Eltako ER12DX-UC Switching Relay User Manual

June 1, 2024
Eltako

22 100 002 – 2,
22 100 003 – 1

Switching relay

ER12DX-UC

ER12DX/110-240V

Only skilled electricians may install this electrical equipment otherwise there is the risk of fire or electric shock!

Temperature at mounting location: -20°C up to +50°C.
Storage temperature: -25°C up to +70°C.
Relative humidity: annual average value <75%.

230V LED lamps up to 200W (with active DX up to 600W), incandescent lamp load 2000W. No standby loss.
Modular devices for DIN-EN 60715 TH35 rail mounting. 1 module = 18mm wide, 58mm deep.
ER12DX-UC: Universal control voltage 12..230V UC.
ER12DX/110-240V: Control voltage 110-240V AC.
Contact position indicator with LED.
By using a bistable relay coil power loss and heating is avoided even in the on mode.
The relay contact can be open or closed when putting into operation. It will be synchronised at first operation.
This relay is not suitable to feed back the switching voltage signal of a dimmer switch. Use only relays ESR12DDX-UC, ESR12NP230V+UC or ESR61NP-230V+UC for this purpose.
1 NO contact potential free 16A/250V AC. With the ELTAKO-Duplex technology the normally potential-free contacts can still switch in zero passage when switching 230V AC 50Hz and therefore drastically reduce wear. Simply connect the neutral conductor to the terminal (N) and L to 1(L) for this. This gives an standby consumption of only 0.1 Watt.

If the contact is used for controlling switching devices which do not perform zero passage switching themselves, (N) should not be connected because the additional closing delay otherwise causes the opposite effect. Same terminal connection as electromechanical switching relay R12-100-.

Typical connections

ER12DX-UC

ER12DX/110-240V:

If N is connected, the zero passage switching is active.

Technical data
230V LED lamps up to 200W3) with active DX up to 600W3) I on ≤ 120A/5ms

Control voltage
ER12DX-UC
ER12DX/110-240V| 12..230V
110-240V AC
Rated switching capacity| 16A/250V AC
Incandescent lamp load and halogen lamp load 1) 230V| 2000W
Fluorescent lamp load with KVG in lead-lag circuit or non compensated| 1000VA
Fluorescent lamps with KVG

shunt-compensated or wih EVG| 500VA
Compact fluorescent lamp with EVG
and energy saving lamps| 15x7W, 10x20W 2)
Standby loss| none

  • EVG = electronic ballast units; KVG = conventional ballast units 1)
    1) For lamps with 150W max.
  1. For electronic ballast gears a 40fold inrush current has to be calculated. For steady loads of 1200W use the current-limiting relay SBR12.
  2. Due to different lamp electronics and depending on the manufacturer, the maximum number of lamps may be limited, especially if the wattage of the individual lamps is very low (e.g. with 2W LEDs).

The strain relief clamps of the terminals must be closed, that means the screws must be tightened for testing the function of the device. The terminals are open ex works.

Manuals and documents in further languages:


https://eltako.com/redirect/ER12DX*110-240V_ER12DX-UC

Must be kept for later use!
We recommend the housing for operating instructions GBA14.

ELTAKO GmbH
D-70736 Fellbach
Technical Support English:
+49 711 94350025
   technical-support@eltako.de
eltako.com

15/2024 Subject to change without notice.