Eltako ES12DX Electronic Latching Switch User Guide

May 15, 2024
Eltako

Eltako ES12DX Electronic Latching Switch

Impulse Switch

Only skilled electricians may install this electrical equipment otherwise there is the risk of fi re or electric shock!

Temperature at mounting location: -20°C up to +50°C.
Storage temperature: -25°C up to +70°C.
Relative humidity: annual average value <75%.

1 NO contact potential free 16 A/250 V AC, 230 V LED lamps up to 600 W, incandescent lamp load up to 2000 W. No standby loss. Modular device for DIN- EN 60715 TH35 rail mounting. 1 module = 18 mm wide, 58 mm deep.

With the patented Eltako Duplex technology (DX) the normally potential-free contacts can still switch in zero passage when switching 230 V AC 50 Hz and therefore drastically reduce wear. Simply connect the neutral conductor to the terminal (N) and L to 1(L) for this. This results in an standby consumption of only 0.1 watt.
If the contact is used for controlling switching devices which do not perform zero passage switching themselves, (N) should not be connected because the additional closing delay otherwise causes the opposite effect. Control voltage 110 V AC – 240 V AC at the control input A1/A2.
Very low switching noise.

No permanent power supply necessary, therefore no standby loss.
State-of-the-art hybrid technology combines advantages of non wearing electronic control with high capacity of special relays.
By using a bistable relay coil power loss and heating is avoided even in the on mode.
The relay contact can be open or closed when putting into operation. It will be synchronised at first operation.

Same terminal connection as the electromechanical impulse switch S12-100- If this impulse switch is in a circuit, which is monitored by a FR12-230V mains disconnection relay, no additional base load is required. However, the monitoring voltage of the FR12-230V must be set to ‘max’. Control only through A1-A2.

Typical connection

If N is connected, the zero passage switching is active.

Technical data

230 V LED lamps up to 200 W 4) with DX up to 600 W 4) I on ≤ 120 A/5 ms
110-240 V AC Control voltage
16 A/250 V AC Rated switching capacity
2000 W Incandescent lamp load and halogen lamp load 1) 230 V
1000 VA Fluorescent lamp load with KVG* in lead-lag circuit or non

compensated
15×7 W, 10×20 W 2)| Compact fluorescent lamps with EVG* and energy saving lamps
none| Standby loss

* EVG = electronic ballast units; KVG = conventional ballast units

  1. For lamps with 150 W max.
  2. If zero passage switching is activated.
  3. For electronic ballast gears a 40fold inrush current has to be calculated. For steady loads of 1200 W or use the current-limiting relay SBR12.
  4. Due to different lamp electronics and depending on the manufacturer, the maximum number of lamps may be limited, especially if the wattage of the individual lamps is very low (e.g. with 2 W LEDs).

The strain relief clamps of the terminals must be closed, that means the screws must be tightened for testing the function of the device. The terminals are open ex works.

Manuals and documents in further languages:

https://eltako.com/redirect/ES12DX*110-240V

Manuals and documents in further languages

CUSTOMER SERVICES

Must be kept for later use!
We recommend the housing for operating instructions GBA14.

Eltako GmbH
D-70736 Fellbach
Technical Support English:
+49 711 94350025
technical-support@eltako.deeltako.com
07/2024 Subject to change without notice.