BEGA 50 337 Recessed Ceiling Downlight Instruction Manual
- June 13, 2024
- BEGA
Table of Contents
BEGA 50 337 Recessed Ceiling Downlight
DIMENSION
Instructions for use
Application
Recessed ceiling downlight · Indoor luminaire with symmetrical wide beam light
distribution. For installation in suspended ceilings of 5-25 mm in interior
applications.
Lamp
- Module connected wattage 17.6 W
- Luminaire connected wattage 21 W
- Rated temperature ta = 25 °C
- Ambient temperature ta max = 40 °C
50 337.1 K3
- Module designation LED-0838/930
- Color temperature 3000 K
- Color rendering index CRI > 90
- Module luminous flux 2670 lm
- Luminaire luminous flux 1935 lm
- Luminaire luminous efficiency 92,1 lm / W
50 337.1 K4
- Module designation LED-0838/940
- Color temperature 4000 K
- Color rendering index CRI > 90
- Module luminous flux 2715 lm
- Luminaire luminous flux 1967 lm
- Luminaire luminous efficiency 93,7 lm / W
Product Description
- Recessed LED ceiling luminaire
- with a remote power supply unit
- Luminaire housing made of cast aluminum
- Finish Colour white
- Reflector surface is made of pure aluminum
- Light-diffusing disc
- Fixing is achieved by using
- 2 fastening springs
- Recessed opening ø 220 mm
- Required installation depth 110 mm
- Connecting cable 2 x 1,0@
- External LED power supply unit
- 220-240 V x 0/50-60 Hz
- Safety Class II 2
- r – Safety mark
- c – Conformity mark
- Weight: 0.7 kg
This product contains light sources of energy efficiency class(es) D
Light technique
Symmetrical wide beam light distribution Half beam angle 73°
Safety
The installation and operation of this luminaire are subject to national
safety regulations. Installation and commissioning may only be carried out by
a qualified electrician. The manufacturer accepts no liability for damage
caused by improper use or installation. If subsequent modifications are made
to the luminaire, the person responsible for these modifications shall be
considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547. To achieve additional protection
against e. g. transients, etc. we recommend separate overvoltage protection
components. You can find them on our website at
www.bega.com.
Installation
Luminaire housing and external LED power supply unit must not be covered by
any heat-insulating materials. LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during
installation or relamping. Cover the recessed opening with the stop ring of
the luminaire housing. The luminaire housing is then fixed in the recessed
opening via two springs.
Installation in suspended ceilings:
A recessed opening of 220 mm with a minimum depth of 110 mm is required. The
lateral clearance from the installation housing to parts of the building must
be at least 50 mm. The minimal thickness of the ceiling panel must be 5 mm and
must not be greater than 25 mm. A ceiling panel with less than 5 mm thickness
must be reinforced on the reverse. The electrical connection must be made on-
site in the appropriate safety class on the LED power supply unit connecting
cable. A distribution box must be used. Ensure the correct assignment of the
connecting cable. Establish the main connection on the brown (L) and blue (N)
wires. Guide the LED power supply unit through the opening in the ceiling and
position it on the suspended ceiling. Place the LED unit on top of the
luminaire housing over the reflector and lock it in place by turning it to the
right. Compress the fastening springs of the luminaire housing on both sides
and slide the luminaire housing into the recessed opening. The fastening
springs lock into place behind the ceiling panel.
Cleaning Maintenance
Clean the luminaire regularly with solvent-free cleansers from dirt.
Replacing the LED module
- The designation of the LED module is noted on a label in the luminaire.
- The light color and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
- Disconnect the system and open the luminaire.
- Please follow the installation instructions for the
- LED module.
- Close the luminaire.
Spares
- LED power supply unit DEV-0310/700
- LED module 3000 K LED-0838/930
- LED module 4000 K LED-0838/940
- Reflector 76 001 622
CONTACT
- BEGA Gantenbrink-Leuchten KG
- Postfach 31 60
- 58689 Menden
- info@bega.com .
- www.bega.com.
References