algodue MFC150 Rogowski coil User Manual

June 12, 2024
algodue

algodue MFC150 Rogowski coil

INTRODUCTION

The manual is intended only for qualified, professional and skilled technicians, authorised to act in accordance with the safety standards provided for the electrical installations. This person must have appropriate training and wear suitable Personal Protective Equipment.

WARNING! It is strictly forbidden for anyone who does not have the above- mentioned requires to install or use the coil.

It is forbidden to use the coil for purposes other than intended ones, specified in this manual. The symbols on the product are following described:

Attention! Refer to the user manual.
Protected throughout by DOUBLE INSULATION or
REINFORCED INSULATION.
Do not apply around or remove from HAZARDOUS LIVE conductors without additional protective means.
Complies with the relevant European standards.
Underwriters’ Laboratory Inc. recognized component.

AVAILABLE MODELS

MODEL Built-in INTEGRATOR
MFC150
MFC150/F

SAFETY INSTRUCTIONS

The Rogowski coil must be installed in an environment which are according to the max operation conditions of the coil itself.

WARNING! The connection and installation of the Rogowski coil must be carried out only by qualified technicians aware of the risks involved to the presence of voltage and current.
Before carrying out an operation, check if:

  1. bare conductor wires are not powered, 2. there are no neighbour bare conductors not powered

NOTE: The Rogowski coil complies with UL 61010-1 and UL 61010- 2-032 standards and following amendments. The installation must be carried out in accordance with the standards in force, the instructions of this user manual and the coil insulation value in order to avoid any danger for people.

The Rogowski coil is a sensor for accurate measurement so it must be handled with care. Before use, read the following instructions carefully.

  • Do not use the product if damaged.
  • Always wear protective clothing and gloves when required.
  • Avoid to strongly twist, blow and to perform pulling load on the product: the measurement accuracy may be impaired.
  • Do not paint the product.
  • Do not put metallic labels or other objects on the product: the insulation may be impaired.
  • It is forbidden any use of the product different from the manufacturer specifications.

MOUNTING

WARNING! Before installing the coil round a conductor not insulated, check that it is not powered otherwise switch the circuit OFF.
WARNING! Check if the coil is properly installed: a bad locking can affect measurement accuracy and the coil will become sensitive to adjacent conductors or other sources of electromagnetic fields.

NOTE: Coil must not fit tightly round the conductor, therefore its internal diameter must exceed that of the conductor.

internal diameter must exceed that of the conductor.
To carry out the installation, proceed as follow:

  1. Fit the coil round the conductor, bringing the coil ends together.
  2. Lock the coil by turning the ring as indicated in picture A.

CONNECTIONS

The coil has an arrow indicating the load side.
In case of model WITHOUT integrator refer to picture B:

A = SOURCE
B = LOAD

  1. WHITE wire, OUT+
  2. BLUE wire, OUT3. SHIELD, connect to GND or OUT If the cable is provided with crimp pins:
  • YELLOW crimp pin, OUT+
  • WHITE crimp pin, OUT

In case of model WITH integrator refer to **picture C:

**

A = SOURCE
B = LOAD

  1. WHITE wire, OUT+
  2. BLACK wire, OUT3. RED wire, positive power, 4…26 VDC
  3. BLUE wire, negative power, GND
  4. SHIELD, connect to GND

The coil is protected against reverse polarity of the power supply

MAINTENANCE

Refer to the following instructions carefully for the product maintenance.

  • Keep the product clean and free of surface contamination.
  • Clean the product with a soft cloth damp with a water and neutral soap. Avoid to use corrosive chemical products, solvents or aggressive detergents.
  • Make sure the product is dry before further use.
  • Do not use or leave the product in particularly dirty or dusty environments.

TECHNICAL FEATURES

NOTE: For any doubt on the installation procedure or on product application, please contact our technical services or our local distributor.

COIL

Coil length| 250 … 3000 mm
Sensor internal diameter| 71 … 945 mm
Coil diameter| 8.3 ±0.2 mm
Jacket material| Thermoplastic polyurethane UL94-V0
Fastening| Bayonet holder
Weight| 150 … 500 g
ELECTRICAL CHARACTERISTICS FOR MODEL WITHOUT INTEGRATOR
Nominal output rate| 100 mV / kA @ 50 Hz (RMS values) Refer to the value indicated on the product label
Max measurable current| 100 kA
Coil resistance| 70 … 900 Ω
Positioning error| Better than ±1% of reading
Frequency| 50/60 Hz
Overvoltage category| 1000 V CAT III, 600 V CAT IV
Pollution degree| 2
Insulation test voltage| 7400 VRMS / 5 s
ELECTRICAL CHARACTERISTICS FOR MODEL WITH INTEGRATOR
Power voltage| 4 … 26 VDC
Max consumption| 5 mADC
Nominal output rate| 333 mV / FS (RMS values) FS changes according to the model: 1, 2, 5 kA Refer to the value indicated on the product label
Positioning error| Better than ±1% of reading
Frequency| 50/60 Hz
Overvoltage category| 1000 V CAT III, 600 V CAT IV
Pollution degree| 2
Insulation test voltage| 7400 VRMS / 5 s
CONNECTION CABLE FOR MODEL WITHOUT INTEGRATOR
Type| 3 x 22 AWG shielded
Length| 3 m. Other lengths on request: 5, 7, 10, 15 m
CONNECTION CABLE FOR MODEL WITH INTEGRATOR
Type| 5 x 22 AWG shielded
Length| 3 m. Other lengths on request: 5, 7, 10, 15 m
ENVIRONMENTAL CONDITIONS
Protection degree| IP67 or IP68 according to the model (not evaluated by UL)
Altitude| Up to 2000 m over sea-level
Operating temperature| -30 … +80°C
Storage temperature| -40 … +80°C
Relative humidity| 0 … 95%
Installation and use| Indoor
STANDARD COMPLIANCE
IEC, UL standards| UL 61010-1 Ed3, UL 61010-2-032, CAN/CSA-C22.2 No. 61010-1, IEC 60529