Eltako FR62NP-230V Wireless Relay Actuator Instruction Manual
- October 27, 2023
- Eltako
Table of Contents
- Eltako FR62NP-230V Wireless Relay Actuator Instruction Manual
- Only skilled electricians may install this electrical equipment otherwise
- Wireless relay actuator 10 A/250 V AC.
- Zero passage switching.
- Typical connection
- Switch on/off confirmation telegrams:
- Read More About This Manual & Download PDF:
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Eltako FR62NP-230V Wireless Relay Actuator Instruction Manual
Only skilled electricians may install this electrical equipment otherwise
there is the risk of fire or electric shock!
Temperature at mounting location: -20°C up to +50°C.
Storage temperature: -25°C up to +70°C.
Relative humidity: annual average value <75%.
valid for devices from production week 18/21 (see bottom side of housing)
Wireless relay actuator 10 A/250 V AC.
1 NO contact or NC contact, not potential free. Standby loss only 0.4 watt.
For installation. 49×51 mm, 20 mm deep. The terminals are plug-in terminals
for conductor cross-sections of 0.2 mm2 to 2.5 mm2.
Up to 32 wireless pushbuttons and wireless window contacts can be taught in
using easy tap technology.
Bidirectional wireless switchable.
Zero passage switching.
Supply voltage, switching voltage and control voltage local 230 V.
If supply voltage fails, the device is switched off in defined mode. When the
supply voltage is restored, the device is switched off in a defined process.
After installation, wait until the short automatic synchronisation takes place
before the switched user is connected to the network.
In addition to the wireless control input via an internal antenna, this
wireless actuator can also be controlled locally by a conven- tional 230 V
control switch if fitted previously.
Glow lamp current is not permitted.
Typical connection
During teach-in, the function of the contact in quiescent position is defined
as NO or NC. Closes the contact with at least one open window; it can then
activate extraction hoods etc. or generate an alarm.
Opens the contact with at least one open window: it can then switch off
heaters or air conditioners.
Several wireless window contacts are linked together. The function is
determined by the last wireless window contact which is taught in.
Start-up:
After you switch on the power supply, the teach-in mode is automatically
active for 2 minutes provided the memory content is empty (as-delivered state)
and/or the teach-in mode is not blocked.
Readiness for teach-in is indicated by briefly switching the load on/off.
If no action takes place for 2 minutes, teach-in mode ends automatically.
This is signalled by switching the load on and off briefly.
Teaching-in sensors:
Wireless pushbutton as NO contact:
tap briefly 3 times;
Wireless pushbutton as NC contact:
tap briefly 4 times;
Wireless window contact FTK, FTKB: (EEP D5-00-01) as well as FTKE (EEP
F6-10-00) as NO contact: Briefly close and open the window 3 times
(close -> open -> close -> open -> close -> open window);
Wireless window contact FTK, FTKB: (EEP D5-00-01) as well as FTKE (EEP
F6-10-00) as NC contact: Briefly close and open the window 4 times
(close -> open -> close -> open -> close -> open -> close -> open window);
Wireless window handle sensor FFG7B as NO contact: (EEP A5-14-09)
Wireless window/door contact FTKB-hg, mTronic as NO contact: (EEP
A5-14-0A) Wireless window/door contact FFGB-hg as NO contact: (EEP
A5-14-01, -03, -0A)
Wireless window/door contact eTronic as NO contact: (EEP A5-14-01)
GFVS: (EEP A5-38-08);
During the teaching-in of the GFVS, con- firmation telegrams are switched on
and sent automatically.
Teaching-in a sensor, is confirmed by briefly switching the load on/off. The
teach-in mode is then active for a further 2 minutes. To prevent
unintentional teach-in, the
teach-in mode is automatically blocked
2 minutes after the last teach-in. This is indicated by the load
switched on/ off briefly twice.
Unencrypted and encrypted sensors can be taught in.
Teach in encrypted sensors:
- Activate teach-in mode if
- Activate sensor encryption within 2
- Then teach in the encrypted sensor as described under ‘Teach in sensors’.
With encrypted sensors, use the ‘rolling code’, i.e. the code changes in each
tele- gram, both in the transmitter and in the receiver.
If a sensor sends more than 50 telegrams when the actuator is not active, the
sensor is no longer recognised by the active actuator and must be taught in
again as ‘encrypted sensor’. It is not necessary to teach in the function
again.
Block teach-in mode immediately:
Tap 3 times briefly and once long (>2 seconds) on a wireless pushbutton
that is already taught in or the wireless window contact.
With a wireless window contact, tapping briefly 3 times and once long = close
-> open -> close -> open -> close -> open -> close long (>2 seconds)-> open
window.
A block is indicated by switching the load
on/off twice briefly.
Unblock teach-in mode:
Tap 4 times briefly and once long (>2 seconds) on a wireless pushbutton
that is already taught in, the local push- button or the wireless window
contact. Briefly close and open the window
4 times briefly and 1 once long (close -> open -> close -> open -> close ->
open -> close -> open -> long close (>2 seconds) > open window).
Readiness for teach-in is indicated by briefly switching the load on/off.
Teach in confirmation telegrams from other actuators:
Unlock simplified learning mode:
- Tap an already taught-in wireless push- button (not central control pushbutton) or the local wired button 4 times briefly plus 2 times long (> 2 seconds). The readiness for teching-in is signaled by briefly switching the load on and off, this mode is active for 30
- Switch the actuator, which its confir- mation telegram has to be taught in, on or off with its wired button. The auto- matic locking is signaled immediately after teaching-in by briefly switching the load on and off
Confirmation telegram ‘ON’ (0x70 and 0x30) is taught-in as ‘Central ON’.
Confirmation telegram ‘OFF’ (0x50 and 0x10) is taught-in as ‘Central OFF’.
Clear memory content completely (restore as-delivered state):
- Switch power supply off/on.
- Tap 8 times briefly and once long
(>2 seconds) on a wireless pushbutton that is already taught in, the local
pushbutton or the wireless window contact.
Clear is indicated by switching the load on/off briefly.
Apply on ‘Teach in wireless pushbutton’
Switch on/off confirmation telegrams:
- Switch power supply off/on.
- Tap 7 times briefly and once long (>2 seconds) on a wireless push button that is already taught in, the local pushbutton or the wireless window contact.
ON is indicated by switching the load on/ off briefly twice.
OFF is indicated by switching the load on/ off briefly once.
Hereby, Eltako GmbH declares that the radio equipment type FR62NP-230V is in
compliance with Directive 2014/53/EU.
The full text of the EU declaration of conformity is available at the
following internet address: eltako.com
Must be kept for later use!
Eltako GmbH
D-70736 Fellbach
Technical Support English:
+49 711 94350025
technical-support@eltako.de eltako.com
Read More About This Manual & Download PDF:
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>