DAUDIN iO-GRIDm Relay Output Module User Manual
Relay Output Module List
Product No. | Description | Remarks |
---|---|---|
GFAR-RM11 | 8-Channel relay module, grounded | |
GFAR-RM21 | 4-Channel relay module, grounded |
Product Description
The GFAR relay module series is designed specifically for industrial
applications. It has a 4-channel and 8-channel model, both can control AC/DC
load through communication
Caution (ATTENTION):
- THIS DEVICE IS FOR INDOOR USE ONLY, DON’T PUT OR USE IT IN HIGH TEMPERATURE AND HIGH MOISTURE ENVIRONMENT.
- AVOID FALLING AND BUMPING OTHERWISE THE ELECTRICAL COMPONENTS WILL BE DAMAGED.
- DON’T TRY TO DISASSEMBLE OR OPEN THE COVER UNDER ANY CIRCUMSTANCE IN ORDER TO AVOID DANGER.
- IF THE EQUIPMENT IS USED IN A MANNER NOT SPECIFIED BY THE MANUFACTURER, THE PROTECTION PROVIDED BY THE EQUIPMENT MAY BE IMPAIRED.
- THE INSTALLATION THAT THE SAFETY OF ANY SYSTEM INCORPORATING THE EQUIPMENT IS THE RESPONSIBILITY OF THE ASSEMBLER OF THE SYSTEM.
- USE WITH COPPER CONDUCTORS ONLY. INPUT WIRING: MINIMUM 28 AWG, 85°C, OUTPUT WIRING: MINIMUM 28 AWG, 85°C
- FOR USE IN A CONTROLLED ENVIRONMENT. REFER TO MANUAL FOR ENVIRONMENTAL CONDITIONS.
- DISCONNECT ALL SOURCES OF SUPPLY BEFORE SERVICING.
- PROPER VENTILATION IS REQUIRED TO REDUCE THE RISK OF HAZARDOUS OR EXPLOSIVE GAS BUILDUP DURING INDOOR CHARGING. SEE OWNERS MANUAL.
Relay Output Module Specification
GFAR-RM11
Technical Specification
Number Of Outputs| 8
Voltage Supply| 24 VDC / 5 VDC
Current Consumption| <200 mA at 24 VDC”
Max Output Voltage| 250 VAC / 30 VDC
Max Output Current| 10 A
Actuation Time| 10 ms maximum
Reoperate Time| 5 ms maximum
Communication Specification
Fieldbus Protocol| Modbus RTU
Format| N, 8, 1
Baud Rate Range| 1200-1.5 Mbps
General Specification
Dimension (WDH)| 134 x 121 x 60.5mm
Weight| 358g
Ambient temperature (operation)| -10…+60 ˚C
Storage Temp.| -25 ˚C…+85 ˚C
Permissible Humidity(non-condensing)| RH 95%, non-condensing
Altitude Limit| < 2000 m
Ingress Protection (IP)| IP 20
Pollution Severity| II
Safety Approval| CE
Wiring Range (IEC / UL)| 0.2 mm2~2.5 mm2 / AWG 24~12
Wiring Ferrules| DN00508D、DN00708D、DN01008D、DN01510D
GFAR-RM21
Technical Specification
Number of Outputs| 4
Voltage Supply| 24 VDC
Current Consumption| <109 mA at 24 VDC”
Max Output Voltage| 250 VAC / 30 VDC
Max Output Current| 10A
Actuation Time| 10 ms maximum
Reoperate Time| 5 ms maximum
Communication Specification
Fieldbus Protocol| Modbus RTU
Format| N, 8, 1
Baud Rate Range| 1200-1.5 Mbps
General Specification
Dimension (WDH)| 68 x 121.8 x 60.5mm
Weight| 195g
Ambient temperature (operation)| -10…+60 ˚C
Storage Temp.| -25 ˚C…+85 ˚C
Permissible Humidity(non-condensing)| RH 95%, non-condensing
Altitude Limit| < 2000 m
Ingress Protection (IP)| IP 20
Pollution Severity| II
Safety Approval| CE
Wiring Range (IEC / UL)| 0.2 mm2~2.5 mm2 / AWG 24~12
Wiring Ferrules| DN00508D、DN00708D、DN01008D、DN01510D
Relay Output Module Information
Relay Output Module Dimension
-
GFAR-RM11
-
GFAR-RM21
Relay Output Module Panel Information
- GFAR-RM11
Terminal block labeling | 1 | 2 | 3 | 4 | 5 | 7 |
---|---|---|---|---|---|---|
Port definitions | 24V | 0V | 5V | 0V | RS485A | RS485B |
Terminal block B port definitions:
Terminal block labeling| 0 A| 0B| 1 A| 1B| 2 A|
2B
---|---|---|---|---|---|---
Port definitions| NO 1| NC 1| NO 2| NC 2| NO 3| NC 3
Terminal block labeling| 3A| 3B| COM1| COM1| |
Port definitions| NO 4| NC 4| Commonport| Commonport| |
Terminal block C port definitions:
Terminal block labeling | COM2 | COM2 | 4A | 4B | 5A | 5B |
---|---|---|---|---|---|---|
Port definitions | Commonport | Commonport | NO 5 | NC 5 | NO 6 | NC 6 |
Terminal block labeling | 6A | 6B | 7A | 7B | ||
Port definitions | NO 7 | NC 7 | NO 8 | NC 8 |
- GFAR-RM21
Terminal block A port definitions:
Terminal block labeling | 1 | 2 | 3 | 4 | 5 | 7 |
---|---|---|---|---|---|---|
Port definitions | 24V | 0V | 5V | 0V | RS485A | RS485B |
Terminal block B port definitions:
Terminal block labeling| 0A| 0B| 1A| 1B| 2A|
2B
---|---|---|---|---|---|---
Port definitions| NO 1| NC 1| NO 2| NC 2| NO 3| NC 3
Terminal block labeling| 3A| 3B| COM| COM| |
Connector definitions| NO 4| NC 4| Common
port| Common
port| |
Module Installation/Disassembly
Installation
- With the front of the relay output module facing you, press the module down with the signal input ports against the upper side of the DIN rail.
- Press the module down and the plastic clamp will slide. Continue to push down until the plastic clamp “clicks”.
Removal
- Use a screwdriver to pull the plastic clamp sideways and detach the module from the DIN rail.
- Remove the relay output module from the DIN rail in reverse order of installation.
iO-GRID M Series Introduction
iO-GRID M series utilizes the standard Modbus communication protocol and supports Modbus RTU/ASCII and Modbus TCP. Please choose products and factory controllers to figure your system based on your communication protocol.
iO-GRID M Components
DINKLE Bus
Rail 1 to 4 are defined for power supply and rail 5 to 7 are defined for
communication.
DINKLE Bus Rail Definitions:
Rail | Definition | Rail | Definition |
---|---|---|---|
8 | — | 4 | 0V |
7 | RS485B | 3 | 5V |
6 | — | 2 | 0V |
5 | RS485A | 1 | 24V |
Gateway Module
A gateway module converts between Modbus TCP and Modbus RTU/ASCII. The module
provides two sets of external Ethernet ports to connect to the controller and
the Internet
There are two types of gateway modules available:
4-channel gateway module: Provides 4 RS485 ports to connect to a control
module Single-channel gateway module: No external connectivity for the RS485
ports.The RS485 signals are transmitted via DINKLE Bus and I/O module.
Gateway module products information:
Product No. | Description |
---|---|
GFGW-RM01N | Modbus TCP-to-Modbus RTU/ASCII gateway module. 4 Ports |
GFGW-RM02N | Modbus TCP-to-Modbus RTU/ASCII gateway module. 1 Port |
Control module
The control module manages I/O modules and sets up the configuration. Provides
external RS485 ports to connect to the controller.
There are two types of control modules available:
3-channel control module:
Provides 3 external RS485 ports, suitable stations with 2 or more control
modules. Among the RS485 ports, 2 of them will be connected to the controller
and the control module of the next station.
Single-channel control module:
Provides one single RS485 port to connect to the controller, suitable for
single-module stations.
Control module products information:
Product No. | Description |
---|---|
GFMS-RM01N | RS485 control module, Modbus RTU/ASCII 3 Ports |
GFMS-RM01S | RS485 control module, Modbus RTU/ASCII 1 Port |
I/O Module
Dinkle offers different types of I/O modules with different functions:
Product No. | Description |
---|---|
GFDI-RM01N | 16-channel digital input module (source/sink) |
GFDO-RM01N | 16-channel digital output module (sink) |
GFDO-RM02N | 16-channel digital output module (Source) |
GFAR-RM11 | 8-Channel relay module, grounded |
GFAR-RM21 | 4-Channel relay module, grounded |
GFAI-RM10 | 4-channel analog input module (±10VDC) |
GFAI-RM11 | 4-channel analog input module (0…10VDC) |
GFAI-RM20 | 4-channel analog input module (0… 20mA) |
GFAI-RM21 | 4-channel analog input module (4… 20mA) |
GFAO-RM10 | 4-channel analog output module (±10VDC) |
GFAO-RM11 | 4-channel analog output module (0…10VDC) |
GFAO-RM20 | 4-channel analog output module (0… 20mA) |
GFAO-RM21 | 4-channel analog output module (4… 20mA) |
I/O Module Parameter Settings and Introduction
I/O Module Settings and Connections
I/O Module System Configuration List
Name/Product No. | Description |
---|---|
GFDO-RM01N | 16-channel digital output module (sink) |
GFDO-RM02N | 16-channel digital output module (Source) |
GFTK-RM01 | USB-to-RS232 converter |
Micro USB cable | Must have data transfer functionality |
Computer | BSB-compatible |
Module Initial Setting List
Product No.| Description| Station No.| Baud rate|
Format
---|---|---|---|---
GFMS-RM01N| RS485 control module, RTU/ASCII| 1| 115200| RTU(8,N,1)
GFDI-RM01N| 16-channel digital input module (source/sink)| 1| 115200|
RTU(8,N,1)
GFDO-RM01N| 16-channel digital output module (sink)| 1| 115200| RTU(8,N,1)
GFDO-RM02N| 16-channel digital output module (Source)| 1| 115200| RTU(8,N,1)
GFAR-RM11| 8-Channel relay module, grounded| 1| 115200| RTU(8,N,1)
GFAR-RM21| 4-Channel relay module, grounded| 1| 115200| RTU(8,N,1)
GFAI-RM10| 4-channel analog input module (±10VDC)| 1| 115200| RTU(8,N,1)
GFAI-RM11| 4-channel analog input module (0…10VDC)| 1| 115200| RTU(8,N,1)
GFAI-RM20| 4-channel analog input module (0… 20mA)| 1| 115200| RTU(8,N,1)
GFAI-RM21| 4-channel analog input module (4… 20mA)| 1| 115200| RTU(8,N,1)
GFAO-RM10| 4-channel analog output module (±10VDC)| 1| 115200| RTU(8,N,1)
GFAO-RM11| 4-channel analog output module (0…10VDC)| 1| 115200| RTU(8,N,1)
GFAO-RM20| 4-channel analog output module (0… 20mA)| 1| 115200| RTU(8,N,1)
GFAO-RM21| 4-channel analog output module (4… 20mA)| 1| 115200| RTU(8,N,1)
Setup Software Functions:
The setup software shows the I/O module station numbers, baud rates and data
formats.
I/O Module Settings and Connections
Connect the Micro USB port and GFTL-RM01 (RS232 converter) to your computer
and open the iO-Grid M Utility program to set up I/O module parameter
I/O module connection illustration:
I/O module connection image:
i-Designer Program Tutorial
-
Connect to the I/O module using GFTL-RM01 and a Micro USB cable
-
Click to launch the software
-
Select “M Series Module Configuration”
-
Click on the “Setting Module” icon
-
Enter the “Setting Module” page for M-series
-
Select the mode type based on the connected module
-
Click on “Connect”
-
Set up I/O modules’ station numbers and communication format (must click on “Save” after changing them)
Relay Output Module Control Register Description
Relay Output Module Register Communication Method
Use Modbus RTU/ASCII to write in single-chip relay output module registers The
address for the relay output module register to be written is: 0x2000
※With no control module, RS485’s physical wire must be connected with an adapter to send the signal to the power and relay output module
| 1| 2| 3| 4| 5| 6| 7| 8
---|---|---|---|---|---|---|---|---
Adapter BS-211| 24V| 0V| 5V| 0V| 485A| ─| 485B| ─
Terminal block 0181-A106| 24V| 0V| 5VDC| 0V| 485A| | 485B|
Use Modbus RTU/ASCII with control modules to write in relay output
registers
Once a relay output module is set up with a control module, it will
automatically assign the relay output
modules’ output records registers at the address of 0x2000
Example:
Two relay output module registers will be between 0x2000 and 0x2001
※When using control modules, RS485 can connect to control modules with BS-210 and BS-211
The configuration that uses Modbus RTU/ASCII with a control module to write in relay output modules is listed below:
Name/Product No. | Description |
---|---|
GFMS-RM01S | Master Modbus RTU, 1 Port |
GFAR-RM11 | 8-Channel relay module, grounded |
GFAR-RM21 | 4-Channel relay module, grounded |
0170-0101 | RS485(2W)-to-RS485(RJ45 interface) |
Relay Output Module Register Format Information (0x2000, rewritable)
GFAR-RM11 Register Format: Channel open-1; channel closed – 0; reserved value
– 0.
Bit15| Bit14| Bit13| Bit12| Bit11| Bit10| Bit9| Bit8| Bit7| Bit6| Bit5| Bit4|
Bit3| Bit2| Bit1| Bit0
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Reserved| 8A| 7A| 6A| 5A| 4A| 3A| 2A| 1A
Example: With channel 1 to 8 open:0000 0000 1111 1111 (0x00 0xFF); with
all
channels closed: 0000 0000 0000 0000 (0x00 0x00).
GFAR-RM11 Register Format: Channel open-1; channel closed – 0; reserved
value – 0.
Bit15| Bit14| Bit13| Bit12| Bit11| Bit10| Bit9| Bit8| Bit7| Bit6| Bit5| Bit4|
Bit3| Bit2| Bit1| Bit0
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Reserved| 4A| 3A| 2A| 1A
Example: With channel 1 to 4 open:0000 0000 0000 1111 (0x00 0x0F); with
all
channels closed: 0000 0000 0000 0000 (0x00 0x00).
GFAR-RM20 Register Format: Channel open-1; channel closed – 0; reserved
value – 0.
Modbus function code 0x10 Demonstration
Use Modbus RTU/ASCII to write in single-chip relay output module registers
** Modbus function code| Code sent example(ID:0x01)| Code replied
example(ID:0x01)
---|---|---
0x10**| 01 10 20 00 00 01 02 00 FF| 01 01 10 20 00 00
※In this example, we are writing in “0x2000” with the I/O module ID of “01” ※When not using control modules for communications, the registers will be at 0x2000
Use Modbus RTU/ASCII with control modules to write in relay output register
** Modbus function code| Code sent sample(ID:0x01)| Code replied
sample(ID:0x01)
---|---|---
0x10**| 01 10 20 00 00 01 02 00 FF| 01 01 10 20 00 00
※In this example, we are writing in “0x2000” with the control module ID of
“01”
※When using control modules for communications, the registers will start at
0x2000
Read User Manual Online (PDF format)