TRAXON AB444180035 SYMPL dmx Node Instructions
- June 15, 2024
- traxon
Table of Contents
AB444180035 SYMPL dmx
Node Instructions
AB444180035 SYMPL eDMX Node
AB444180035 e:cue
SYMPL dmx Node
Information for Use
Read the Information for Use and the Safety Instructions carefully. Subject to
modification without prior notice.
Typographical and other errors do not justify any claim for damages.
Modification of the product is prohibited.
This manual is designed for electricians, system administrators, and product
users.
All product names and trademarks mentioned in this manual are trademarks of
their respective owners.
Except for internal use, relinquishment of the instructions to a third party,
duplication in any type or form – also extracts – as well as exploitation and
/ or communication of the contents is not permitted.
Downloads and more information at: www.ecue.com
Safety instructions
Please read the safety instructions, provided in a separate manual, carefully. Make sure that the environmental, mounting, and installation prerequisites are met. This manual should be kept at a safe place and in reach of the device.
1.1 Symbols
The exclamation mark warns about possible damage of the device itself, to
connected devices, and to the user.
The information symbol gives general hints and informs about handling and
procedures for use of the device.
1.2 General instructions
— Connect cables and data only when the device is powered down.
— The maximum length of each connected cable is 30 m.
— When using a power supply unit, the device must be supplied by a separate
power supply that is certified according to the local regulations (e.g. SELV,
Class 2).
— If safety instructions are missing, please contact Taxon e:cue to receive a
new copy.
General device description
e:cue SYMPL Nodes are a system of interfaces for e:cue SYMPHOLIGHT only. They
provide various connection types like DMX512, DALI, digital inputs and outputs
etc. SYMPL Nodes always operate in online mode, as a device interface for
SYMPHOLIGHT. All interactions are initiated and controlled by SYMPHOLIGHT.
Connections between servers, Cores and Nodes are always made with e:net via
Ethernet.
The SYMPL dmx Node is a two-channel DMX and RDM interface for use with e:cue’s
lighting control solution SYMPHOLIGHT. It provides two independent DMX/RDM
interfaces for two DMX512 universes. The SYMPL dmx Node can be powered by an
external power supply or via Power-over-Ethernet. It is easily mounted on
standard 35 mm DIN rails, or with a key hole in the housing base on walls or
on any stable vertical surface. The SYMPL dmx Node is a simple, reliable and
easy to use interface solution for e:cue lighting control solutions with
SYMPHOLIGHT.
— To operate SYMPL Nodes a SYMPHOLIGHT version 2.0 or higher or a Lighting
Application Suite version 7.0 SR2 or higher is mandatory.
— Connections to the SYMPL dmx Node are not hotpluggable.
2.1 Delivery content
Delivery content for the e:cue SYMPL dmx Node (AB444180035):
- e:cue SYMPL dmx Node
- Safety instructions
- Welcome note
2.2 Product specifications
Dimensions (W x H x D)| 53.5 x 90.5 x 62 mm/ 2.1 x 3.6 x 2.4 in (excl.
fastening clip)
---|---
Weight| 100 g
Power supply| 24 V DC (terminal plug) wire gauge: 0.21 … 3.31 sum; or PoE IEEE
802.3af on RJ45
Power consumption| 2 W (incl. DMX termination)
Operating temperature| -20 … 50 °C / -4 … 122 °F
Storage temperature| -20 … 70 °C / -4 … 158 °F
Electrical safety| SELV
Op./storage humidity| 0 … 80% non-condensing
Protection Class| IP20
Housing material| Self extinguishing blend PC/ABS UL document E140692
Mounting| on 35 mm DIN rail (EN 60715), 3 units or with key hole
on any stable vertical surface
Certification| CE, ETL, UKCA
Interface specifications
Interfaces| 2 x DMX512/RDM, individually isolated (1 kV) 3-pin terminal plug
wire gauge: 0.08 … 1.31 sqmm
---|---
Interface|
specifications| Short circuit protected: I = 62 mA
Ethernet-Port| 1 x e:net 10/100 Mbit/s, RJ-45
User interface| LEDs for error, Ethernet activity, device status, DMX/RDM
status Identify button
2.3 Connectors and interfaces
View from top:
1| DMX output 1 (GND, DMX–, DMX+ left to right)| „4.4 DMX connection“ on page
08
---|---|---
2| DMX output 2 (GND, DMX–, DMX+ left to right)|
3| DMX/RDM 1 status LED| „2.4 User interface: LEDs“ on page
4| DMX/RDM 2 status LED| 05
5| Test / Error LED|
6| e:net LED (Ethernet, LAN activity)|
7| Status LED (Device status)|
8| Identify button| „2.5 Identify button: Identification &
Reset & Testing“ on page 06
9| Power supply (Vcc+, Vcc– left to right)| „4.5 Power supply“ on page 08
10| e:net / Ethernet| „4.3 Ethernet connection“ on page 08
2.4 User interface: LEDs
The SYMPL dmx Node has five LEDs on the front panel. The five LEDs show the
basic states of the SYMPL dmx Node.
LEDs
Status| On: If constantly on, the device is online. Server application is in
operation.
Blinking: If blinking in one second intervals, the device is offline, no
connection to a SYMPHOLIGHT server or Core is available. If blinking more
rapidly, the device is in bootloader mode.
---|---
e:net| Off: no link available.
On: link established.
Blinking: e:net traffic.
Test / Error| Off: no error detected.
Short-short-long sequence: Test mode active.
On: If constantly lights in red, an error occurred. This can be an internal
error or malfunction of the device, or an external error, e.g. a shortcut of
interface connections or alien power supply. Switch the device off and on. If
the error persists, check the wiring or contact Taxon e:cue Service.
Status + Test / Error| The Status and Test / Error LED blink simultaneously to
identify the SYMPL Node (enabled “Identify Interface Mode” in SYMPHOLIGHT).
DMX/RDM 1 and 2| Orange: DMX/RDM data outgoing.
Blue: data incoming.
Orange + White: port error.
2.5 Identify button: Identification & Reset & Testing
The Identify button has four functions: to send an Identify message (A), to
reset the Node (B), to test the installation (C), and to exit the error state
(D)
(A) A short press during operation in online mode sends an Identify message to
the server. This allows the Node of the installation to be associated with the
indicated Node in SYMPHOLIGHT.
(B) The Identify button can also be used to reset the device to factory state
or to stay in bootloader mode.
With a reset you restore the password and other properties by using the
Identify button. Please note that the device name and the offline content are
not reset:
-
Keep the Identify button pressed while powering up, Status and Test / Error LEDs light up at first.
Bootloader mode is signaled by a fast blinking Status LED. Release the button now. The device stays in bootloader mode to download a new firmware.
To exit the bootloader mode, short press the Identify button again. -
Press the Identify button until Status and Test / Error LEDs blink alternating, then blink together.
Releasing the button now resets the device to its factory settings. The password and other settings are reset to their default values. Please note that the Offline Content cannot be reset. To employ a reset Startup behavior, a restart of the device is required. -
Keeping the button pressed further on, the device proceeds to normal operation. No changes apply.
(C) Use the Identify button also to test the connected fixtures to ensure their correct installation. -
Access the Test mode of the SYMPL Node by double-pressing the Identify button during operation.
The Test / Error LED signals the Test mode by blinking short-short-long repeatedly. The Test mode starts at the first DMX port with blinking lights of all channels (test pattern 1). -
Single-press the Identify button to switch between the following Test patterns:
– Chasing lights at intervals of 96 channels (pattern 2).
– All channels at 100% (pattern 3).
– All channels off (pattern 4).
– Alternate between the individual DMX ports and the four test patterns. After the individual test of the DMX/RDM port 8, all DMX/RDM ports are tested simultaneously. Another short-press starts the test patterns from the beginning. -
Exit the Test mode any time by double-pressing the Identify button again. The device proceeds to normal operation. The DMX/RDM LEDs no longer flicker and the Test / Error LED is off.
(D) Short press the Identify button if an error occurs and you want to exit the error mode. The device will switch back to normal activity if the cause of error is eliminated. The Node might reboot.
General remarks
3.1 Transport
Only transport the device in its original packaging. This protects the device
from damage.
3.2 Unpacking
Only unpack the e:cue SYMPL dmx Node at its installation location. To protect
the device against condensation water, unpack it and wait until all moisture
remaining in the device has evaporated.
Condensation can occur when the device is moved from a cold to a warm
location. Keep the packaging for use in case of further transport. Inspect all
parts for completeness regarding chapter „2.1 Delivery content“ on page 04. If
there is apparent damage to the device or parts are missing from the delivery
scope, please contact the Taxon e:cue support service.
3.3 Warranty regulations
Depending on the product, warranty regulations are of different duration. The
warranty time is usually noted in the quote and in the order confirmation. See
www.traxon-ecue.com/terms-and-conditions for details. Legal warranty
regulations apply in any case.
3.4 Maintenance and Repair
This device requires no maintenance.
— Before dismounting, appropriate measures must be taken to protect the
respective components against damage caused by electrostatic discharge (ESD
protection).
— Do not try to repair the device. Return it to your Traxone: cue distributor
for replacement or repair.
To update the firmware see „8 Firmware Update“ on page 12.
3.5 Disposal
Batteries and technical appliances must not be disposed of with domestic
waste, but should be handed in at the appropriate collection and disposal
points.
The proper disposal of packing materials and of the device is the
responsibility of the respective user and for his account; in all other
matters, the retrieval obligation for packing materials and the device is
subject to the statutory regulations.
3.6 Support
In case of technical problems or questions regarding installation and repair
please contact:
Traxone Technologies Europe GmbH
Customer Service
Karl-Schurz-Str. 38
33100 Paderborn, Germany
+49 (5251) 54648-0
support@ecue.com
Installation
— Connect cables and data only when the device is powered down.
— Each cable should not exceed a length of 30 m.
The installation of the SYMPL dmx Node consists of mounting the device,
connections to DMX devices, to e:net, and to power supply.
The sequence of cabling is not defined. Supply the SYMPL dmx Node with power
after all cabling is completed; it starts booting.
4.1 Installation conditions
Installation position | Terminals on top and bottom |
---|---|
Horizontal spacing | No spacing necessary |
Minimum vertical rail grid spacing | 115 mm (90 + 25 mm) (excluding conduit) |
Recommended vertical rail grid spacing | 160 mm (with 40 mm conduit) |
Installation location | Indoor |
4.2 Mounting process
The e:cue SYMPL dmx Node is designed to mount onto a 35 mm DIN rail (EN 60715)
in a vertical position.
- Clip the device to the rail from top.
- Gentle pressure is then applied to the top front to snap it in place. The SYMPL dmx Node has been mounted successfully.
You can also mount the e:cue SYMPL dmx Node on any flat vertical surface. Use 3 to 3.5 mm screws for the hanger hole.
For mechanical stability, mounting on a rail is recommended.
4.3 Ethernet connection
— Never connect more than one SYMPL Node in factory state to a network. The
identical IP addresses will conflict and disturb proper communication.
— The Ethernet port of the SYMPL Node is not designed for inter-building
connections with power and lighting transients. Use only intra-building
networks to connect the SYMPL Nodes and Cores.
The pin-assignment of the Ethernet port corresponds to RJ45 standards. You can
use every common Ethernet component, like cable. Connect the SYMPL dmx Node at
the designated Ethernet interface with a patch cable (RJ45, CAT5).
4.4 DMX connection
The SYMPL dmx Node can control two DMX512 universes with its two DMX ports.
Connect DMX devices to the SYMPL Node using 3-pin terminal plugs at the DMX
interface of the SYMPL Node.
The appropriate pin assignment is defined as follows: From left to right: GND,
DMX-, DMX+
It is recommended to use twisted pair cabling
4.5 Power supply
The e:cue SYMPL dmx Node can be powered via Power-over-Ethernet (PoE) or by an
external power supply (PSU).
PoE:
Connect an Ethernet connection from a power sourcing device.
External power supply:
Connect the SYMPL dmx Node to a 24 V DC power supply unit that complies with
the local regulations.
Present power supply equates to the status “On” or running of the SYMPL dmx
Node.
To connect the device to a power supply unit, use the provided 2-pole terminal
and lay the wires as stated on the front label. The voltage assignment is left
V+ and right V-.
Turn the power on when all cables are connected to the SYMPL dmx Node. The
device starts operating. The device is in operation when the LED Status is
flashing.
The SYMPL dmx Node is not suited for powering over a DC power supply network.
The device must be supplied by a separate power supply that is certified
according to the local regulations (e.g. SELV, Class 2).
Network configuration
The configuration of the e:cue SYMPL dmx Node is completely done via e:cue
SYMPHOLIGHT. See the SYMPHOLIGHT System Manual for details on configuration,
available at www.ecue.com.
The network properties of the device are preconfigured. The successful
installation of the power supply is required for changing the network
configuration. You can either adjust the network settings with SYMPHOLIGHT or
using the web interface of the device. Via the web interface extended DMX/RDM
settings are configurable.
5.1 Default network properties
The SYMPL dmx Node has as factory setting the default IP address
192.168.123.1. Subnet mask: 255.255.255.0.
DHCP is enabled by default.
Login credentials for the web interface of the SYMPL dmx Node:
The default password is: issue
To change the network configuration use either SYMPHOLIGHT or the web
interface of the SYMPL dmx Node:
5.2 Network configuration with SYMPHOLIGHT
- Open the context menu of the SYMPL dmx Node in the Setup tab of SYMPHOLIGHT by a right-click on the device.
- Select “Configure Network”:
- Define the IP address, the subnet mask and the DHCP settings to your needs:
- Click “Apply” to submit the changes.
The network configuration of the SYMPL dmx Node is completed.
5.3 Network configuration with the web interface
-
Open a common web browser on a connected PC. Enter the SYMPL dmx Node’s IP address into the address bar: e.g. http://192.168.123.1
The web interface of the SYMPL dmx Node is displayed: -
On the left side, select “Settings” and enter the default password ecue:
-
Click “Apply”. The Settings page is displayed:
-
Define the network settings at “Device Basics” to your needs. You can also change the password for entry to the web interfaces of the SYMPL dmx Node here.
-
Click “Submit” to apply the settings.
The network configuration of the SYMPL dmx Node is completed.
— The employment of a discrete network is recommended.
— Note down all employed and, if applicable, reserved IP addresses. Keep the
information for future network configurations.
— You can change the login password to the SYMPL dmx Node’s configuration page
and the device name of the SYMPL dmx Node at “Settings” page. Do not forget
the new password.
Extended DMX/RDM settings
DMX/RDM settings are configured via SYMPHOLIGHT at the properties of the SYMPL
dmx Node in the Setup Tab. Is the Node not connected to SYMPHOLIGHT, extended
DMX/RDM settings take effect.
Over the web interface of the SYMPL dmx Node you can define the extended
DMX/RDM properties for:
- the period of powering up until a show takes over (Startup Setting)
- the time of no e:net connection (Offline Setting) – after prior connection to a show
- DMX and RDM Break time and Mark
- DMX to RDM wait Switch time (RDM Packet Space).
These properties are only configurable when the device is not assigned to a
show. SYMPHOLIGHT must have had control once over the Node for the settings to
take effect.
To access the web interface, open a common web browser on a connected PC.
Enter the device’s IP address into the address bar: e.g.
http://192.168.123.1.
At Startup Setting and Offline Setting, the setting “send MARK” sends a MARK
(a logical one) on the bus: no data are sent to the fixtures and the DMX port
awaits further commands. With the setting “High Impedance”, the same behavior
without sending a MARK is configured. It is recommended to use “High
Impedance” for backup systems only.
Running Startup Setting is indicated by flashing DMX/RDM status LEDs.
Please note that when you select an content image (snapshot) at these
settings, the framerate of the displayed image is reduced to 20 FPS.
Test mode
– SYMPHOLIGHT v5.0 or higher needed-
The SYMPL dmx Node provides a Test mode for the connected DMX devices. The
Test mode is designed for
DMX luminaires. There are two kinds: using the Identify button and using the
web interface of the SYMPL dmx Node.
Please note that the Test mode overwrites all other DMX output like running
shows, Startup Setting’s or Offline Setting’s output for the time of testing.
A running show, the Startup and the Offline output respectively are reverted
to after exiting the Test mode.
The Test mode is indicated by flickering DMX/RDM LED(s) and the blinking Test
/ Error LED.
7.1 Test mode via Identify button
See section (C) on page 06 at “2.5 Identify button: Identification & Reset &
Testing”.
7.2 Test mode via Web interface
The web interface of the SYMPL dmx Node provides four different test patterns
and allows to change their properties.
To access the web interface, open a common web browser on a connected PC.
Enter the SYMPL dmx Node’s IP address into the address bar: e.g.
http://192.168.123.1.
Open the Test mode page by selecting “Test Mode” on the left side of the web
interface of the SYMPL dmx Node:
Click a button to choose a test pattern. Define the properties:
Property | Description |
---|---|
Output | DMX ports to run the test on. |
Channel Count | Total frame length (0 – 1024). |
Block Size | Block size in which to step through the frame length in channel |
count.
Offset| Start address of the first test loop (first channel = 1).
Value| Luminance of the test output (0 – 255).
Step Time| Delay between steps. Manual: Press the Test button to move the
block. Define the first
channel at “Start Address”.
Click “set” to run the test and to apply changes in the test settings.
Exit the Test mode by leaving the Test mode page, e.g. go to “Dashboard”, or
by double-pressing the Identify button.
Firmware Update
To update the SYMPL dmx Node, a connection of the SYMPL dmx Node to
SYMPHOLIGHT is required.
Updating with SYMPHOLIGHT
Use the usual update options in the Device Tree of the Setup tab in
SYMPHOLIGHT: select “Update firmware” in the context menu of the SYMPL dmx
Node or click the Update button in the head toolbar.
Dismounting
Before dismounting, appropriate measures must be taken to protect the
respective components against damage caused by electrostatic discharge (ESD
protection).
Disconnect all attached cables. Dismount the e:cue SYMPL dmx Node from the
rail by pulling the black DIN rail handle and unhitching the SYMPL dmx Node.
The dismounting is completed.
Certifications
Conforms to UL Std. 62368-1
Certified to CSA Std. C22.2 NO. 62368-1
Dimensions
All dimensions in mm
Edition:
18.07.23 [EN_SYMPL_dmx_Node_Setup_v3p0] Published by:
Traxone Technologies Europe GmbH
Karl-Schurz-Strasse 38
33100 Paderborn, Germany
©2023 Traxone Technologies Europe GmbH
All rights reserved
Traxone Technologies Europe GmbH
Sales Operations
Karl-Schurz-Str. 38
33100 Paderborn, Germany
+49 5251 54648-0
support@ecue.com Please check for the latest
updates and changes on the Traxone website.
© 2023 TRAXON TECHNOLOGIES. ALL RIGHTS RESERVED.
www.traxon-ecue.com
References
- e:cue Lighting Controls - Traxon e:cue Europe
- Traxon e:cue
- Terms and Conditions - Traxon e:cue North America