DAUDIN GFMS-RM01S Remote I O Module System User Manual
- June 9, 2024
- DAUDIN
Table of Contents
- DAUDIN GFMS-RM01S Remote I O Module System
- Product Information
- Product Usage Instructions
- 2.1 FATEK PLC Hardware Connection
- 2.2 FATEK PLC Connection Setup
- Remote I/O Module System Configuration List
- Product Description
- FATEK PLC Connection Setup
- FATEK PLC Connection Setup
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
DAUDIN GFMS-RM01S Remote I O Module System
Product Information
The GFMS-RM01S Remote I/O Module System Configuration includes a master Modbus RTU with one port, a digital input with 16 channels (GFDI-RM01N), a digital output with 16 channels (GFDO-RM01N), a power supply with 24V/48W (GFPS-0202), a power supply with 5V/20W (GFPS-0303), and an interface module with an 8-pin RJ45 female connector/RS-485 interface (0170-0101). The interface module is used externally to convert FATEK PLC RS485’s communication port (Modbus RTU) to a RJ45 connector. The main controller is in charge of the management and dynamic configuration of I/O parameters and so on. The power module and interface module are standard for remote I/Os, and users can choose the model or brand they prefer.
Product Usage Instructions
1. Remote I/O Module System Configuration List
Refer to the table of contents, and go to section 1 for the Remote I/O Module System Configuration List. This section provides a list of parts, specifications, and descriptions of the product components included in the system configuration.
2. FATEK PLC Connection Setup
Refer to section 2 for FATEK PLC Connection Setup. This chapter
explains how to use the WinProladder program to connect FATEK PLC
with the Remote I/O Module System Configuration.
2.1 FATEK PLC Hardware Connection
To connect the Remote I/O Module System Configuration to FATEK PLC, follow these steps:
- Locate the connection port on the top of the FATEK PLC machine. For example, take FBs-10MAR2-AC, which uses Port2 (RS485 pin).
- Connect Port2 (RS485 A/B) on the top of the machine to the interface module (1/2) to convert it into an RJ45 connector, which
will be connected to the main controller.
2.2 FATEK PLC Connection Setup
To set up the communication between FATEK PLC and the Remote I/O Module System Configuration using the WinProladder program, follow these steps:
- Launch WinProladder and set up the communication ports. This demonstration utilizes communication module CB55 RS485 with Port2 in its address. The communication parameter setting must be consistent to enable communication.
- Edit the program by clicking on the Set up program block diagram, then from the dropdown menu, select Communication Commands, and then select M-BUS.
- Select Function Commands:
- Pt: The address of the port for selecting a Modbus communication module
- SR: Starting registering for the communication program
- WR: The starting register running the commands will take up totally of 8 registers. In this example, we select 2, R5000, and R3000.
- Refer to Internal Related Relays for Communication Port. The form’s starting address must be the same as that of the register from the SR command.
- Set the Communication Commands.
Remote I/O Module System Configuration List
Part No. | Specification | Description |
---|---|---|
GFMS-RM01S | Master Modbus RTU, 1 Port | Main Controller |
GFDI-RM01N | Digital Input 16 Channel | Digital Input |
GFDO-RM01N | Digital Output 16 Channel / 0.5A | Digital Output |
GFPS-0202 | Power 24V / 48W | Power Supply |
GFPS-0303 | Power 5V / 20W | Power Supply |
0170-0101 | 8 pin RJ45 female connector/RS-485 Interface | Interface Module |
Product Description
- The interface module is used externally to convert FATEK PLC RS485’s communication port (Modbus RTU) to a RJ45 connector
- The main controller is in charge of the management and dynamic configuration of I/O parameters and so on.
- The power module and interface module are standard for remote I/Os and users can choose the model or brand they prefer.
FATEK PLC Connection Setup
This chapter explains how to use the WinProladder program to connect FATEK PLC with For detailed information, please refer to the Winproladder Manual
FATEK PLC Hardware Connection
- The connection port is on the top of the machine. Take FBs-10MAR2-AC for example. It uses Port2(RS485 pin) Connections for other communication modules
All FATEK’s RS485 communication modules have the following pins on the
terminal blocks (from top to bottom):
First pin : “+”
Second pin: “-”
Third pin: “Ground”
- Connect Port2 (RS485 A/B) on the top of the machine to the interface module (1/2) to convert it into a RJ45 connector, which will be connected to the main controller
FATEK PLC Connection Setup
-
Launch WinProladder and set up the communication ports
- This demonstration utilizes communication module CB55 RS485 with Port2 in its address
- The communication parameter setting must be consistent with to enable communication
-
Editing the program- Click on “Set up program block diagram”, then from the drop-down menu, select “Communication Commands” and then select “M-BUS”
-
Function Commands
- Pt: The address of the port for selecting a Modbus communication module
- SR: Starting register for the communication program
- WR: The starting register running the commands will take up totally 8 registers
In this example, we select ”2”, ”R5000” and ”R3000
-
Internal Related Relays****
Internal Related RelaysCommunication Port| Port Ready Indicating Relay
Port1| M1960
Port2| M1962
Port3| M1936
Port4| M1938 -
Establish a Communication Form The form’s starting address must be the same with that of the register from the SR command
-
Setting the Communication Commands
-
station number
-
From the drop-down menu, select “Read” or “Write” to PLC
-
With double-word data, select “2” for data length
-
Read ’s value to PLC R1’s address
’s register address
Note:
※ ’s first GFDI-RM01N has the register address at 1000(HEX) converted to
4096(DEC)+1, and the starting address at 404097
※ ’s first GFDO-RM01N has the register address at 2000(HEX) converted to
8192(DEC)+1, and the starting address at 408193