MEAN WELL NPP-450 Ultra Wide Output Range Battery Charger & Power Supply Instruction Manual
- June 4, 2024
- MEAN WELL
Table of Contents
MEAN WELL NPP-450 Ultra Wide Output Range Battery Charger & Power
Supply
Features
- Mulit-function single unit battery charger or power supply operation modes selectable
- Output voltage and current adjustable via potentiometer
- 3-stage charging curve for charging mode
- -30~+70℃ wide operating temperature
- Multiple protections: Short circuit / Over load / Over voltage / Over temperature
- Thermal controlled DC fan for noise reduction
- Remote ON-OFF control
- Comply with 62368-1+60335-1/-2-29 dual certification
- Suitable for lead-acid (Pb) batteries
- Carry handle accessory available (Order NO.:DS-Carry handle, sold separately)
- 3 years warranty
Applications
- Radio system backup solution
- Electric scooter charger
- Camping car、Buses、Heavy duty truck、 Specialty vehicles
- Surveillance system
- Industrial automation machinery
- Industrial control system
- Mechanical and electrical equipment
Description
NPP-450 is a miniaturized dual-purpose charger and power supply. In addition to being used as a three- stage charger for lead-acid batteries, it can also be used as a constant voltage output power supply to drive general load. The operating mode can be quickly switched by plugging or unplugging a connector on the front panel. Other features include: ultra-wide voltage output, adjustable voltage via VR on the panel (10.5~21V, 21~42V, 42~80V, 54~100V), adjustable charging current (50~100%), built-in intelligent fan with variable speed based on temperature to reduce noise and extend fan lifetime, – 30~+70° C wide operating temperature, suitability for use in different environments, built-in remote ON/OFF control, compliance to IEC/EN/UL62368-1 and household EN60335-1/-2-29 dual safety, multiple built-in protections, and 3-year warranty. The NPP-450 is truly an intelligent, safe, and reliable universal dual-purpose charger and power supply with outstanding cost performance
Model Encoding
SPECIFICATION for Battery Charger mode (Default)
| MODEL | NPP-450-12 | NPP-450-24 | NPP-450-48 | NPP-450-72 | 
|---|
OUTPUT
|  BOOST CHARGE VOLTAGE(Vboost)(default)|  14.4V| 28.8V| 57.6V|
72V
FLOAT CHARGE VOLTAGE(Vfloat)(default)|  13.8V| 27.6V| 55.2V| 69V  
VOLTAGE ADJUSTABLE RANGE
|  10.5 ~ 21V| 21 ~ 42V| 42 ~ 80V| 54 ~ 100V
By built-in potentionmeter
MAX. OUTPUT CURRENT(CC)|  25A| 13.5A| 6.8A| 5.5A
CURRENT ADJUSTABLE RANGE
Note.3
|  12.5 ~ 25A| 6.75 ~ 13.5A| 3.4 ~ 6.8A| 2.75 ~ 5.5A
By built-in potentionmeter
MAX. POWER|  420W| 453.6W| 456.96W| 462W
RECOMMENDED BATTERY CAPACITY (AMP HOURS) Note.4|  90 ~ 300AH| 45 ~
155AH| 24 ~ 80AH| 19 ~ 64AH  
INPUT
|  VOLTAGE RANGE Note.5|  90 ~ 264VAC            127 ~ 370VDC
FREQUENCY RANGE|  47 ~ 63Hz
POWER FACTOR (Typ.)|  PF>0.98/115VAC, PF>0.95/230VAC at full load
EFFICIENCY (Typ.) Note.6|  92%| 93%| 93%| 93%
AC CURRENT (Typ.)|  4.5A/115VAC             2.2A/230VAC
INRUSH CURRENT (Typ.)|  COLD START 50A at 230VAC  
PROTECTION
| SHORT CIRCUIT Note.7| Protection type : Constant current limiting, charger will shutdown after 5 sec, re-power on to recover
OVER VOLTAGE
|  21.5 ~ 26V| 43 ~ 52V| 82 ~ 100V| 102 ~ 120V
Protection type : Shut down and latch off o/p voltage, re-power on to recover
OVER TEMPERATURE|  Shut down O/P voltage, recovers automatically after
temperature goes down  
FUNCTION
|  CHARGING STAGE|  3 stage only
CHARGER OK SIGNAL|  The TTL signal out, Charger OK = H(4.5 ~ 5.5V) ;
Charger failure or protection status =L( -0.5 ~ +0.5V)
BATTERY FULL SIGNAL|  The TTL signal out, Battery full = H(4.5 ~ 5.5V );
Charging = L(-0.5 ~ +0.5V)
REMOTE CONTROL|  Open : Charger stop charging             Short : Charger
normal work
FAN SPEED CONTROL|  Depends on internal temperature  
ENVIRONMENT
|  WORKING TEMP.|  -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY|  20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY|  -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT|  ±0.05%/℃ (0 ~ 50℃)
VIBRATION|  10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes  
SAFETY & EMC
(Note 8)
|  SAFETY STANDARDS|  CB IEC62368-1,IEC60335-1/2-29, Dekra BS
EN/EN62368-1,BS EN/EN60335-1/2-29, UL62368-1, EAC TP TC 004 approved
WITHSTAND VOLTAGE|  I/P-O/P:3KVAC  I/P-FG:2KVAC  O/P-FG:0.5KVAC
ISOLATION RESISTANCE|  I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/
70% RH  
EMC EMISSION
|  Parameter|  Standard|  Test Level / Note
Conducted| BS EN/EN55032 (CISPR32),BS EN/EN55014-1| Class B
Radiated| BS EN/EN55032 (CISPR32),BS EN/EN55014-1| Class B
Harmonic Current| BS EN/EN61000-3-2| Class A
Voltage Flicker| BS EN/EN61000-3-3| —–  
EMC IMMUNITY
|  BS EN/EN61000-6-2
Parameter|  Standard|  Test Level / Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air ; Level 2, 4KV contact
Radiated| BS EN/EN61000-4-3| Level 2, 3V/m
EFT / Burst| BS EN/EN61000-4-4| Level 2, 1KV
Surge| BS EN/EN61000-4-5| Level 2, 1KV/Line-Line,Level 3, 2KV/Line-Earth
Conducted| BS EN/EN61000-4-6| Level 2, 3Vrms
Magnetic Field| BS EN/EN61000-4-8| Level 1, 1A/m
Voltage Dips and Interruptions| BS EN/EN61000-4-11| >95% dip 0.5 periods, 30%
dip 25 periods, >95% interruptions 250 periods  
OTHERS
|  MTBF|  352.3K hrs min.        Telcordia SR-332 (Bellcore) ;
118.5K hrs min. MIL-HDBK-217F (25℃)
DIMENSION|  20513055mm  (LWH)
PACKING|  1.02Kg; 8pcs/ 10Kg / 1.71CUFT  
NOTE
|
- 
Modification for charger specification may be required for different battery specification. Please contact battery vendor and MEAN WELL for details. 
- 
All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. 
- 
Float charge voltage(Vfloat) adjustable via potentiomerter in battery charger mode. 
- 
This is MEAN WELL’s suggested range. Please consult your battery manufacturer for their suggestions about maximum charging current limitation. 
- 
Derating may be needed under low input voltages. Please check the derating curve for more details. 
- 
The efficiency is measured at 16.8V charge voltage(12V model), 33.6V charge voltage(24V model), 67.2V charge voltage(48V model), 84V charge voltage(72V model). 
- 
This protection mechanism is specified for the case the short circuit occurs after the charger is turned on. 
- 
The charger is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on 
 a 600mm*900mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com)
- 
The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft). 
Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
SPECIFICATION for Power Supply mode (Selectable via pin3 & 4 jumper of 14pins connector on panel)
| MODEL | NPP-450-12 | NPP-450-24 | NPP-450-48 | NPP-450-72 | 
|---|
OUTPUT
| DC VOLTAGE| 14.4V| 28.8V| 57.6V| 72V
VOLTAGE ADJUSTABLE RANGE
|  10.5 ~ 21V| 21 ~ 42V| 42 ~ 80V| 54 ~ 100V
By built-in potentionmeter
CURRENT ADJUSTABLE RANGE|  12.5 ~ 25A| 6.75 ~ 13.5A| 3.4 ~ 6.8A|
2.75 ~ 5.5A
RATED CURRENT|  25A| 13.5A| 6.8A| 5.5A
RATED POWER|  420W| 453.6W| 457W| 462W
RIPPLE & NOISE(max.)| 180mVp-p| 300mVp-p| 480mVp-p| 600mVp-p
VOLTAGE TOLERANCE|  ±1.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION|  ±0.5%| ±0.5%| ±0.5%| ±0.5%
LOAD REGULATION|  ±1.0%| ±1.0%| ±0.5%| ±0.5%
SETUP, RISE TIME|  1800ms, 60ms/230VAC at full load
HOLD UP TIME (Typ.)|  16ms/230VAC at 75% load  10ms/230VAC at full load  
INPUT
|  VOLTAGE RANGE Note.3|  90 ~ 264VAC            127 ~ 370VDC
FREQUENCY RANGE|  47 ~ 63Hz
POWER FACTOR (Typ.)|  PF>0.98/115VAC, PF>0.95/230VAC at full load
EFFICIENCY (Typ.)|  92%| 93%| 93%| 93%
AC CURRENT (Typ.)|  4.5A/115VAC            2.2A/230VAC
INRUSH CURRENT (Typ.)|  COLD START 50A at 230VAC  
PROTECTION
| ****
OVERLOAD
|  105 ~ 115% rated output power
Protection type : Constant current limiting, unit will shutdown after 5 sec,
re-power on to recover
SHORT CURRENT|  Protection type : Constant current limiting, unit will
shutdown after 5 sec, re-power on to recover  
OVER VOLTAGE
|  21.5 ~ 26V| 43 ~ 52V| 82 ~ 100V| 102 ~ 120V
Protection type : Shut down and latch off o/p voltage, re-power on to recover
OVER TEMPERATURE|  Shut down O/P voltage, recovers automatically after
temperature goes down  
FUNCTION
|  REMOTE CONTROL|  Open : Power OFF            Short : Power ON
DC OK|  The TTL signal out, DC OK = H(4.5 ~ 5.5V) ; Power supply failure
or protection = L(-0.5 ~ +0.5V)
FAN SPEED CONTROL|  Depends on internal temperature  
ENVIRONMENT
|  WORKING TEMP.|  -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY|  20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY|  -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT|  ±0.05%/℃ (0 ~ 50℃)
VIBRATION|  10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes  
SAFETY & EMC
(Note 4)
|  SAFETY STANDARDS|  CB IEC62368-1,IEC60335-1/2-29, Dekra BS
EN/EN62368-1,BS EN/EN60335-1/2-29, UL62368-1, EAC TP TC 004 approved
WITHSTAND VOLTAGE|  I/P-O/P:3KVAC  I/P-FG:2KVAC  O/P-FG:0.5KVAC
ISOLATION RESISTANCE|  I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/
70% RH  
EMC EMISSION
|  Parameter|  Standard|  Test Level / Note
Conducted| BS EN/EN55032 (CISPR32),BS EN/EN55014-1| Class B
Radiated| BS EN/EN55032 (CISPR32),BS EN/EN55014-1| Class B
Harmonic Current| BS EN/EN61000-3-2| Class A
Voltage Flicker| BS EN/EN61000-3-3| —–  
EMC IMMUNITY
|  BS EN/EN61000-6-2
Parameter|  Standard|  Test Level / Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air ; Level 2, 4KV contact
Radiated| BS EN/EN61000-4-3| Level 2, 3V/m
EFT / Burst| BS EN/EN61000-4-4| Level 2, 1KV
Surge| BS EN/EN61000-4-5| Level 2, 1KV/Line-Line,Level 3, 2KV/Line-Earth
Conducted| BS EN/EN61000-4-6| Level 2, 3Vrms
Magnetic Field| BS EN/EN61000-4-8| Level 1, 1A/m
Voltage Dips and Interruptions| BS EN/EN61000-4-11| >95% dip 0.5 periods, 30%
dip 25 periods,
95% interruptions 250 periods
OTHERS
|  MTBF|  352.3K hrs min.        Telcordia SR-332 (Bellcore) ;
118.5K hrs min.        MIL-HDBK-217F (25℃)
DIMENSION|  20513055mm  (LWH)
PACKING|  1.02Kg; 8pcs/ 10Kg / 1.71CUFT  
NOTE
|
- 
Modification for charger specification may be required for different battery specification. Please contact battery vendor and MEAN WELL for details. 
- 
All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. 
- 
Derating may be needed under low input voltages. Please check the derating curve for more details. 
- 
The PSU is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on 
 a 600mm*900mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.” (as available on http://www.meanwell.com)
- 
The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft). 
※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx
Block Diagram

Derating Curve

Function Manual
- Battery Charger or Power Supply Operation modes selectable via pin3 and pin4 jumper
 Between pin3 and pin4| Operation modes
 ---|---
 Jumper connected| Power supply mode
 Jumper removed| Battery charger mode (Default)
- Charging Curve (Charging Mode)
 State| NPP-450-12| NPP-450-24| NPP-450-48| NPP-450-72
 ---|---|---|---|---
 Constant Current| 25A| 13.5A| 6.8A| 5.5A
 Vboost| 14.4V| 28.8V| 57.6V| 72V
 Vfloat| 13.8V| 27.6V| 55.2V| 69V

- 
Charger OK / DC OK Signal 
 Charger OK / DC OK signal is a TTL level signal. The maximum sourcing current is 10mACharger OK / DC OK signal| Charger status
 ---|---
 “High” : 4.5 ~ 5.5V| Work normally
 “Low” : -0.5 ~ 0.5V| Failure or protection function activated
- 
Remote ON-OFF Control 
 The NPP-450 can be turned ON/OFF by using the “Remote Control” function.Between pin7 remote ON-OFF and pin8 +12Vaux| Charger status
 ---|---
 Short ( Pin 7 = 10.8 ~ 13.2V)| ON (Default)
 Open ( Pin 7 = -0.5 ~ 0.5V)| OFF
Mechanical Specification

- Connector Pin No. Assignment : HRS DF11-14DP-2DS or equivalent
 Pin No.| Assignment| Mating Housing| Terminal
 ---|---|---|---
 1,2,11~14| NC|
HRS DF11-14DS
or equivalent
|
HRS DF11-**SC
or equivalent  
3,4| Battery Charger or Power Supply mode selectable
5| Battery Full
6| Charger OK (Charger mode) or DC OK (Power supply mode)
7| Remote ON-OFF
8| +12V-AUX
9,10| GND-AUX  
- 
LED Status Table
 Charger (Default)LED Indicator| Status 
 Green| Float stage (stage 3) or full charged
 Red| Charging (stage 1 or stage 2)
 No Light| Abnormal
 Power supply mode
 LED Indicator| Status
 Green| Normal working
 No Light| Abnormal
- Control Pin No. Assignment : HRS DF11-14DP-2DS or equivalent
 Mating Housing| HRS DF11-14DS or equivalent
 ---|---
 Terminal| HRS DF11-**SC or equivalent
| Pin No. | Function | Description | 
|---|---|---|
| 1,2,11~14 | NC | —– | 
3,4
| Battery charger / Power supply| Open: Battery charger, Color of LED loading
indicator: Reference to battery charger. Short: Power supply, Color of LED
loading indicator :Green.
5| Battery Full| Battery Full Signal, referenced to GND-AUX(Pin 9 & 10). The
Signal is a TTL level signal. The maximum sourcing current is 10mA and only
for output.(Note.2) Low (-0.5 ~ 0.5V) : When the battery is charging. High
(4.5 ~ 5.5V) : When the battery is full.
6| Charger OK / DC OK| Charger OK / DC OK Signal, referenced to GND-AUX(Pin 9
& 10). The Signal is a TTL level signal. The maximum sourcing current is 10mA
and only for output.(Note.2) Low (-0.5 ~ 0.5V) : When the charger fails or the
protect function is activating. High (4.5 ~ 5.5V) : When the charger is
working properly.
7| Remote ON-OFF| Remote charger ON/OFF Function. The charger can turn the
output ON/OFF by dry contact between Remote ON-OFF and +12V-AUX.(Note.2) Short
(10.8 ~ 13.2V) : Charger ON ; Open(-0.5 ~ 0.5V) : Charger OFF ; The maximum
input voltage is 13.2V.
8| +12V-AUX| It is controlled by the Remote ON-OFF control.
9,10| GND-AUX| The signal return is isolated from the output terminal. (+V &
-V)  
Note1: Non-isolated signal, referenced to [GND(signal)].
Note2: Isolated signal, referenced to GND-AUX
Accessory List
Battery Charger or Power Supply mode of pin 3 and pin 4 mating pin along with NPP-450 (Standard accessory)
| Pin 3 and Pin 4 mating pin | Quantity | 
|---|---|
| 1FF1HMJ20-020-95BS or equivalent | 1 | 
Carry handle (Optional accessory, battery charger and pull handle should be ordered seperately)
| MW’s Order No. | Item | Quantity | 
|---|---|---|
| DS-Carry Handle | 1 | Handle | 
| 2 | Foot pad | 4 | 
| 3 | Screw | 2 | 
- 
Handle 
  
- 
Foot pad 
  
INSTALLATION MANUAL
Please refer to : http://www.meanwell.com/manual.html
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>