DAUDIN GFDO-RM01N MELSEC-Q Modbus TCP Connection User Manual

October 30, 2023
DAUDIN

DAUDIN GFDO-RM01N MELSEC-Q Modbus TCP Connection

Product Information

Product Name: 2210TW V2.0.0 and MELSEC-Q Modbus TCP Connection

The product is a remote I/O module system that allows users to connect the MELSEC-Q series communication port (Modbus TCP) externally. It includes a gateway, main controller, digital input, digital output, and power supply modules. The main controller manages and dynamically configures I/O parameters. The power module is standard for remote I/Os and users can choose the model or brand of power module they prefer.

Remote I/O Module System Configuration List

The list includes the following:

Part No. Specification Description
GFGW-RM01N Modbus TCP-to-Modbus RTU/ASCII, 4 Ports Gateway
GFMS-RM01S Master Modbus RTU, 1 Port Main Controller
GFDI-RM01N Digital Input 16 Channel Digital Input
GFDO-RM01N Digital Output 16 Channel / 0.5A Digital Output
GFPS-0202 Power 24V / 48W Power Supply
GFPS-0303 Power 5V / 20W Power Supply

Product Gateway Parameter Settings

This section explains how to connect the gateway to the MELSEC-Q series. For detailed information, refer to the MELSEC-Q Series Product Manual. The i-Designer program is used for setup.

i-Designer Program Setup

  1. Ensure that the module is powered and connected to the gateway module using an Ethernet cable.
  2. Launch the i-Designer software.
  3. Select M Series Module Configuration.
  4. Click on the Setting Module icon.
  5. Enter the Setting Module page for M-series.
  6. Select the mode type based on the connected module.
  7. Click on Connect.
  8. Set the Gateway Module IP Address. Note: The IP address must be in the same domain as the MELSEC-Q controller.
  9. Set Gateway Module Operational Modes. Note: Set Group 1 as Slave and set the gateway to use the first set of RS485 port to connect to the main controller (GFMS-RM01N).

MELSEC-Q series Connection Setup

This chapter explains how to use the GX Works2 program to connect the MELSEC-Q series to a gateway module and add a remote I/O module. For detailed information, refer to the MELSEC-Q Series Manual.

MELSEC-Q series Hardware Connections

  • The QJ71MT91 module’s Ethernet port is at its bottom center and can be connected to the gateway.

MELSEC-Q series IP Address and Connection Setup

  1. Launch GX Works 2 and right-click on the Intelligent Function Module menu under Project on the left side.
  2. Click on New Module to create a QJ71MB91 module.

Simple Program Demonstration using MELSEC-Q series and

  • No information provided in the user manual for this section.

Product Usage Instructions

  1. Connect the gateway to the MELSEC-Q series communication port (Modbus TCP) externally using an Ethernet cable.
  2. Use the i-Designer program to set up the gateway parameters by following the steps mentioned in section 2.1 of the user manual.
  3. Use the GX Works2 program to connect the MELSEC-Q series to the gateway module and add a remote I/O module by following the steps mentioned in section 3 of the user manual.

Remote I/O Module System Configuration List

Part No. Specification Description
GFGW-RM01N ****

Modbus TCP-to-Modbus RTU/ASCII, 4 Ports

| Gateway
GFMS-RM01S| Master Modbus RTU, 1 Port| Main Controller
GFDI-RM01N| Digital Input 16 Channel| Digital Input
GFDO-RM01N| Digital Output 16 Channel / 0.5A| Digital Output
GFPS-0202| Power 24V / 48W| Power Supply
GFPS-0303| Power 5V / 20W| Power Supply

Product Description

  1. The gateway is used externally to connect with MELSEC-Q series’ communication port (Modbus TCP)
  2. The main controller is in charge of the management and dynamic configuration of I/O parameters and so on.
  3. The power module is standard for remote I/Os and users can choose the model or brand of power module they prefer.

Gateway Parameter Settings

This section details how to connect a gateway to MELSEC-Q series. For detailed information regarding , please refer to the -Series Product Manual

i-Designer Program Setup

  1. Make sure that the module is powered and connected to the gateway module using an Ethernet cable
  2. Click to launch the software
  3. Select “M Series Module Configuration”
  4. Click on the “Setting Module” icon
  5. Enter the “Setting Module” page for M-series
  6. Select the mode type based on the connected module
  7. Click on “Connect”
  8. Gateway Module IP Settings
    • Note: The IP address must be in the same domain as the MELSEC-Q controller
  9. Gateway Module Operational Modes

Note: Set Group 1 as Slave and set the gateway to use the first set of RS485 port to connect to the main controller (GFMS-RM01N)

MELSEC-Q series Connection Setup

This chapter explains how to use the GX Works2 program to use the QJ71MT91 module to connect MELSEC-Q series to a gateway module and add a remote I/O module. For detailed information, please refer to the “MELSEC-Q Series Manual

MELSEC-Q series Hardware Connections

  1. The QJ71MT91 module’s Ethernet port is at its bottom center and can be connected to the gateway

MELSEC-Q series IP Address and Connection Setup

  1. Launch GX Works 2 and right click on the “Intelligent Function Module” menu under “Project” on the left side. Then click on “New Module” to create a “QJ71MB91” module
  2. Launch GX Works 2 and select the “Intelligent Function Module” menu under “Project” on the left side. Then click on “Switch Setting” in the “QJ71MT91” menu
  3. Set “IP Address” to the same domain as the gateway domain at 192.168.1.XXX.
  4. Click on “Automatic_Communication_Parameter” to set up reading and writing methods
  • Target Station IP Address is set by default at ”192.168.1.20”
  • The station number to be connected
  • From the drop-down menu, select “0505h:Read/Write Holding Registers”
  • Set to 1000h
  • The Target MODBUS Device Head Number is set to 4096
  • Read Points
  • Set to 3000h
  • H The Target MODBUS Device Head Number is set to 8192
  • Write Points

Notes

  • first GFDI-RM01N has the register address at 1000(HEX) converted to 4096
  • first GFDO-RM01N has the register address at 2000(HEX) converted to 8192
  1. Click on “Auto_Refresh” to set up the internal register for reading and writing

Simple Program

Simple Program Demonstration using MELSEC-Q series and

  • The read register address is 4096, which is D0 for the corresponding internal register of the controller.
  • And the write register address is 8192, which is D300 for the corresponding internal register of the controller.
  • Therefore, when you want to control the program, you can just use the internal register to control the writing and reading.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

DAUDIN User Manuals

Related Manuals