V80 Value Series Pure Sine Wave
Line Interactive UPS
700VA, 1000VA, 1500VA, 2000VA Models
User & Installation Manual
Important Safety Warning
This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate your UPS.
- To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area free of conductive contaminants. (See the specifications for the acceptable temperature and humidity range.)
- To reduce the risk of overheating the UPS, do not cover the UPS’ cooling vents and avoid exposing the unit to direct sunlight or installing the unit near heat emitting appliances such as space heaters or furnaces.
- Do not attach non-computer-related items, such as medical equipment, life-support equipment, microwave ovens, or vacuum cleaners to UPS.
- Do not plug the UPS input into its own output.
- Do not allow liquids or any foreign object to enter the UPS. Do not place beverages or any other liquidcontaining vessels on or near the unit.
- In the event of an emergency, press the OFF button and disconnect the power cord from the AC power supply to properly disable the UPS.
Transportation
- Please transport the UPS system only in the original package to protect against shock and impact.
Preparation
- Condensation may occur if the UPS system is moved directly from cold to warm environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate the environment.
- Do not install the UPS system near water or in moist environments.
- Do not install the UPS system where it would be exposed to direct sunlight or near heater.
- Do not block ventilation holes in the UPS housing.
Installation
How to determine the power requirements of your equipment
- Ensure that the equipment plugged into the battery power-supplied outlets does not exceed the UPS unit’s rated capacity. If rated unit capacities are exceeded, an overload condition may occur and cause the UPS unit to shut down or the fuse blow.
- There are many factors that can affect the amount of power that your computer system will require.
For optimal system performance keep the load below 80% of the unit’s rated capacity.
Hardware Installation Guide
- Your new UPS may be used immediately upon receipt. However, recharging the battery for at least 8 hours is recommended to ensure that the battery’s maximum charge capacity is achieved. Charge loss may occur during shipping and storage. To recharge the battery, simply leave the unit plugged into an AC outlet. The unit will charge in both the on and off position.
- With the UPS unit off and unplugged, connect the computer, monitor, and any externally powered data storage device.
- Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is protected by a fuse or circuit breaker and does not service equipment with large electrical demands.
- Depress the power switch to turn the unit on. The LCD indicator light will illuminate and the unit will “beep”.
- To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times.
- To store your UPS for an extended period, cover it and store with the battery fully charged. Recharge the battery every three months to ensure battery life.
Maintenance, Service, and Faults
The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel.
-
Caution – risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.
-
Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors.
-
To avoid electrical shock, turn off the unit and unplug it form the AC power source before servicing the battery.
-
Only persons are adequately familiar with batteries and with the required precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
-
Caution – risk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the ground.
Before touching, please verify that no voltage is present! -
Batteries may cause electric shock and have a high short-circuit current. Please take the precautionary measures specified below and any other measures necessary when working with batteries:
» Remove wristwatches, rings and other metal objects
» Use only tools with insulated grips and handles. -
When changing batteries, install the same number and same type of batteries.
-
Do not attempt to dispose of batteries by burning them. This could cause battery explosion.
-
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may be toxic.
-
When replacing batteries, replace with the same type and number of batteries or battery packs.
-
Do not dismantle the UPS system.
-
A battery can present a risk of electrical shock and high short-circuit current. The following precautions should be observed when working on batteries:
» Remove watches, rings, or other metal objects.
» Use tools with insulated handles.
» Wear rubber gloves and boots.
» Do not lay tools or metal parts on top of batteries.
» Disconnect charging source prior to connecting or disconnecting battery terminals.
» Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance.
Storage
- First turn off your UPS and disconnect its power cord from the wall outlet. Disconnect all cables con nected the UPS to avoid battery drain.
- The UPS should be stored in a cool dry location.
- Make sure the battery is fully charged before the UPS is stored.
- For extended storage in moderate climates, the battery should be charged for 12 hours every 3 months by plugging the power cord into the wall receptacle and turning on the main switch. Repeat it every 2 months in high temperature locations.
Basic Operation
Front and Top Panel Description
-
Input Circuit Breaker
The circuit breaker provides optimal overload protection. -
AC Inlet
Connect to utility power through the input power cord.
(IEC320 C14 for 700VA/1000VA/1500VA, IEC 320 C20 for 2000VA) -
AC outlet
The UPS provides outlets for connected equipment to insure temporary uninterrupted operation during a power failure and against surges and spikes. -
USB Port
This port allows connection and communication from the USB port on the computer to the UPS unit. -
Power On/Off Button
Press the power Button to turn the UPS ON or OFF. -
Setting Button
The audible alarm can be turned off/on by pressing this button 3s. -
LCD Display
The LCD will display the UPS status.
Definitions for Illuminated LCD Indicators
LCD Indicators
| Line mode
---|---
| Bat-mode
| Battery capacity
| Load capacity
| Fault
| Sound disable (Press the setting key 3s to disable and enable the buzzer
sound)
Troubleshooting
Problem | Possible Causes | Remedy |
---|
Abnormal
Mains normal but not works in AC mode| 1. AC Input missing| 1. Check AC
input connection.
2. Input Breaker is tripped| 2. Unplug the power cord of the UPS then press
the circuit breaker knob.
The UPS will not turn on.| The on/off Button is designed to prevent damage by
rapidly turning it off and on.| Turn the UPS off. Wait 10 seconds and then
turn the UPS on.
The unit is not connected to an AC outlet.| The unit must be connected to a
100- 127V 50/60Hz outlet.
The battery is worn out.| Contact technical support.
Mechanical problem.
Outlets do not provide power to equipment| Circuit breaker is tripped due to
overload| Turn the UPS off and unplug at least one piece connected equipment.
Unplug the power cord of the UPS then press the circuit breaker knob
Batteries are discharged| Allow the unit to recharge for at least 4 hours.
Unit has been damaged by a surge or spike.| Contact technical support.
Alarm code A51| Site Fail:
Line and neutral conductors of UPS Input are reversed or the Ground is
disconnected.| Check the input plug and socket.
Alarm code A56| Battery low:
Battery capacity is low, UPS will turn off soon| 1.Shut off non-essential
equipment.
2.Save your data and turn off the comouter.
Alarm code A64| Overload:
Your equipment requires more power than the UPS can provide.| 1. Shut off
non-essential equipment.
Alarm code A68| Over Temperature| 1. Shut off non-essential equipment.
Fault Codes
Fault
Fault code E09| Output Short : Output circuit short.| 1.Shut down the UPS
2.Your attached equipment may have problems, please remove them and check
again.
Fault code E14| Overload:
Your equipment requires more power than the UPS can provide.
It will shutdown.| Shut off non-essential equipment. If this solves the
overload problem, the UPS will transfer to normal operation.
Fault code E18| Fan fail :
Fan has been damaged.| 1.Shut down the UPS 2.Replace the fan
Fault code E19| Over Temperature| 1.Shut down the UPS. Restart the UPS to
Check the fan for operation and if the ventilation hole has been covered
2.Contact technical support for repair.
Specifications
Shipping List
- Line cord
- Rack Ear
- User manual
- USB cable
Obtaining Service
If the UPS requires Service:
- Use the TROUBLESHOOTING section in this manual to eliminate obvious causes.
- Verify there are no circuit breakers tripped.
- Call your dealer for assistance. If you cannot reach your dealer, or if they cannot resolve the problem, call Xtreme Power Conversion Corp Technical Support at 800.582.4524. Technical support inquiries can also be made at support@xpcc.com. Please have the following information available BEFORE calling the Technical Support Department:
• Your name and address.
• The serial number of the unit.
• Where and when the unit was purchased.
• All of the model information about your UPS.
• Any information on the failure, including LED’s that may or may not be illuminated.
• A description of the protected equipment, including model numbers if possible.
• A technician will ask you for the above information and, if possible, help solve your problem over the phone. In the event that the unit requires factory service, the technician will issue you a Return Mate- rial Authorization number (RMA).
If you are returning the UPS to Xtreme Power for service, please follow these procedures:
- Pack the UPS in its original packaging. If the original packaging is no longer available, ask the Technical Support Technician about obtaining a replacement set of packaging material. It is important to pack the UPS properly in order to avoid damage in transit. Never use Styrofoam beads for a packing material.
- Include a letter with your name, address, daytime phone number, RMA number, a copy of your original sales receipt, and a brief description of the problem.
- Mark the RMA number on the outside of all packages. Xtreme Power cannot accept any package without the RMA number marked on the outside of the boxes.
- Return the UPS by insured, prepaid carrier to the address provided by the Technician.
- Refer to the Warranty statements in this manual for additional details on what is covered.
Xtreme Power Conversion Limited Warranty
Xtreme Power Conversion (XPC) Corporation warrants Xtreme Power Conversion
equipment, when properly applied and operated within specified conditions,
against faulty materials or workmanship for a period of three years for
V80-Series products from the date of purchase. XPC Corporation warrants
internal batteries for a period of three years from the date of purchase. For
equipment sites within the United States and Canada, this warranty covers
repair or replacement, at the sole discretion of XPC Corporation. The customer
is responsible for the costs of shipping the defective product to XPC
Corporation. XPC Corporation will pay for ground shipment of the repaired or
replacement product.
This warranty applies only to the original purchaser. If equipment provided by
XPC Corporation is found to be Dead-on-Arrival (DOA), XPC Corporation will be
responsible for the costs of shipping product to and returning equipment from
the customer in a timely manner as agreed to with the customer, once the
customer has requested and received a Return Material Authorization (RMA)
number. DOA equipment is defined as equipment that does not properly function
according to user documentation when initially received and connected in
conjunction with proper procedures as shown in the user documentation or via
support provided by XPC Corporation personnel or authorized agents. This
warranty shall be void if (a) the equipment is repaired or modified by anyone
other than XPC Corporation or a XPC Corporation approved third party; (b) the
equipment is damaged by the customer, is improperly used or stored, is
subjected to an adverse operating environment, or is operated outside the
limits of its electrical specifications; or (c) the equipment has been used or
stored in a manner contrary to the equipment’s operating manual, intended use
or other written instructions. Any technical advice furnished by XPC
Corporation or a XPC Corporation authorized representative before or after
delivery with regard to the use or application of Xtreme Power Conversion
equipment is furnished on the basis that it represents XPC Corporations best
judgment under the situation and circumstances, but it is used at the
recipient’s sole risk.
EXCEPT AS STATED ABOVE, XPC Corporation DISCLAIMS ALL WARRANTIES, EXPRESSED OR
IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE. EXCEPT AS STATED ABOVE, IN NO EVENT WILL XPC Corporation BE LIABLE
FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES ARISING
OUT OF THE USE OF Xtreme Power Conversion EQUIPMENT, including but not limited
to, any costs, lost profits or revenue, loss of equipment, loss of use of
equipment, loss of software, loss of data, cost of substitutes, or claims by
third parties. Purchaser’s sole and exclusive remedy for breach of any
warranty, expressed or implied, concerning Xtreme Power Conversion equipment,
and the only obligation of XPC Corporation under this warranty, shall be the
repair or replacement of defective equipment, components, or parts; or, at XPC
Corporations sole discretion, refund of the purchase price or substitution of
an equivalent replacement product.
Xtreme Power Conversion Load Protection Policy
THIS POLICY IS NOT A WARRANTY. REFER TO THE XPC CORPORATION, INC. LIMITED
WARRANTY FOR INFORMATION CONCERNING THE WARRANTY FOR YOUR XPC PRODUCT. THE
LIMITATIONS AND CONDITIONS CONTAINED IN THIS POLICY DO NOT AFFECT THE TERMS OF
THE XPC LIMITED WARRANTY.
Definitions:
- “Product” means a Standard 120, 208, or 240 Volt power protection device that is used in the United States and Canada. This policy does not include custom manufactured products.
- “Power Disturbance” means an AC power line transient (telephone line or Local Area Network, if applicable), spike or surge.
- “Connected Equipment” properly connected electronic equipment
- “Fair Market Value” of damaged Connected Equipment as determined by XPC shall be the lower of (a) the average price the same or similar items are being sold for on eBay, (b) the price list of Orion Blue Book (or if such price list is no longer published, a published or announced price list reasonably selected by XPC), (c) the lowest price the same or similar items can be purchased for in the United States or (d) the total amount of all payment(s) you have or are entitled to receive from insurance, other warranties, extended warranties, a legal liability claim or from other sources or persons for the damaged Connected Equipment.
- “Purchaser” means the person or entity that originally purchased the Product from an authorized reseller or distributor of XPC Products. The Purchaser of this Product is protected, for the term of the XPC Limited Warranty, against certain losses caused by a Power Disturbance for properly connected electronic equipment (referred to as the “Connected Equipment”) subject to certain terms and conditions provided below. This policy applies only to the original purchaser of the Product. If the Product is transferred or sold to another person or entity, this policy is void. Load Protection Policy Dollar and Period Limits For purchasers that meet the qualifications and conditions set forth in this policy, XPC will provide reimbursement (cost of repair or fair market value as determined by XPC) during the period limits and up to the dollar limits stated as follows:
PRODUCT | DOLLAR LIMIT | PERIOD OF COVERAGE |
---|---|---|
V80 | 25,000 | Term of XPC Limited Warranty |
XST | 25,000 | Term of XPC Limited Warranty |
S70 | 25,000 | Term of XPC Limited Warranty |
XPRT 6kVA & 10kVA | 50,000 | Term of XPC Limited Warranty |
P80, P80g | 50,000 | Term of XPC Limited Warranty |
P90, P90L, P90g, P90Lg | 50,000 | Term of XPC Limited Warranty |
T90, T91 | 50,000 | Term of XPC Limited Warranty |
TX90, TX90i | 50,000 | Term of XPC Limited Warranty |
This Load Protection Policy is not deemed “first dollar” coverage. XPC’s
obligation is reduced by any amounts that the Purchaser is entitled to
recover, from other sources regarding the Connected Equipment, including, but
not limited to, insurance, other warranty, extended warranty, or legal
liability, regardless of whether or not the Purchaser makes a claim for
recovery.
Eligibility for Coverage Under the Load Protection Policy
- The Product must be registered on the XPC website, www.xpcc.com , within 10 days of purchase. All required information must be provided, and Purchaser should retain a copy for Purchaser’s records. When registering on the website, Purchaser must list all connected equipment that is directly connected to the product. Only those devices registered in that manner will be covered.
- All Connected Equipment must be UL or CSA approved.
- The Product must be plugged into a properly wired and grounded outlet. Use of input surge devices, extension cords, adapters, ground wires, or electrical connections not manufactured by XPC voids the XPC Load Protection Policy. No other surge protection device may be connected to the output sockets of the Product. The installation must comply with all applicable electrical and safety codes set forth pursuant to the NEC.
- The Product must have undeniable physical evidence of a Power Disturbance that directly and proximately caused the damage;
- The Connected Equipment must have been damaged by a Power Disturbance on a properly installed, grounded, and National Electric Code, (“NEC”), code-compliant 120, 208, 240 Volt AC power line in the United States or Canada, by a Power Disturbance on standard telephone land line or PBX telephone equipment line that is properly installed and connected to an RJ11 port on the Product; or by a Power Disturbance on a standard Local Area Network connection that is properly installed and connected to an RJ45 port on the Product and (d) is directly plugged into, and properly connected to, the Product in its original condition which was properly operated when a Power Disturbance passed through the Product and (i) exhausts the protection capacity of the Product or (ii) damages the Product.
- The Load Protection Policy does not apply if the Product has been operated in a failure mode or not in compliance with XPC operating instructions in the Product user’s manual, or if the Connected Equipment has not been operated in compliance with the instructions and manuals of its manufacturer/vendor.
- This policy is null and void if, XPC determines, in its sole discretion, that the Product has been tampered with or altered in any way.
What is Not Covered Under the Load Protection Policy:
The following damage is not covered by this Policy:
- Restoration of lost data and reinstallation of software.
- Damage from a cause other than AC power-line transients, except for damage due to telephone line, Local Area Network, or CATV transients, which is covered only if the Product offers such protection.
- DAMAGE CAUSED BY FAILURE TO PROVIDE A SUITABLE INSTALLATION ENVIRONMENT FOR THE PRODUCT (INCLUDING, BUT NOT LIMITED TO, LACK OF A PROPER SAFETY GROUND).
- Damage caused by the use of the Product for purposes other than those for which it was designed.
- Damage caused by accidents, or natural disasters, including but not limited to, fire, flood, and wind.
- Damage caused by abuse, misuse, alteration, modification, or negligence.
- Any labor costs or travel, room and board expenses associated with the repair and/or restoration of lost or damaged hardware, software or data.
EXCEPT AS EXPRESSLY PROVIDED IN THIS POLICY, XPC SHALL NOT BE LIABLE FOR ANY
DAMAGES WHATSOEVER, INCLUDING, BUT NOT LIMITED TO, DIRECT, INDIRECT, SPECIAL,
INCIDENTAL, CONSEQUENTIAL, OR MULTIPLE DAMAGES ARISING OUT OF THE USE OF THE
PRODUCT OR DAMAGE TO THE CONNECTED EQUIPMENT, REGARDLESS OF THE LEGAL THEORY
ON WHICH SUCH CLAIM IS BASED, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH
DAMAGE. SUCH DAMAGES INCLUDE, BUT ARE NOT LIMITED TO, LOSS OF PROFITS, LOSS OF
SAVINGS OR REVENUE, LOSS OF USE OF THE PRODUCT OR THE CONNECTED EQUIPMENT OR
ANY ASSOCIATED EQUIPMENT, LOSS OF SOFTWARE, COST OF CAPITAL, COST OF ANY
SUBSTITUTE EQUIPMENT, FACILITIES OR SERVICES, DOWNTIME, THE CLAIMS OF THIRD
PARTIES, INCLUDING CUSTOMERS, AND INJURY TO PROPERTY.
Submitting a Load Protection Policy Claim:
-
Any claim under the Load Protection Policy must be made within 10 days of the date of alleged damage to the Connected Equipment.
-
Call the XPC technical support department at 1-800- 582-4524 and obtain a Load Protection Policy Returned Material Authorization (RMA) number. Have information on all applicable insurance or other resources of recovery/payment that is available to
the Purchaser and the name of the power utility supplier for the location of the Connected Equipment. XPC will forward to the Purchaser a Load Protection Policy claims form, which must be completed and filed with XPC within 30 days.
• Mark the Load Protection Policy RMA number on the Product the Purchaser is returning.
• Pack the Product in its original packaging or similar packing materials if the original packaging has been discarded. Enclose the completed Load Protection Policy claim form and a copy of the Purchaser’s original sales receipt for the Product in the box.
• Mark the RMA number clearly on the outside of the box.
• Ship the Product (one-way shipping charges paid by the Purchaser) to:
XPC Corporation
230 Yuma Street
Denver, CO 80223
Attn: LPP RMA# -
XPC will evaluate the Product to determine its level of functionality, and will examine the Product for evidence of damage from a Power Disturbance.
• If XPCs’ evaluation provides no evidence of damage from a Power Disturbance, XPC will send to the Purchaser (i) a report summarizing the tests performed and (ii) a rejection of claim notice.
• If the Product shows evidence of damage from a Power Disturbance, XPC will request that all Connected Equipment for which a Load Protection Policy claim has been submitted, be sent for evaluation to either XPC or an authorized service center. If it is determined that the Connected Equipment has been damaged by a Power Disturbance, XPC will, in its sole discretion, issue payment to the Purchaser for either the cost of repair of the Connected Equipment or the Fair Market Value of the damaged Connected Equipment, up to the dollar limits stated above. XPC reserves the right to require the Purchaser to transfer title and deliver the Connected Equipment to XPC if it chooses to reimburse the Purchaser for the fair market value of the Connected Equipment. XPCs’ maximum liability shall be reduced to reflect all such other payments or sources of recovery, whether applied for or not. -
If XPC issues payment to the Purchaser to have the Connected Equipment repaired, the repair must be performed at a service center that is authorized by the manufacturer of the Connected Equipment. XPC reserves the right to contact the authorized service center directly to discuss repair costs and damage to the Connected Equipment to determine if it was caused by a Power Disturbance and the right to request that the service center forward the Connected Equipment or components of the Connected Equipment to XPC for inspection
-
Unless modified in writing signed by an officer of XPC and the Purchaser, the terms of this policy are the complete and exclusive agreement between the parties, superseding all prior agreements, oral or written, and all other communications between the parties relating to the subject matter of this agreement. No employee of XPC or any other party is authorized to make any representations beyond those made in this agreement concerning the Load Protection Policy.
XPC Corporation
230 Yuma Street
Denver, CO 80223
1.800.582.4524
Xtreme Power Conversion Corporation
www.xpcc.com
© 2022 Xtreme Power Conversion Corporation.
All rights reserved. (Rev 7/6/22)