DAUDIN GFMS-RM01S FATEK HMI Modbus RTU Connection User Manual

October 30, 2023
DAUDIN

DAUDIN logo and FATEK HMI
Modbus RTU Connection
Operating ManualDAUDIN GFMS RM01S FATEK HMI Modbus RTU
Connection

Remote I/O Module Configuration List

Part No. Specification Description
GFMS-RM01S Master Modbus RTU, 1 Port Main Controller
GFDI-RM01N Digital Input 16 Channel Digital Input
GFDO-RM01N Digital Output 16 Channel / 0.5A Digital Output
GFPS-0202 Power 24V / 48W Power Supply
GFPS-0303 Power 5V / 20W Power Supply
0170-0101 8 pin RJ45 female connector/RS-485 Interface Interface Module

1.1 Product Description
I. The interface module is used externally to convert FATEK HMI RS485’s communication port (Modbus RTU) to a RJ45 connector
II. The main controller is in charge of the management and dynamic configuration of I/O parameters and so on.
III. The power module and interface module are standard for remote I/Os and users can choose the model or brand they prefer.

FATEK HMI Connection Setup

This chapter explains how to use the FvDesigner program to connect FATEK HMI with .For detailed information, please refer to FATEK FvDesigner User Manual
2.1 FATEK HMI Hardware Connection
I. The connection port is at the bottom of the machine. Take P5070N for example. It uses COM3 (RS485 pin)

DAUDIN GFMS RM01S FATEK HMI Modbus RTU Connection -
bottom

PIN#| COM3 (RS-422)| COM3 (RS-485)| COM4
1| | | DATA+
2| | | DATA-
3| ISO_GND| ISO_GND| ISO_GND
4| RX+| |
5| RX-| |
6| TX+| DATA+|
7| TX-| DATA-|

II. Connect the COM (RS485 6/7) at the bottom of the machine to the interface module (1/2) to convert it into a RJ45 connector, which will be connected to the main controller.DAUDIN GFMS RM01S FATEK HMI Modbus RTU
Connection - controller 2.2 FATEK HMI Connection Setup
I. Launch FvDesigner, open a new file, select the controller page and then click on “Add” DAUDIN GFMS RM01S FATEK HMI Modbus RTU Connection -
controller pageII. Or you can click to open an existing file, select “Project Management” page and then click on “Connect” DAUDIN GFMS RM01S FATEK HMI Modbus RTU Connection -
Project ManagementIII. Connection method setupDAUDIN GFMS RM01S FATEK HMI Modbus RTU Connection -
Connection methodⒶ From the “Communication Interface Type” drop-down menu, select ”Connect Directly (Serial Port)”
Ⓑ From the “Manufacturer” drop-down menu, select ”MODBUS IDA”
Ⓒ From the “Product Series” drop-down menu, select ”MODBUS RTU”
Ⓓ From the “Connection Port” drop-down menu, select ”COM3”
Ⓔ From the “Transmission Rate” drop-down menu, select “115200”
Ⓕ From the “Calibrate” drop-down menu, select “No”
Ⓖ From the “Data Bits” drop-down menu, select “8”
Ⓗ From the “Stop Bits” drop-down menu, select “1”
Ⓘ Set up based on the device
Notes:
※The demonstration in the Connection Operating Manual uses COM3.
For using 485 pin with COM3, please refer to 2.1FATEK HMI Hardware Connection.
※Regarding ’s parameter settings, please refer to Control Module Operating Manual.
IV. Set up the location for the tag register DAUDIN GFMS RM01S FATEK
HMI Modbus RTU Connection - registerⒶ From the “Device” drop-down menu, select the device to be connected
Ⓑ From the “Type” drop-down menu, select “4x”
Ⓒ Set up according to the plan
Example:

register address HMI’s corresponding address*
R 0x1000
R 0x1001
R 0x1000.0
W 0x2000
W 0x2001
W 0x2000.0

Note:
※HMI’s corresponding address: ’s first GFDI-RM01N has the register address at 1000(HEX) converted to 4096(DEC)+1
’s first GFDO-RM01N has the register address at 2000(HEX) converted to 8192(DEC)+1
※Regarding ’s register address and format, please refer to Control Module Operating ManualDAUDIN logo