DAUDIN GFDO-RM01N Digital Output Module User Manual

October 30, 2023
DAUDIN

DAUDIN GFDO-RM01N Digital Output Module

Product Information

Product Name: 2301TW V3.0.0 iO-GRID M Digital Output
Module

Table of Contents:

  • Digital Output Module List
  • Product Description
  • Digital Output Module Specification
  • Digital Output Module Information
  • Module Installation/Disassembly
  • iO-GRID M Series Introduction
  • I/O Module Parameter Settings and Introduction

Digital Output Module List

Product No. Description Remarks
GFDO-RM01N 16-channel digital output module (sink, 24VDC, 0138 terminal
block)
GFDO-RM02N 16-channel digital output module (source, 24VDC, 0138 terminal
block)

Digital Output Module Specification

GFDO-RM01N

  • Type: Sink
  • Number of Channels: 16
  • Voltage: 24VDC
  • Terminal Block: 0138

GFDO-RM02N

  • Type: Source
  • Number of Channels: 16
  • Voltage: 24VDC
  • Terminal Block: 0138

Digital Output Module Information
Digital Output Module Dimension

  • Width: 101mm
  • Height: 90mm
  • Depth: 62mm

Digital Output Module Panel Information

  • LED Indicators: Power and Status
  • Power Supply: 24VDC +/- 20%
  • Operating Temperature: -10°C to +55°C
  • Storage Temperature: -20°C to +75°C

Digital Output Module Wiring Diagram

Please refer to the manual for wiring diagram information.

Module Installation/Disassembly

Installation

  1. Turn off power to the system.
  2. Mount the module onto the DIN rail.
  3. Connect the power supply to the module.
  4. Connect the load to the module.
  5. Turn on power to the system.

Removal

  1. Turn off power to the system.
  2. Disconnect the load from the module.
  3. Disconnect the power supply from the module.
  4. Remove the module from the DIN rail.

iO-GRID M Series Introduction

iO-GRID M Components
The iO-GRID M Series includes various modules such as digital input, digital output, analog input, and analog output. Each module can be used in combination to create a customized I/O system.

I/O Module Parameter Settings and Introduction

I/O Module Settings and Connections
Please refer to the manual for information on I/O module parameter settings and connections.

Product Usage Instructions

  1. Ensure the device is for indoor use only and not exposed to high temperature or high moisture environment.
  2. Do not try to disassemble or open the cover under any circumstance in order to avoid danger.
  3. Read the manual for environmental conditions and use the equipment in a controlled environment.
  4. Follow the instructions provided in section 4 for installation and removal of the module.
  5. Refer to section 6 for I/O module parameter settings and connections.

Digital Output Module List

Product No. Description Remarks
GFDO-RM01N 16-channel digital output module (sink, 24VDC, 0138 terminal
block)
GFDO-RM02N 16-channel digital output module (source, 24VDC, 0138 terminal
block)

Product Description
GFDO, digital output module series is specially designed for industrial applications. It’s the open-type industrial equipment which is intended for installation within enclosures supplied in the field. A digital output allows you to control a voltage with a controller. If the controller instructs the output to be high, the output will produce a voltage (about 24 volts). If the controller instructs the output to be low, its connected to ground and produces no voltage. And the circuit design & all the components of GFDO series are compliant with the latest requirements and standards of UL, CE & RoHS. It has a complete circuit protection design to resist overload, overvoltage and short circuit etc. It is avoided to damage & failure caused from improper operations.

Caution (ATTENTION):

  1.  THIS DEVICE IS FOR INDOOR USE ONLY, DON’T PUT OR USE IT IN HIGH TEMPERATURE AND HIGH MOISTURE ENVIRONMENT.

  2.  AVOID FALLING AND BUMPING OTHERWISE THE ELECTRICAL COMPONENTS WILL BE DAMAGED.

  3.  DON’T TRY TO DISASSEMBLE OR OPEN THE COVER UNDER ANY CIRCUMSTANCE IN ORDER TO AVOID DANGER.

  4.  IF THE EQUIPMENT IS USED IN A MANNER NOT SPECIFIED BY THE MANUFACTURER, THE PROTECTION PROVIDED BY THE EQUIPMENT MAY BE IMPAIRED.
    THE INSTALLATION THAT THE SAFETY OF ANY SYSTEM INCORPORATING THE EQUIPMENT IS THE RESPONSIBILITY OF THE ASSEMBLER OF THE SYSTEM.

  5. USE WITH COPPER CONDUCTORS ONLY. INPUT WIRING: MINIMUM 28 AWG, 85°C, OUTPUT WIRING: MINIMUM 28 AWG, 85°C

  6. FOR USE IN A CONTROLLED ENVIRONMENT. REFER TO MANUAL FOR ENVIRONMENTAL CONDITIONS.

  7. DISCONNECT ALL SOURCES OF SUPPLY BEFORE SERVICING.

  8. PROPER VENTILATION IS REQUIRED TO REDUCE THE RISK OF HAZARDOUS OR EXPLOSIVE GAS BUILDUP DURING INDOOR CHARGING. SEE OWNERS MANUAL.

Output Module Specification

GFDO-RM01N

Technical Specification

Number Of Outputs| 16
Load Voltage| 24 VDC (±10%)
Voltage Supply| 5 VDC via Dinkle Bus
Current Consumption| 135 mA @ 5 VDC
Load Type| Resistive Load, Nominal Load
Connection Type| Sink
Output Current Per Channel For Signal ( Max. )| 0.5A
Communication Interface| RS485 via Dinkle Bus
Communication Specification
Fieldbus Protocol| Modbus RTU
Format| N, 8, 1
Baud Rate Range| 1200-1.5 Mbps
General Specification
Dimension (WDH)| 12 x 100 x 97mm
Weight| 69g
Ambient Temperature (operation)| -10…+60˚C
Storage Temperature| -25˚C…+85˚C
Permissible Humidity(non-condensing)| RH 95%
Altitude Limit| < 2000 m
Ingress Protection (IP)| IP 20
Pollution Severity| II
Safety Approval| CE
Product Certification| UL / CSA / IEC 61010-2-201&-1
Wiring Range (IEC / UL)| 0.2 mm2 ~ 1.5 mm2 / AWG 28~16
Wiring Ferrules| DN00510D、DN00710D

GFDO-RM02N

Technical Specification

Number Of Outputs| 16
Load Voltage| 24 VDC (±10%)
Voltage Supply| 5 VDC via Dinkle Bus
Current Consumption| 135 mA @ 5 VDC
Load Type| Resistive Load, Nominal Load
Connection Type| Source
Output Current Per Channel For Signal ( Max. )| 0.5A
Communication Interface| RS485 via Dinkle Bus
Communication Specification
Fieldbus Protocol| Modbus RTU
Format| N, 8, 1
Baud Rate Range| 1200-1.5 Mbps
General Specification
Dimension (WDH)| 12 x 100 x 97mm
Weight| 69g
Ambient Temperature (operation)| -10…+60˚C
Storage Temperature| -25˚C…+85˚C
Permissible Humidity(non-condensing)| RH 95%
Altitude Limit| < 2000 m
Ingress Protection (IP)| IP 20
Pollution Severity| II
Safety Approval| CE
Product Certification| UL / CSA / IEC 61010-2-201&-1
Wiring Range (IEC / UL)| 0.2 mm2 ~ 1.5 mm2 / AWG 28~16
Wiring Ferrules| DN00510D、DN00710D

Module Information

Digital Output Module Dimension

GFDO-RM01N

DAUDIN-GFDO-RM01N-Digital-Output-Module-01

GFDO-RM02N

DAUDIN-GFDO-RM01N-Digital-Output-Module-02

Digital Output Module Panel Information
GFDO-RM01N

Terminal block connector definitions

Terminal block labeling| Connector definitions| Terminal block labeling| Connector definitions
---|---|---|---
11| Channel 1| 31| Channel 9
12| Channel 2| 32| Channel 10
13| Channel 3| 33| Channel 11
14| Channel 4| 34| Channel 12
21| Channel 5| 41| Channel 13
22| Channel 6| 42| Channel 14
23| Channel 7| 43| Channel 15
24| Channel 8| 44| Channel 16
| | S/S| Common port

GFDO-RM02N

Terminal block connector definitions

Terminal block labeling| Connector definitions| Terminal block labeling| Connector definitions
---|---|---|---
11| Channel 1| 31| Channel 9
12| Channel 2| 32| Channel 10
13| Channel 3| 33| Channel 11
14| Channel 4| 34| Channel 12
21| Channel 5| 41| Channel 13
22| Channel 6| 42| Channel 14
23| Channel 7| 43| Channel 15
24| Channel 8| 44| Channel 16
| | S/S| Common port

Digital Output Module Wiring Diagram
GFDO-RM01N

GFDO-RM02N

Installation/Disassembly

Installation

  1. Align the red arrow on the side of the module to the arrow on the DIN rail.
  2. Press the module down and the metal clamp will slide (thanks to its spring mechanism) and grab on the other side of the DIN rail. Continue to push down until the metal clamp “clicks”.

DAUDIN-GFDO-RM01N-Digital-Output-Module-07

*Note: Make sure the red arrows on the module and the rail are pointing the same direction.

Removal

  1. Use a screwdriver to pull the metal hook sideways and detach the module from the DIN rail.
  2.  Remove all modules from the DIN rail in reverse order of installation.

iO-GRID M Series Introduction
iO-GRID M series utilizes the standard Modbus communication protocol and supports Modbus RTU/ASCII and Modbus TCP. Please choose products and factory controllers to figure your system based on your communication protocol.

iO-GRID M Components
DINKLE Bus
Rail 1 to 4 are defined for power supply and rail 5 to 7 are defined for communication.

DAUDIN-GFDO-RM01N-Digital-Output-Module-09

DINKLE Bus Rail Definitions:

Rail Definition Rail Definition
8 4 0V
7 RS485B 3 5V
6 2 0V
5 RS485A 1 24V

Gateway Module
A gateway module converts between Modbus TCP and Modbus RTU/ASCII. The module provides two sets of external Ethernet ports to connect to the controller and the Internet
There are two types of gateway modules available: channel gateway module: Provides 4 RS485 ports to connect to a control module
Single-channel gateway module: No external connectivity for the RS485 ports.

The RS485 signals are transmitted via DINKLE Bus and I/O module.

Gateway module products information:

Product No. Description
GFGW-RM01N Modbus TCP-to-Modbus RTU/ASCII gateway module. 4 Ports
GFGW-RM02N Modbus TCP-to-Modbus RTU/ASCII gateway module. 1 Port

Control module
The control module manages I/O modules and sets up the configuration. Provides external RS485 ports to connect to the controller.

There are two types of control modules available:

  • Channel control module:
    Provides 3 external RS485 ports, suitable stations with 2 or more control modules. Among the RS485 ports, 2 of them will be connected to the controller and the control module of the next station

  • Single-channel control module:
    Provides one single RS485 port to connect to the controller, suitable for single-module stations.

Control module products information:

Product No. Description
GFMS-RM01N RS485 control module, Modbus    RTU/ASCII 3 Ports
GFMS-RM01S RS485 control module, Modbus    RTU/ASCII 1 Port

I/O Module

Dinkle offers different types of I/O modules with different functions:

Product No. Description
GFDI-RM01N 16-channel digital input module (source/sink)
GFDO-RM01N 16-channel digital output module (sink)
GFDO-RM02N 16-channel digital output module (Source)
GFAR-RM11 8-Channel relay module, grounded
GFAR-RM21 4-Channel relay module, grounded
GFAI-RM10 4-channel analog input module (±10VDC)
GFAI-RM11 4-channel analog input module (0…10VDC)
GFAI-RM20 4-channel analog input module (0… 20mA)
GFAI-RM21 4-channel analog input module (4… 20mA)
GFAO-RM10 4-channel analog output module (±10VDC)
GFAO-RM11 4-channel analog output module (0…10VDC)
GFAO-RM20 4-channel analog output module (0… 20mA)
GFAO-RM21 4-channel analog output module (4… 20mA)
GFAX-RM10 2-channel analog input module, 2-channel analog output module (±

10VDC)
GFAX-RM11| 2-channel analog input module, 2-channel analog output module (0…10VDC)
GFAX-RM20| 2-channel analog input module, 2-channel analog output module (0… 20mA)
GFAX-RM21| 2-channel analog input module, 2-channel analog output module (4… 20mA)

Product I/O Module Parameter Settings and Introduction

I/O Module Settings and Connections
I. I/O Module System Configuration List

Name/Product No. Description
GFDO-RM01N 16-channel digital output module (sink)
GFDO-RM02N 16-channel digital output module (Source)
GFTL-RM01 USB-to-RS232 converter
Micro USB cable Must have data transfer functionality
Computer USB-compatible

Module Initial Setting List

Product No.| Description| Station No.| Baud rate| Format
---|---|---|---|---
GFMS-RM01N| RS485 control module, RTU/ASCII| 1| 115200| RTU(8,N,1)
GFDI-RM01N| 16-channel digital input module (source/sink)| 1| 115200| RTU(8,N,1)
GFDO-RM01N| 16-channel digital output module (sink)| 1| 115200| RTU(8,N,1)
GFDO-RM02N| 16-channel digital output module (Source)| 1| 115200| RTU(8,N,1)
GFAR-RM11| 8-Channel relay module, grounded| 1| 115200| RTU(8,N,1)
GFAR-RM21| 4-Channel relay module, grounded| 1| 115200| RTU(8,N,1)
GFAI-RM10| 4-channel analog input module (±10VDC)| 1| 115200| RTU(8,N,1)
GFAI-RM11| 4-channel analog input module (0…10VDC)| 1| 115200| RTU(8,N,1)
GFAI-RM20| 4-channel analog input module (0… 20mA)| 1| 115200| RTU(8,N,1)
GFAI-RM21| 4-channel analog input module (4… 20mA)| 1| 115200| RTU(8,N,1)
GFAO-RM10| 4-channel analog output module (±10VDC)| 1| 115200| RTU(8,N,1)
GFAO-RM11| 4-channel analog output module (-10…10VDC)| 1| 115200| RTU(8,N,1)
GFAO-RM20| 4-channel analog output module (0… 20mA)| 1| 115200| RTU(8,N,1)
GFAO-RM21| 4-channel analog output module (4… 20mA)| 1| 115200| RTU(8,N,1)
GFAX-RM10| 2-channel analog input module, 2-channel analog output module (± 10VDC)| 1| 115200| RTU(8,N,1)
GFAX-RM11| 2-channel analog input module, 2-channel analog output module (0…10VDC)| 1| 115200| RTU(8,N,1)
GFAX-RM20| 2-channel analog input module, 2-channel analog output module (0… 20mA)| 1| 115200| RTU(8,N,1)
GFAX-RM21| 2-channel analog input module, 2-channel analog output module (4… 20mA)| 1| 115200| RTU(8,N,1)

etup Software Functions:
The setup software shows the I/O module station numbers, baud rates and data formats.

I/O Module Settings and Connections
Connect the Micro USB port and GFTL-RM01 (RS232 converter) to your computer and open the iO-Grid M Utility program to set up I/O module parameters

I/O module connection illustration:

DAUDIN-GFDO-RM01N-Digital-Output-Module-10

I/O module connection image:

DAUDIN-GFDO-RM01N-Digital-Output-Module-11

Please do now power the I/O module during the setup

i-Designer Program Tutorial

  1. Connect to the I/O module using GFTL-RM01 and a Micro USB cable
  2. Click to launch the software
  3. Select “M Series Module Configuration”DAUDIN-GFDO-RM01N-Digital-Output-Module-14
  4. Click on the “Setting Module” iconDAUDIN-GFDO-RM01N-Digital-Output-Module-15
  5. Enter the “Setting Module” page for M-series DAUDIN-GFDO-RM01N-Digital-Output-Module-16
  6. Select the mode type based on the connected module DAUDIN-GFDO-RM01N-Digital-Output-Module-17
  7. Click on “Connect” DAUDIN-GFDO-RM01N-Digital-Output-Module-18
  8. Set up I/O modules’ station numbers and communication format (must click on “Save” after changing them) DAUDIN-GFDO-RM01N-Digital-Output-Module-19

Digital Output Module Control Register Description

Digital Output Module Register Communication Method

  1. Use Modbus RTU/ASCII to write in single-chip digital output module registers The address for the digital output module register to be written is: 0x2000DAUDIN-GFDO-RM01N-Digital-Output-Module-20With no control module, RS485’s physical wire must be connected with an adapter to send the signal to the Dinkle Bus
    The configuration that uses Modbus RTU/ASCII to write single-chip digital output module registers is listed below: Name/Product No.| Description
    ---|---
    GFDO-RM01N| 16-channel digital output module (sink)
    GFDO-RM02N| 16-channel digital output module (Source)
    BS-210| Adapter
    BS-211| Adapter
  2. Use Modbus RTU/ASCII with control modules to write in digital output registers
    Once a digital output module is set up with a control module, it will automatically assign the digital output modules’ output records registers at the address of 0x2000
    Example:
    Two digital output module registers will at 0x2000 and 0x2001 DAUDIN-GFDO-
RM01N-Digital-Output-Module-21When using control modules, RS485 can connect to control modules with 0170-0101.

The configuration that uses Modbus RTU/ASCII with a control module to write in digital output modules is listed below:

Name/Product No. Description
GFMS-RM01S Master Modbus RTU, 1 Port
GFDO-RM01N 16-channel digital output module (sink)
GFDO-RM02N 16-channel digital output module (Source)
0170-0101 RS485(2W)-to-RS485(RJ45 interface)

Digital Output Module Register Format Information (0x2000, rewritable)
GFDO-RM01N/ GFDO-RM02N Register Format: Channel open-1; channel closed – 0; reserved value – 0.

Bit15 Bit14 Bit13 Bit12 Bit11 Bit10 Bit9 Bit8
Ch44 Ch43 Ch42 Ch41 Ch34 Ch33 Ch32 Ch31
Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
Ch24 Ch23 Ch22 Ch21 Ch14 Ch13 Ch12 Ch11

Example:

  • With all channels open: 1111 1111 1111 1111 (0xFF 0xFF);
  • With channel 1 to 8 open: 0000 0000 1111 1111 (0x00 0xFF);
  • With all channels closed: 0000 0000 0000 0000 (0x00 0x00).

Modbus function code 0x10 Demonstration

  1. Use Modbus RTU/ASCII to write in single-chip digital output module registers
    Modbus function code| Transmission example (ID:0x01)| Respond example (ID:0x01)|
    ---|---|---|---
    0x10| 01 10 20 00 00 01 02 FF FF| 01 10 20 00 00 01

In this example, we are writing in “0x2000” with the I/O module ID of “01”
When not using control modules for communications, the registers will be at 0x2000

  1. Use Modbus RTU/ASCII with control modules to write in digital output registers
    Modbus function code| Transmission example (ID:0x01)| Respond example (ID:0x01)
    ---|---|---
    0x10| 01 10 20 00 00 01 02 FF FF| 01 10 20 00 00 01

In this example, we are writing in “0x2000” with the control module ID of “01”
When using control modules for communications, the registers will start at 0x2000

  1. Supports Modbus function code
    Modbus function code| Transmission example (ID :0x01)| Respond example (ID :0x01)
    ---|---|---
    0x01| 01 01 00 00 00 10| 00 01 02 FF FF
    0x05| 01 05 00 00 FF 00| 01 05 00 00 FF 00
    0x06| 01 06 20 00 FF FF| 01 06 20 00 FF FF
    0x0F| 01 0F 00 00 00 10 02 00 01| 01 0F 00 00 00 10
    0x10| 01 10 20 00 00 01 02 FF FF| 01 10 20 00 00 01