Eltako ES12DX Electronic Latching Switch User Guide
- May 15, 2024
- Eltako
Table of Contents
Eltako ES12DX Electronic Latching Switch
Impulse Switch
Only skilled electricians may install this electrical equipment otherwise there is the risk of fi re or electric shock!
Temperature at mounting location: -20°C up to +50°C.
Storage temperature: -25°C up to +70°C.
Relative humidity: annual average value <75%.
1 NO contact potential free 16 A/250 V AC, 230 V LED lamps up to 600 W, incandescent lamp load up to 2000 W. No standby loss. Modular device for DIN- EN 60715 TH35 rail mounting. 1 module = 18 mm wide, 58 mm deep.
With the patented Eltako Duplex technology (DX) the normally potential-free
contacts can still switch in zero passage when switching 230 V AC 50 Hz and
therefore drastically reduce wear. Simply connect the neutral conductor to the
terminal (N) and L to 1(L) for this. This results in an standby consumption of
only 0.1 watt.
If the contact is used for controlling switching devices which do not perform
zero passage switching themselves, (N) should not be connected because the
additional closing delay otherwise causes the opposite effect. Control voltage
110 V AC – 240 V AC at the control input A1/A2.
Very low switching noise.
No permanent power supply necessary, therefore no standby loss.
State-of-the-art hybrid technology combines advantages of non wearing
electronic control with high capacity of special relays.
By using a bistable relay coil power loss and heating is avoided even in
the on mode.
The relay contact can be open or closed when putting into operation. It
will be synchronised at first operation.
Same terminal connection as the electromechanical impulse switch S12-100- If this impulse switch is in a circuit, which is monitored by a FR12-230V mains disconnection relay, no additional base load is required. However, the monitoring voltage of the FR12-230V must be set to ‘max’. Control only through A1-A2.
Typical connection
If N is connected, the zero passage switching is active.
Technical data
230 V LED lamps | up to 200 W 4) with DX up to 600 W 4) I on ≤ 120 A/5 ms |
---|---|
110-240 V AC | Control voltage |
16 A/250 V AC | Rated switching capacity |
2000 W | Incandescent lamp load and halogen lamp load 1) 230 V |
1000 VA | Fluorescent lamp load with KVG* in lead-lag circuit or non |
compensated
15×7 W, 10×20 W 2)| Compact fluorescent lamps with EVG* and energy saving
lamps
none| Standby loss
* EVG = electronic ballast units; KVG = conventional ballast units
- For lamps with 150 W max.
- If zero passage switching is activated.
- For electronic ballast gears a 40fold inrush current has to be calculated. For steady loads of 1200 W or use the current-limiting relay SBR12.
- Due to different lamp electronics and depending on the manufacturer, the maximum number of lamps may be limited, especially if the wattage of the individual lamps is very low (e.g. with 2 W LEDs).
The strain relief clamps of the terminals must be closed, that means the screws must be tightened for testing the function of the device. The terminals are open ex works.
Manuals and documents in further languages:
https://eltako.com/redirect/ES12DX*110-240V
CUSTOMER SERVICES
Must be kept for later use!
We recommend the housing for operating instructions GBA14.
Eltako GmbH
D-70736 Fellbach
Technical Support English:
+49 711 94350025
technical-support@eltako.deeltako.com
07/2024 Subject to change without notice.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>