DAUDIN iO-GRID m and FX5U Modbus RTU User Manual
- June 13, 2024
- DAUDIN
Table of Contents
DAUDIN iO-GRID m and FX5U Modbus RTU
Product Information
Part No. | Specification | Description |
---|---|---|
GFMS-RM01S | Master Modbus RTU, 1 Port | Main Controller |
GFDI-RM01N | Digital Input 16 Channel | Digital Input |
GFDO-RM01N | Digital Output 16 Channel / 0.5A | Digital Output |
GFPS-0202 | Power 24V / 48W | Power Supply |
GFPS-0303 | Power 5V / 20W | Power Supply Interface Module |
0170-0101 | 8 pin RJ45 female connector/RS-485 Interface | Interface Module |
Product Usage Instructions
MLESEC-FX5U Connection Setup
- Launch GX Works3 software.
- Select the Parameters menu from the Navigate on the left side.
- Click on 485 Connector under the Module Parameters menu.
FX5U Hardware Connection
- The connector is on the left side of the FX5U and uses RS485 connections.
- Connect the COM (RS485 A, B) on the left of the FX5U to the interface module (1/2) to convert it to a RJ45 connector before connecting it to the main controller.
FX5U Connection Setup
- Set up the communication format in Protocol Format.
- From the drop-down menu, select MODBUS_RTU Communication.
- From the drop-down menu, select None.
- From the drop-down menu, select 1bit.
- From the drop-down menu, select Equipment Baud.
- The communication format setting must be consistent with the device being connected.
- Reading of the communication register:
- Command functions are listed below:
Station No.| Function code| Register for reading| Data Amount for Reading|
Register for storage| Initial address of the command execution
---|---|---|---|---|---
01| 03| 10 00| 00 01
- Writing of the communication register:
- Command functions are listed below:
Station No.| Function code| Register for writing| Data Amount for Writing|
Register for reading| Initial address of the command execution
---|---|---|---|---|---
01| 10| 20 00| 00 02
Remote I/O Module System Configuration List
Product Description
- The interface module is used externally to convert FX5U’s communication module (Modbus RTU) to a RJ45 connector
- The main controller is in charge of the management and dynamic configuration of I/O parameters and so on.
- The power module and interface module are standard for remote I/Os and users can choose the model or brand they prefer.
MLESEC-FX5U Connection Setup
This section details how to use the GX Works3 software to connect FX5U. For more details, please refer to the “Commands/Universal FUN/FB” chapter of the MELSEC iQ-F FX5 Programming Manual
FX5U Hardware Connection
- The connector is on the left side of the FX5U and uses RS485 connections
- Connect the COM (RS485 A, B) on the left of the FX5U to the interface module (1/2) to convert it to a RJ45 connector before connecting it to the main controller
FX5U Connection Setup
- Launch GX Works3 and select the “Parameters” menu from the “Navigate” on the left side, then click on “485 Connector” under the “Module Parameters” menu
- Set up the communication format in “Protocol Format”
- Reading of the communication register
- Writing of the communication register Notes:
- iO-GRID ’s first GFDI-RM01N has the register address at 1000(HEX)
- iO-GRID ’s first GFDO-RM01N has the register address at 2000(HEX).
- Programming Example:
Control with one GFDI-RM01N and one GFDO-RM01N When DI_1000.0 has received a signal and is triggered, DO_2000.0 will output a signal as it is connected