DAUDIN AS300 Series Modbus TCP Connection User Guide

June 9, 2024
DAUDIN

DAUDIN AS300 Series Modbus TCP Connection

DAUDIN-AS300-Series-Modbus-TCP-Connection-PRODUCT-
IMG
Connection Operating Manual

Remote I/O Module System Configuration List

Part No. Specification Description
GFGW-RM01N Modbus TCP-to-Modbus RTU/ASCII, 4 Ports Gateway
GFMS-RM01S Master Modbus RTU, 1 Port Main Controller
GFDI-RM01N Digital Input 16 Channel Digital Input
GFDO-RM01N Digital Output 16 Channel / 0.5A Digital Output
GFPS-0202 Power 24V / 48W Power Supply
GFPS-0303 Power 5V / 20W Power Supply
0170-0101 8 pin RJ45 female connector/RS-485 Interface Interface Module

Product Description

  1. The gateway is used externally to connect with AS300’s communication port (Modbus TCP).
  2. The main controller is in charge of the management and dynamic configuration of I/O parameters and so on.
  3. The power module and interface module are standard for remote/Os and users can choose the model or brand they prefer.

Gateway Parameter Settings

This section details how to connect a gateway to AS300. For detailed information, please refer to the -Series Product Manual.

Designer Program Setup

  1. Make sure that the module is powered and connected to the gateway module using an Ethernet cable.
  2. Click to launch the software.
  3. Select M Series Module Configuration.
  4. Click on the Setting Module icon.
  5. Enter the Setting Module page for M-series.
  6. Select the mode type based on the connected module.
  7. Click on Connect.
  8. Gateway Module IP Settings (Note: The IP address must be in the same domain as the controller equipment).
  9. Gateway Module Operational Modes (Note: Set Group 1 as Slave and set the gateway to use the first set of RS485 port to connect to the main controller (GFMS-RM01N)).

AS300 Connection Setup

This chapter explains how to use the ISPSoft program to connect AS300 with. For detailed information, please refer to the ISPSoft User Manual.

AS300 Hardware Connection

  1. The Ethernet port is on the top of AS300 and can be connected to the gateway.
  2. The gateway’s first 485 port is connected to the interface module 0170-0101 before being connected to the control module via an Ethernet cable.

AS300 Connection Setup

  1. Launch ISPSoft, create a new file and double-click HWCONFIG on the project management section on the left to enter the configuration page.

Note: The product information and usage instructions above are extracted from the user manual for the 2302EN V2.0.0 and AS300 Series Modbus TCP Connection Operating Manual. Please refer to the complete user manual for more detailed information and instructions.

Remote I/O Module System Configuration List

Part No. Specification Description
GFGW-RM01N Modbus TCP-to-Modbus RTU/ASCII, 4 Ports Gateway
GFMS-RM01S Master Modbus RTU, 1 Port Main Controller
GFDI-RM01N Digital Input 16 Channel Digital Input
GFDO-RM01N Digital Output 16 Channel / 0.5A Digital Output
GFPS-0202 Power 24V / 48W Power Supply
GFPS-0303 Power 5V / 20W Power Supply
0170-0101 8 pin RJ45 female connector/RS-485 Interface Interface Module

Product Description

  1. The gateway is used externally to connect with AS300’s communication port (Modbus TCP)
  2. The main controller is in charge of the management and dynamic configuration of I/O parameters and so on.
  3. The power module and interface module are standard for remote I/Os and users can choose the model or brand they prefer.

Gateway Parameter Settings

This section details how to connect a gateway to AS300. For detailed information regarding this, please refer to the -Series Product Manual

Designer Program Setup

  1. Make sure that the module is powered and connected to the gateway module using an Ethernet cableDAUDIN-AS300-Series-Modbus-TCP-Connection-FIG-2
  2. Click to launch the software
  3. Select “M Series Module Configuration”DAUDIN-AS300-Series-Modbus-TCP-Connection-FIG-4
  4. Click on the “Setting Module” iconDAUDIN-AS300-Series-Modbus-TCP-Connection-FIG-5
  5. Enter the “Setting Module” page for the M-seriesDAUDIN-AS300-Series-Modbus-TCP-Connection-FIG-6
  6. Select the mode type based on the connected moduleDAUDIN-AS300-Series-Modbus-TCP-Connection-FIG-7
  7. Click on “Connect”DAUDIN-AS300-Series-Modbus-TCP-Connection-FIG-8
  8. Gateway Module IP SettingsDAUDIN-AS300-Series-Modbus-TCP-Connection-FIG-9
  9. Gateway Module Operational ModesDAUDIN-AS300-Series-Modbus-TCP-Connection-FIG-10

Note: The IP address must be in the same domain as the controller equipment

Note: Set Group 1 as Slave and set the gateway to use the first set of RS485 port to connect to the main controller (GFMS-RM01N)

AS300 Connection Setup

This chapter explains how to use the ISPSoft program to connect AS300 with . For detailed information, please refer to the ISPSoft User Manual

AS300 Hardware Connection

  1. The Ethernet port is on the top of AS300 and can be connected to the gatewayDAUDIN-AS300-Series-Modbus-TCP-Connection-FIG-11
  2. The gateway’s first 485 port is connected to the interface module 0170-0101 before being connected to the control module via an Ethernet cableDAUDIN-AS300-Series-Modbus-TCP-Connection-FIG-12

AS300 Connection Setup

  1. Launch ISPSoft, create a new file and double-click “HWCONFIG” on the project management section on the left to enter the configuration pageDAUDIN-AS300-Series-Modbus-TCP-Connection-FIG-13
  2. Right-click on the PLC icon and select “Summary” under “Hardware Configuration”DAUDIN-AS300-Series-Modbus-TCP-Connection-FIG-14
  3. For this demonstration, click on “Ethernet – Basic Settings”DAUDIN-AS300-Series-Modbus-TCP-Connection-FIG-15
  4. Click on “Data Exchange” on the left to switch to the Data Exchange page and select the desired COM PORT (Ethernet in this case). Make sure to select “啟動方式” , otherwise the data communication will not be initiated. Select “Add” or modify existing fields to set up the communicationDAUDIN-AS300-Series-Modbus-TCP-Connection-FIG-16
  5. Data Exchange Settings” image and details:DAUDIN-AS300-Series-Modbus-TCP-Connection-FIG-17
  • To use that communication, make sure to check “Initiate”
  • When there are too many addresses to read and write, increase the “Minimum Refresh Cycle”.
  • control module can accept 0x17 function code while reducing the communication time by one writing and one reading
  • The IP address should be the IP address of the gateway you want to connect
  • For “Remote Device Type”, select “Standard Modbus Device”
  • s first GFDI-RM01N has the register address at 1000(HEX)
  • ’s first GFDO-RM01N has the register address at 2000(HEX)
  1. Once the setup is complete, click on “Download” for the setting to be incorporated in PLCDAUDIN-AS300-Series-Modbus-TCP-Connection-FIG-18
  2. Once the register for data storage is set up following the instructions above in the ISPSoft program, it is ready to useDAUDIN-AS300-Series-Modbus-TCP-Connection-FIG-19