DAUDIN iO-GRID m and FX5U Modbus RTU User Manual

June 13, 2024
DAUDIN

DAUDIN iO-GRID m and FX5U Modbus RTU

DAUDIN-iO-GRID-m-and-FX5U-Modbus-
RTU-product

Product Information

Part No. Specification Description
GFMS-RM01S Master Modbus RTU, 1 Port Main Controller
GFDI-RM01N Digital Input 16 Channel Digital Input
GFDO-RM01N Digital Output 16 Channel / 0.5A Digital Output
GFPS-0202 Power 24V / 48W Power Supply
GFPS-0303 Power 5V / 20W Power Supply Interface Module
0170-0101 8 pin RJ45 female connector/RS-485 Interface Interface Module

Product Usage Instructions

MLESEC-FX5U Connection Setup
  1. Launch GX Works3 software.
  2. Select the Parameters menu from the Navigate on the left side.
  3. Click on 485 Connector under the Module Parameters menu.
FX5U Hardware Connection
  1. The connector is on the left side of the FX5U and uses RS485  connections.
  2. Connect the COM (RS485 A, B) on the left of the FX5U to the interface module (1/2) to convert it to a RJ45 connector before connecting it to the main controller.
FX5U Connection Setup
  1. Set up the communication format in Protocol Format.
    • From the drop-down menu, select MODBUS_RTU Communication.
    • From the drop-down menu, select None.
    • From the drop-down menu, select 1bit.
    • From the drop-down menu, select Equipment Baud.
    • The communication format setting must be consistent with the device being connected.
  2. Reading of the communication register:
    • Command functions are listed below:

Station No.| Function code| Register for reading| Data Amount for Reading| Register for storage| Initial address of the command execution
---|---|---|---|---|---
01| 03| 10 00| 00 01

  1. Writing of the communication register:
    • Command functions are listed below:

Station No.| Function code| Register for writing| Data Amount for Writing| Register for reading| Initial address of the command execution
---|---|---|---|---|---
01| 10| 20 00| 00 02

Remote I/O Module System Configuration List

Product Description
  1. The interface module is used externally to convert FX5U’s communication module (Modbus RTU) to a RJ45 connector
  2. The main controller is in charge of the management and dynamic configuration of I/O parameters and so on.
  3. The power module and interface module are standard for remote I/Os and users can choose the model or brand they prefer.

MLESEC-FX5U Connection Setup

This section details how to use the GX Works3 software to connect FX5U. For more details, please refer to the “Commands/Universal FUN/FB” chapter of the MELSEC iQ-F FX5 Programming Manual

FX5U Hardware Connection
  1. The connector is on the left side of the FX5U and uses RS485 connections
  2. Connect the COM (RS485 A, B) on the left of the FX5U to the interface module (1/2) to convert it to a RJ45 connector before connecting it to the main controller
FX5U Connection Setup
  1. Launch GX Works3 and select the “Parameters” menu from the “Navigate” on the left side, then click on “485 Connector” under the “Module Parameters” menu
  2. Set up the communication format in “Protocol Format”
  3. Reading of the communication register
  4. Writing of the communication register Notes:
    • iO-GRID ’s first GFDI-RM01N has the register address at 1000(HEX)
    • iO-GRID ’s first GFDO-RM01N has the register address at 2000(HEX).
  5. Programming Example:
    Control with one GFDI-RM01N and one GFDO-RM01N When DI_1000.0 has received a signal and is triggered, DO_2000.0 will output a signal as it is connected