
Connection input ports labeled 1 and 2, observing polarity when making connections. Refer to the Install the Current Transformer section later in the document for additional wiring information.
D: Pigtail Neutral -
Connect the pigtail-type neutral wire to the neutral bar in the breaker panel.
E:120V AC Connection – Plug the module onto the 120V AC bus bar in the breaker panel. The voltage on this connection powers the module.
Features
-
The GPM-H2SEM-00 Smart Energy Monitor modules is compatible with Schneider Homeline, Eaton BR, Siemens, and Powermark Gold load centers with a one-inch on-center bus bar.
-
Energy monitoring; +/- 0.5% revenue grade accuracy / 1 sec sample time. The module communicates with a Panel Bridge Controller or Savant
Power Director using Bluetooth Low Energy (BLE) technology. -
Color LCD display for easy identification.
**ELECTRIC SHOCK! The 120V AC, 60 Hz source poses an electrical shock
hazard that has the potential to cause serious injury to installers and end
users.
CAUTION! Risk of Electric Shock – More than one disconnect switch may be
required to de-energize the device before servicing. Always disconnect the
power to the module before making any connections.
IMPORTANT!** A licensed electrician is required to install any of Savant’s
Power and Energy Monitoring Modules.
Important Information
-
Each Smart Energy Monitor requires two spaces in an electrical breaker panel.
-
All wiring in the United States must be installed in accordance with the latest adopted edition of the National Electrical Code
(ANSI/NFPA 70, NEC) -
All wiring in Canada must be installed in accordance with the latest adopted edition of the Canadian Electrical Code (CSA C222.2 CEC, Part 1) and any provincial or local requirements.
-
Use only Savant-approved current transformers. A list of supported transformers is available in the Accessories section on the previous page.
-
The largest current transformer offered by Savant supports wire up to a 750 kcmil conductor (with the jacket just under 1 inch in diameter).
Installation into Breaker Panel
- Remove power from the breaker panel by switching off the panel’s main breaker.
- Position and install the Smart Energy Monitor Module into the slots where it will be installed. Press firmly until fully seated onto the appropriate bus bars.
- The next few sections describe how to install and wire a current transformer to the Smart Energy Monitor module.
Install the Current Transformer
The GPM-H2SEM module supports connecting up to two Savantapproved current transformers. See the approved list on the previous page. Instructions on wiring and renting the current transformer are explained below.
-
Toggle the electrical panel’s main breaker Off to remove power from the panel.
-
Remove the panel’s front cover and set it aside. Verify that power is removed from the circuit breakers using a voltage tester.
-
Separate the current transformer by squeezing the knurled panel and pulling/rotating the top open.
-
Place the current transformers around each of the conductors being monitored.
– Orient the current transformer so the arrow in the middle points towards the source i.e., breaker or utility meter. -
Close the current transformer around the conductor. For added security, wrap a cable tie around the CT or run the tie through the loop on the front.
-
Route the twisted black and white wires around the breaker panel back to the Smart Energy Monitor module. Route the wires so they don’t directly come in contact with a live bus bar or terminal.
-
Observing polarity, insert the wires into the supplied 4-pin connector and secure by turning screws clockwise. See the Making Connections section in this document for information on attaching wires to the connector.
HELPFUL: A negative current will be measured if the wires are reversed or the current transformer is installed backward.
- Repeat steps 3-7 to install a second current transformer if needed.
- Ensure the 4-pin connector is fully seated into the SEM module and tighten the screws to .18 ft-lb (.25 N-m) max.
- Toggle the main breaker back to the On position and re-apply power to the electrical panel. The Current Transformer and Smart Energy Monitor module are ready to monitor the power consumed by the circuit the CT is monitoring.
Making Connections
-
Remove power if power is applied.
-
Pull to remove the terminal block from the Smart Energy Monitor’s rear panel.
-
With a small flat-bladed screwdriver, turn the screws on the top of the connector counterclockwise until the silver crimps on the front of the connector open enough to lide the wire into the square slot.
-
Strip back the insulation of each wire to 1/4 inch (6.5 mm). Insert the stripped wire into the proper port. Do not allow more than 1/8 inch (3.2 mm) of bare wire exposed. See image.
-
Turn the screws clockwise until the silver crimps tighten around the wire. Tug on the wire a bit to verify the wire is installed securely.
-
Continue until all wires are installed.
-
Plug the terminal block into the appropriate port on the Smart Energy Monitor.
-
Repeat steps 2-7 for all wires from the current transformer.
-
Reapply power.
Additional Information
– Savant Power Deployment Guide – Sol-Ark
System Overview
SEM Display Descriptions
Smart Energy Monitor Module (Supports QO Style Load Centers) Quick Reference and Installation Guide
Box Contents
(1) Smart Energy Monitor Module (SEM)
– GPM-QP2SEM-xx w/Plug-on neutral
– GPM-Q2SEM-xx w/Pigtail type neutral
(1) 4-pin screw down plug-in connector (028-9395)
(1) Product Information and Regulatory Insert (009-1950)
(1) Quick Reference and Installation Guide (this document)
Accessories
Current Transformers
– ACTL-1250-250 Opt CO.2 250 Amp
– ACTL-1250-400 Opt CO.2 400 Amp
– ACTL-1250-600 Opt CO.2 600 Amp
Specifications
Environmental|
---|---
Temperature| 32° to 104° F (0° to 40° C)
Humidity| 5% to 85% Relative Humidity (non-condensing)
Location| Indoor Use Only
Dimensions and Weights
| Length| Width| Height| Weight
---|---|---|---|---
Module
(QO)| 4.97 in.
(12.63 cm)| 1.45 in.
(3.68 cm)| 2.60 in.
(6.61 cm)| .5 lbs
(.23 kg)
Shipping| 7.50 in.
(19.05 cm)| 4.30 in.
(10.92 cm)| 1.71 in.
(4.34 cm)| 1.0 lbs.
(.45 kg)
Power
Input Power
(powers the module)| 120V AC (+/- 10%) @ 60 Hz, 0.1A (max)
---|---
Signal Input| 0.333V AC @ 60Hz
Type of Action| Type 1 action
Standards
Wireless| Bluetooth 5 Low Energy (BLE)
– 2.4 GHz radio frequency
---|---
This meter will be tested and certified to the following standards:
ANSI C12.20-2015| American National Standard for Electricity
Meters – 0.5 Accuracy Class
ANSI C12.1-2014| American National Standard for Electric Meters
– Code of electricity Metering
Regulatory
Safety and Emissions | FCC Part 15 | UL | ICES 003 |
---|---|---|---|
Contains FCC ID: | PUU-HQC2SEM | ||
Contains IC: | 10798A-HQC2SEM | ||
RoHS | Compliant |
Recommended Load Center Types
Refer to the Features section to the right for compatibility.
Electrical and Safety Characteristics
Pollution Degree | 2 |
---|---|
Purpose of Control | Energy Monitoring |
Software | Class A |
Impulse Voltage | 2500V |
Construction of Control
Open Type| Independently mounted for flush mounting
Minimum Supported Release
Savant OS| da Vinci 10.x
Descriptions
A Multi-Page LCD screen that offers the following information:
– Real-time energy usage.
– Firmware and Mac Address of the module.
– UID of the connected Host
– Real-time Bluetooth status connectivity icon.
– Module set-up and calibration screens.
B PAIR Button – The PAIR button is a multi-use button. The duration that
the button is pressed and held determines the function that gets initiated:
– Press and Release – Cycles through the screens available on the LCD (POWER >
POWER > INFO 1 > INFO 2).
– Press and hold – Press and hold for 2 seconds to put the module into pairing
mode. Press and hold for greater than 5 seconds to reset the module.
C CT Connections – Connect a current transformer to each CT Connection
input port labeled 1 and 2, observing polarity when making connections. Refer
to the Install the Current Transformer section later in the document for
additional wiring information.
D Neutral – The model number of the module determines the type of neutral
connection on the module:
– Plug-on Neutral – Positioned on the bottom of the module is a neutral clip
that plugs directly onto the neutral bar.
– Pigtail Neutral – A neutral wire protrudes from the module’s rear and gets
wired to the neutral bar in the breaker panel.
E 120V AC Connection – Plug the module onto the 120V AC bus bar in the
breaker panel. The voltage on this connection powers the module.
Features
- The GPM-Q2SEM-00 and GPM-QP2SEM Smart Energy Monitor modules are compatible with Schneider/Electric Square D™ QO™ load centers.
- Energy monitoring; +/- 0.5% revenue grade accuracy / 1 sec sample time.
- The module communicates with a Panel Bridge Controller or Savant Power Director using Bluetooth Low Energy (BLE) technology.
- Color LCD display for easy identification.
ELECTRIC SHOCK! The 120V AC, 60 Hz source poses an electrical shock
hazard that has the potential to cause serious injury to installers and end
users.
CAUTION! Risk of Electric Shock – More than one disconnect switch may be
required to de-energize the device before servicing. Always disconnect the
power to the module before making any connections. ring Modules.
IMPORTANT! A licensed electrician is required to install any of Savant’s
Power and Energy Monitoring Modules.
Important Information
- Each Smart Energy Monitor requires two spaces in an electrical breaker panel.
- All wiring in the United States must be installed in accordance with the latest adopted edition of the National Electrical Code (ANSI/NFPA 70, NEC)
- All wiring in Canada must be installed in accordance with the latest adopted edition of the Canadian Electrical Code (CSA C222.2 CEC, Part 1) and any provincial or local requirements.
- Use only Savant-approved current transformers. A list of supported transformers is available in the Accessories section on the previous page.
- The largest current transformer offered by Savant supports wire up to a 750 kcmil conductor (with the jacket is just under 1 inch in diameter).
Installation into Breaker Panel
- Remove power from the breaker panel by switching off the panel’s main breaker.
- Position and install the Smart Energy Monitor Module into the slots where it will be installed. Press firmly until fully seated onto the appropriate bus bars.
- The next few sections describe how to install and wire a current transformer to the Smart Energy Monitor module.
Install the Current Transformer
The GPM-Q2SEM and GPM-QP2SEM module supports connecting up to two Savant- approved current transformers. See the approved list on the previous page. Instructions on wiring and orienting the transformer are explained below.
-
Toggle the electrical panel’s main breaker Off to remove power from the panel.
-
Remove the panel’s front cover and set it aside. Verify that power is removed from the circuit breakers using a voltage tester.
-
Separate the current transformer by squeezing the knurled panel and pulling/rotating the top open.
-
Place the current transformers around each of the conductors being monitored.
– Orient the current transformer so the arrow in the middle points towards the source i.e., breaker or utility meter. -
Close the current transformer around the conductor. For added security, wrap a cable tie around the CT or run it through the loops on the front.
-
Route the twisted black and white wires around the breaker panel back to the Smart Energy Monitor module. Route the wires so they don’t directly come in contact with a live bus bar or terminal.
-
Observing polarity, insert the wires into the supplied 4-pin connector and secure by turning screws clockwise. See the Making Connections section in this document for more information on attaching the wires to the connector.
HELPFUL : A negative current will be measured if the wires are reversed or the current transformer is installed backward. -
Repeat steps 3-7 to install a second current transformer if needed.
-
Ensure the 4-pin connector is fully seated into the SEM module and tighten the connector’s mounting screws to .18 ft-lb (.25 N-m) max.
-
Toggle the main breaker back to the On position and re-apply power to the electrical panel. The Current Transformer and Smart Energy Monitor module are ready to monitor the power consumed by the circuit the CT is monitoring.
Making Connections
-
Remove power if power is applied.
-
Pull to remove the terminal block from the Smart Energy Monitor’s rear panel.
-
With a small flat-bladed screwdriver, turn the screws on the top of the connector counterclockwise until the silver crimps on the front of the connector open enough to slide the wire into the square slot.
-
Strip back the insulation of each wire to 1/4 inch (6.5 mm). Insert the stripped wire into the proper port. Do not allow more than 1/8 inch (3.2 mm) of bare wire exposed. See image.
-
Turn the screws clockwise until the silver crimps tighten around the wire. Tug on the wire a bit to verify the wire is installed securely.
-
Continue until all wires are installed.
-
Plug the terminal block into the appropriate port on the Smart Energy Monitor.
-
Repeat steps 2-7 for all wires from the current transformer.
-
Reapply power.
Additional Information
– Savant Power Deployment Guide – Sol-Ark
System Overview
SEM Display Descriptions
NOTES
Smart Energy Monitor Module (Supports Eaton CH Style Load Centers) Quick Reference and Installation Guide
Box Contents
(1) Smart Energy Monitor Module (SEM)
– GPM-QP2SEM-xx w/Plug-on neutral
– GPM-Q2SEM-xx w/Pigtail type neutral
(1) 4-pin screw down plug-in connector (028-9395)
(1) Product Information and Regulatory Insert (009-1950)
(1) Quick Reference and Installation Guide (this document)
Accessories
Current Transformers
– ACTL-1250-250 Opt CO.2 250 Amp
– ACTL-1250-400 Opt CO.2 400 Amp
– ACTL-1250-600 Opt CO.2 600 Amp
Specifications
Environmental|
---|---
Temperature| 32° to 104° F (0° to 40° C)
Humidity| 5% to 85% Relative Humidity (non-condensing)
Location| Indoor Use Only
Dimensions and Weights
| Length| Width| Height| Weight
---|---|---|---|---
Module
(QO)| 4.97 in.
(12.63 cm)| 1.45 in.
(3.68 cm)| 2.60 in.
(6.61 cm)| .5 lbs
(.23 kg)
Shipping| 7.50 in.
(19.05 cm)| 4.30 in.
(10.92 cm)| 1.71 in.
(4.34 cm)| 1.0 lbs.
(.45 kg)
Power
Input Power
(powers the module)| 120V AC (+/- 10%) @ 60 Hz, 0.1A (max)
---|---
Signal Input| 0.333V AC @ 60Hz
Type of Action| Type 1 action
Standards
Wireless| Bluetooth 5 Low Energy (BLE)
– 2.4 GHz radio frequency
---|---
This meter will be tested and certified to the following standards:
ANSI C12.20-2015| American National Standard for Electricity
Meters – 0.5 Accuracy Class
ANSI C12.1-2014| American National Standard for Electric Meters
– Code of electricity Metering
Regulatory
Safety and Emissions | FCC Part 15 | UL | ICES 003 |
---|---|---|---|
Contains FCC ID: | PUU-HQC2SEM | ||
Contains IC: | 10798A-HQC2SEM | ||
RoHS | Compliant |
Recommended Load Center Types
Refer to the Features section to the right for compatibility.
Electrical and Safety Characteristics
Pollution Degree | 2 |
---|---|
Purpose of Control | Energy Monitoring |
Software | Class A |
Impulse Voltage | 2500V |
Construction of Control
Open Type| Independently mounted for flush mounting
Minimum Supported Release
Savant OS| da Vinci 10.x
Descriptions
A Multi-Page LCD screen that offers the following information:
– Real-time energy usage.
– Firmware and Mac Address of the module.
– UID of the connected Host
– Real-time Bluetooth status connectivity icon.
– Module set-up and calibration screens.
B PAIR Button – The PAIR button is a multi-use button. The duration that
the button is pressed and held determines the function that gets initiated:
– Press and Release – Cycles through the screens available on the LCD (POWER >
POWER > INFO 1 > INFO 2).
– Press and hold – Press and hold for 2 seconds to put the module into pairing
mode. Press and hold for greater than 5 seconds to reset the module.
C CT Connections – Connect a current transformer to each CT Connection
input port labeled 1 and 2, observing polarity when making connections. Refer
to the Install the Current Transformer section later in the document for
additional wiring information.
D Neutral – The model number of the module determines the type of neutral
connection on the module:
– Plug-on Neutral – Positioned on the bottom of the module is a neutral clip
that plugs directly onto the neutral bar.
– Pigtail Neutral – A neutral wire protrudes from the module’s rear and gets
wired to the neutral bar in the breaker panel.
E 120V AC Connection – Plug the module onto the 120V AC bus bar in the
breaker panel. The voltage on this connection powers the module.
Features
- All Eaton CH style Smart Energy Modules are compatible with Eaton CH 3/4 inch load centers.
- Energy monitoring; +/- 0.5% revenue grade accuracy / 1 sec sample time.
- The module communicates with a Panel Bridge Controller or Savant Power Director using Bluetooth Low Energy (BLE) technology.
- Color LCD display for easy identification.
ELECTRIC SHOCK! The 120V AC, 60 Hz source poses an electrical shock
hazard that has the potential to cause serious injury to installers and end
users.
CAUTION! Risk of Electric Shock – More than one disconnect switch may be
required to de-energize the device before servicing. Always disconnect the
power to the module before making any connections. ring Modules.
IMPORTANT! A licensed electrician is required to install any of Savant’s
Power and Energy Monitoring Modules.
Important Information
- Each Smart Energy Monitor requires two spaces in an electrical breaker panel.
- All wiring in the United States must be installed in accordance with the latest adopted edition of the National Electrical Code (ANSI/NFPA 70, NEC)
- All wiring in Canada must be installed in accordance with the latest adopted edition of the Canadian Electrical Code (CSA C222.2 CEC, Part 1) and any provincial or local requirements.
- Use only Savant-approved current transformers. A list of supported transformers is available in the Accessories section on the previous page.
- The largest current transformer offered by Savant supports wire up to a 750 kcmil conductor (with the jacket is just under 1 inch in diameter).
Installation into Breaker Panel
- Remove power from the breaker panel by switching off the panel’s main breaker.
- Position and install the Smart Energy Monitor Module into the slots where it will be installed. Press firmly until fully seated onto the appropriate bus bars.
- The next few sections describe how to install and wire a current transformer to the Smart Energy Monitor module.
Install the Current Transformer
The GPM-Q2SEM and GPM-QP2SEM module supports connecting up to two Savant- approved current transformers. See the approved list on the previous page. Instructions on wiring and orienting the transformer are explained below.
-
Toggle the electrical panel’s main breaker Off to remove power from the panel.
-
Remove the panel’s front cover and set it aside. Verify that power is removed from the circuit breakers using a voltage tester.
-
Separate the current transformer by squeezing the knurled panel and pulling/rotating the top open.
-
Place the current transformers around each of the conductors being monitored.
– Orient the current transformer so the arrow in the middle points towards the source i.e., breaker or utility meter. -
Close the current transformer around the conductor. For added security, wrap a cable tie around the CT or run it through the loops on the front.
-
Route the twisted black and white wires around the breaker panel back to the Smart Energy Monitor module. Route the wires so they don’t directly come in contact with a live bus bar or terminal.
-
Observing polarity, insert the wires into the supplied 4-pin connector and secure by turning screws clockwise. See the Making Connections section in this document for more information on attaching the wires to the connector.
HELPFUL : A negative current will be measured if the wires are reversed or the current transformer is installed backward. -
Repeat steps 3-7 to install a second current transformer if needed.
-
Ensure the 4-pin connector is fully seated into the SEM module and tighten the connector’s mounting screws to .18 ft-lb (.25 N-m) max.
-
Toggle the main breaker back to the On position and re-apply power to the electrical panel. The Current Transformer and Smart Energy Monitor module are ready to monitor the power consumed by the circuit the CT is monitoring.
Making Connections
-
Remove power if power is applied.
-
Pull to remove the terminal block from the Smart Energy Monitor’s rear panel.
-
With a small flat-bladed screwdriver, turn the screws on the top of the connector counterclockwise until the silver crimps on the front of the connector open enough to slide the wire into the square slot.
-
Strip back the insulation of each wire to 1/4 inch (6.5 mm). Insert the stripped wire into the proper port. Do not allow more than 1/8 inch (3.2 mm) of bare wire exposed. See image.
-
Turn the screws clockwise until the silver crimps tighten around the wire. Tug on the wire a bit to verify the wire is installed securely.
-
Continue until all wires are installed.
-
Plug the terminal block into the appropriate port on the Smart Energy Monitor.
-
Repeat steps 2-7 for all wires from the current transformer.
-
Reapply power.
Additional Information
– Savant Power Deployment Guide – Sol-Ark