DAUDIN iO-GRID C PLC PROFINET Coupler Instruction Manual

October 30, 2023
DAUDIN

DAUDIN iO-GRID C PLC PROFINET Coupler

Product Information

Product Name
2301EN V1.0.0 & SIEMENS PLC PROFINET Connection Operating Manual

Table of Contents

  1. Example Remote I/O Module System Configuration List
  2. Coupler Parameter Settings
  3. Siemens S7-1200 Connection Setup

1. Example Remote I/O Module System Configuration List

Part No. Specification Remarks
GF2-C004T PROFINET Coupler
GF2-DI01T 16-channel digital input module, Sink, 24VDC
GF2-DQ01T 16-channel digital output module, Sink, 24VDC
GF2-AI01T 4-channel analog input module (-10… 10VDC,
0…10VDC0…5VDC)
GF2-AQ01T 4-channel analog output module (-10… 10VDC,
0…10VDC0…5VDC)
GFPS-0202 Power 24V / 48W

Product Description

  • The coupler connects to the communication port (PROFINET) on Siemens S7-120.
  • The coupler is in charge of the management and dynamic configuration of I/O parameters and so on.
  • The power module is standard for remote I/Os and users can choose the model or brand of power module they prefer.

Coupler Parameter Settings

This chapter explains how a coupler connects to Siemens S7-1200, detailed introduction on, please refer to the i-Designer User Manual.

Preceding Operation of Software Setup

  1. Connect with the coupler module using a Micro-USB cable.
  2. Plug your Micro-USB cable to the Micro-USB port on your coupler module.
  3. Make sure the fieldbus is powered and then open the i-Designer setup program.

Coupler Module Parameters Setup

Coupler module connection illustration

Before setting up the coupler module, please confirm that the I/O modules are lined up closely on the Fieldbus

Coupler Software Setup

  1. Make sure that the module is powered and connected to the USB port.
  2. Click to launch the software.
  3. Select C Series Module Configuration.
  4. Click on the Setting Module icon.
  5. Enter the Setting Module page for the C-series.
  6. Click on Connect.
  7. Please Stop the System warning appears.
  8. Click on System Stop.
  9. Select the coupler module and click on Auto Addressing.
  10. Once addressing is completed, modules will appear on the Module List on the left.
  11. Click on the coupler module to open the Setting Module page
  12. Type in the device name and if the transmission should continue once the connection is interrupted (Timelock at 0).
  13. Type in your IP address (default IP address:192.168.1.20).

Siemens S7-1200 Connection Setup

This chapter explains how to use the TIA Portal program to connect S7-1200 and a coupler and add a remote I/O module. For detailed information, please refer to the “SIMATIC STEP 7” section in the user manual

Siemens S7-1200 hardware connection
Siemens S7-1200 IP Address and Connection Setup
  1. Open the TIA Portal, click on “Device Configuration” and then the “PROFINET Port” menu
  2. Click on “Ethernet Address” and type in the IP address (same as the coupler at 192.168.1.XXX)
  3. GSDML Document Installation
    • Click on “Options” on the menu bar
    • Select “Manage GSD File” from the drop-down menu
    • Choose the GSDML file you want and click on “Install”
  4. Click on the “Topology View”
    • Select “PROFINET IO” on the right-side menu
    • Select “I/O” and choose to add “Dinkle I/O” to the PLC network
  5. Select “Network View”
    • Right-click on the I/O port and select “Assign to a new I/O controller”
  6. Double-click on the icon of GF2-C004T
  7. Select the IP address to connect to (the module’s default IP address is 192.168.1.20)
  8. VIII. Under the 【Equipment View】&【Hardware Menu】
    • Add modules in the same sequence as UI’s addressing
    • ※Attention! The sequence must be the same as UI’s addressing. Otherwise, the device cannot communicate normally.
  9. Click on “Network View”
    • Assign device names
  10. Right-click on the device, select “Compile” and download it to PLC
    • Hardware (completely rebuilt)
    • Software (fully rebuilt)
    • Download to equipment (hardware configuration)
    • Download to equipment (download all of the software)
  11. Register addresses are assigned based on the modules added EX: %I168.0 at the first DI, %I168.1 at the second DI, %IW2 at the first channel of AI, and %IW4 at the second channel of AIC