Eltako PTN12-230V Battery Supply Instruction Manual
- June 4, 2024
- Eltako
Table of Contents
23 001 802 – 1
Test pushbutton for emergency lighting systems with its own battery
supply
PTN12-230V
Only skilled electricians may install this electrical equipment otherwise there is the risk of fire or electric shock!
Temperature at mounting location: -20°C up to +50°C.
Storage temperature: -25°C up to +70°C.
Relative humidity: annual average value <75%.
Test push button for emergency lighting systems with its own battery supply. 1 CO contact 16 A/250 V AC. Off-delay settable between 10 and 180 minutes. Only 0.5 watt standby loss.
Modular device for DIN-EN 60715 TH35 rail mounting. 1 module = 18 mm wide, 58
mm deep.
Supply voltage 230V, 50/60Hz.
Off-delay 10, 20, 30, 40, 50, 60, 90, 120, 150 and 180 minutes settable with
rotary switch. When the supply voltage is applied, the green LED lights up.
The emergency lighting system with its own battery supply is connected to
terminals 16 and N and thus connected to the supply voltage.
Pressing the TEST button on the PTN12 the relay is energized and the contact
changes from 16 to the 18. Therefore the emergency lighting system is
disconnected from the supply voltage and the yellow LED lights up. At the same
time, the set time is started at which end the relay drops back, the contact
switches from 16 to 18 and the emergency lighting system is applied again to
the supply voltage. During the time lapse, the green LED flashes regularly.
The TEST button can be operated any number of times during the time lapse
without affecting it. By pressing the button a long time (green LED flashes
nervously) >2 seconds, the time lapse can be terminated.
When the supply voltage fails during time lapse, it will be switched-off
defined. When the relay is energized during the off-delay, the power loss
increases to 1 watt.
If the emergency lighting system requires a larger current than 16A, a
contactor with normally closed contact must be inserted according to the
circuit diagram.
Typical connections
Direct control of the emergency light systems I≤16A; Emergency light systems with own battery supply
Control of emergency light systems via electric contactor I>16A; Emergency light systems with own battery supply
Technical data
Contact material/ contact gap | AgSnO2 /0.5 mm |
---|---|
Rated switching capacity | 16A/250V AC |
Incandescent lamp and halogen lamp load I on ≤ 70A/10 ms | 2300 W |
Compact fluorescent lamps with EVG and energy saving lamps ESL | 15×7 W |
10×20 W
Life at rated load, cos φ = 1 for incandescent lamps 1000 W at 100/h| >105
Maximum conductor cross-section| 6 mm2
Two conductors of same cross-section| 2,5mm2
Screw head| slotted/crosshead, pozidriv
Type of enclosure/ terminals| IP50/IP20
Time on| 100%
Max./min. temperature at mounting location| +50°C/-20°C
Stored energy time in the event of power failure (then total reset)| ≥ 0.2
seconds
Standby loss (active power) 230V| 0.5 W
Must be kept for later use!