Roth Touchline PL Controller 8 Channels Installation Guide

June 10, 2024
Roth

Roth Touchline PL Controller 8 Channels

Roth-Touchline-PL-Controller-8-Channels-PRODUCT

Product Information

The product is a control unit that operates with a 230V power supply. It is designed to control the temperature of a building’s heating system by pairing it with up to 22 actuators and sensors. The unit has a 230V pump output with a maximum load of 0.5A, and it comes with a glass fuse WT 6.3A (5 x 20mm).

Product Usage Instructions

  1. Warning: Before working on the controller always switch off the 230V power supply and prevent it from being accidentally switched on.
  2. Connect the brown wire to L and the blue wire to N for the actuators. Use Roth Project actuators 230V 1 watt, HVAC no. 7466275430. The maximum number of actuators that can be connected is 22 pcs, which can be divided into 3 zones of 4 pcs and 5 zones of 2 pcs.
  3. For the pump output, connect the cables and secure them with a cable strain relief. The maximum load for the pump output is 0.5A.
  4. Connect the controller unit to a 230V power supply. Once connected, the controller is ready for pairing with sensors. Please refer to the thermostat/sensor operation manual for instructions on pairing sensors.
  5. If the glass fuse needs to be replaced, turn off the 230V power before changing it. The recommended glass fuse is WT 6.3A (5 x 20mm).

WARNING
Risk of fatal electric shock from touching live connections. Before working on the controller always switch on the 230V power supply and prevent it from being accidentally switched on

OVERVIEW

Must be mounted on at surface or using a DIN rail (not incl.), screws max. Ø 3 mm.

Roth under our heating system

  •  Actuators, connect “brown” to L and “blue” to N.
  • Use Roth Project actuators 230V 1 watt, HVAC no. 7466275430.
  • Max. the number of actuators = 22 pcs. (3 zones of 4 pcs. and 5 zones of 2 pcs.).
  • 1230V pump output, max. load 0,5 A. Cables must be secured.Roth-Touchline-PL-Controller-8-Channels-FIG-4
  • Boiler/heat supply, potential free relay max. load 1 A.

Roth-Touchline-PL-Controller-8-Channels-FIG-5

  • Connect to 230V power, Controller is ready for the pairing of sensors. Please see the thermostat/sensor operation manual.
  • Glass fuse WT 6.3A (5 × 20mm). Turn off 230V power before changing.
  • ROTH UK Ltd.
  • Phone +44 (0) 1984 623982
  • E-mail:enquiries@roth-uk.com
  • roth-uk.com

Documents / Resources

| Roth Touchline PL Controller 8 Channels [pdf] Installation Guide
Touchline PL Controller 8 Channels, Touchline PL, Controller 8 Channels, Controller
---|---
| Roth Touchline PL Controller 8 Channels [pdf] Installation Guide
Touchline, Touchline PL Controller 8 Channels, PL Controller 8 Channels, Controller 8 Channels, 8 Channels

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Roth User Manuals

Related Manuals