Roth QuickStop Sensor 1 Detect Small Leaks Installation Guide
- June 13, 2024
- Roth
Table of Contents
Roth QuickStop Sensor 1
Installation
Living full of energy
Roth QuickStop Sensor 1
Roth QuickStop Sensor 1 are a simple protection system against water intrusions leaks in non visible or difficult access areas. Function – If the sensor cable comes into contact with water between the two conductors, the actuator closes within 5 seconds, and the control unit will start beeping. The valve will stay closed and the controller will continue beeping until you manually either override the alarm for 12 hours, e.g. if the floor still is wet, but it is expected to be dry within 12 hours, or, if the sensor cable is dry again, cancel the alarm. The valve is made of stainless steel 316 and can be mounted in all domestic water installation after the water meter. The control unit can handle up to two 230V actuatores and two sensor cables. One 230V actuator is included in the package. The 230v socket can be used for any purpose up to 10A e.g. electric water heater. The sensor cable is self- adhesive and can be mounted on dry, smooth and non-dusty surfaces. The sensor cable is delivered in a roll of 4 m and can be cut with scissors in the desired length. To prevent the valve from getting stuck, there is a built-in valve exercise program in the control unit, which briefly closes the valve once a week. The closing takes place automatically after a 7 days +12 hours. If the shutdown occurs at an inconvenient time, you can cut off the power to the control unit for a short time 12 hours before the time you want the program to occur. Example:
- Device is plugged in on monday 10 am
- First program Sequence starts – monday 10 pm
- Subsequently starts – every monday 10 pm
If you want to connect a sensor cable directly to the control unit, do so before connecting it to 230V. Before use the control unit needs to have a sensor cable connected. To do that, open the cover, by pushing it down (down towards the two connectors) and and turn it up 90 degrees.
Pull the white protective foil off the sensor cable approx. 20 mm, so that the
adhesive surface is free. The side of the sensor cable that does not have the
copper conductors. If you are in doubt, you can feel with a fingernail if
there are two elevations on the cable, these are the copper conductors.
Press sensor tape firmly into the cover, and pull approx. 20 mm of the yellow
protective film of the sensor cable so that the contact surface of the cable
becomes free.
Press the cover down against the clamps and push it into place so it is locked.
Insert the actuator plug into the socket at the bottom. It does not matter if you use one or the other connector if you only use one actuator. REMEMBER to screw the plug tight with the delivered screw.
The QuickStop ball valve must be mounted on the domestic water installation
after the water meter.
If the QuickStop only needs to secure one tap, it can be mounted on the inlet
of the tap.
Remember that work on domestic water may only be carried out by authorized
companies.
If only one actuator is used, the empty plug must be mounted in the free plug
and screwed on.
Remove the white protective film and unwind the sensor cable at the place you
want protection against water.
Remove the yellow protective film from the sensor cable.
Use of the QuickStop Sensor 1 – Plug in the control unit in a 230V socket.
During startup, the controller detects how many sensor cables are connected in
the first three seconds, when it blinks twice. After three seconds, it will
flash once or twice, depending on how many sensor cables are installed. If one
or more sensor cables are mounted directly to the control unit, but the
control unit remains on and flashes green after start-up, the sensor cable is
not mounted correctly. Check the installation if necessary. turn the sensor
cable 180 degrees so that the opposite side is facing up. The side with the
copper conductors must face upwards.
After the start-up sequence, the controller goes into normal mode and lights
up green. If no sensor cables are connected to the control unit, it will stand
and flash green until the first wireless sensor is registered. The
installation of the sensor cable can be easily checked by placing a damp
finger on the sensor cable, if the sensor cable is installed correctly, the
con- trol unit will sound an alarm and shut off the water. The alarm can be
reset most easily by cutting off the power to the unit for 5 seconds.
alternatively, you can hold “ ” for 2 sec. to mute the alarm, then hold ” ”
for 2 sec. to open the valve. If you want to connect a sensor cable at a later
stage, the power to the control unit must be disconnected.
Normal mode:
- Control unit light green
- Valve is open
- 230V socket is turn on
Light indications on the control unit:
- Everything OK – Green
- Alarm – Red
- Alarm mute – Flashing red
- No sensor cable detected – Flashing green (only by startup)
- Discounted sensor cable – Flasing 4 times red, small break, and then flasing 4 times red.
Leakage register
Water is detected on a sensor. Investigate why there is water on the sensor
before you possibly interrupts the alarm.
Indicator – The logo on the control unit lights red – The control unit
sounds.
Solution – Mute the alarm, directly on the control unit by holding down “
” for 2 sec. If you want to open the water, do so by holding down “ ” for 2
sec.
By muting the alarm, the QuickStop is deactivated, ie it no longer monitors
the system for the next 12 hours, which can lead to water damage.
Manual opening/closing of the valve
If you want to operate the valve manually, it is possible.
A. Pull up the small adjustable pinhead (approx. 5 mm)
B. Turn clockwise to close the valve – turn counterclockwise to open REMEMBER
to push the impeller down again after manual operation, as otherwise the valve
will not be able to shut off the water afterwards and there is a risk of water
damage.
Tear off this page and place it on the control unit
Light indications on the control unit:
- Everything OK – Green
- Alarm – Red
- Alarm mute – Flashing red
- No sensor cable detected – Flashing green (only by startup)
- Discounted sensor cable – Flasing 4 times red, small break, and then flasing 4 times red.
peration of the control unit
- Mute alarms – Hold down the “ ” for 2 sec. (2 flashes)
- Open/close the valve manually – Hold down “ ” for 2 sec. (2 flashes)
Accessories til Roth QuickStop Sensor 1
4 m sensor cable SAP No. 17TE1000.006
½” actuator SAP No. 17TO1000,000
¾” actuator SAP No. 17TO1000.001
https://rebrand.ly/QR-fkr-QuickStop-Sensor
ROTH UK Ltd
1a Berkeley Business Park
Wainwright Road
Worcester WR4 9FA
Phone +44 (0) 1905 453424
E-Mail enquiries@roth-uk.com
technical@roth-uk.com
orders@roth-uk.com
accounts@roth-uk.com
roth-uk.com
ROTH DANMARK A/S
Centervej 5
3600 Frederikssund
Tlf. +45 4738 0121
E-mail: service@roth-danmark.dk
roth-danmark.dk| ROTH SVERIGE AB
Höjdrodergatan 22
212 39 Malmö
Tel. +46 40534090
Fax +46 40534099
E-mail: service@roth-sverige.se
roth-sverige.se| ROTH NORGE AS
Billingstadsletta 19
1396 Billingstad
Tel. +47 67 57 54 00
E-mail: service@roth-norge.no
roth-norge.no
facebook.com/RothNorge| ROTH FINLAND OY
Raaseporintie 9 (Talo 2)
10600 Tammisaari
Puh. +358 (0)19 440 330
S-posti: service@roth-finland.fi
roth-finland.fi
facebook.com/RothFinland
---|---|---|---
Installation Roth QuickStop Sensor_1_20221209
References
- borger.dk - din indgang til det offentlige
- Frontpage | Norge.no
- Hej! Welcome to sweden.se – the official website of Sweden
- UK.COM
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>