BEGA 50 684.6 Recessed Ceiling Downlight for Indoor Use Instruction Manual
- June 12, 2024
- BEGA
Table of Contents
Recessed ceiling downlight for indoor use
50 684.6
50 684.6 Recessed Ceiling Downlight for Indoor Use
Instructions for use
Application
Recessed ceiling luminaire · indoor luminaire with symmetrical wide beam light
distribution for connection to external LED power supply unit.
For flush-mounting installation in indoor suspended ceilings of 5-25 mm
thickness.
Product description
Recessed ceiling luminaire downlight »STUDIO LINE« without power supply unit
Luminaire housing made of cast aluminium The recessed housing is made of glass
fibre reinforced synthetic material Centre-plate made of rigid polystyrene
foam Trim ring, Colour velvet black Reflector made of pure anodised aluminium
Inside hue matt copper Recessed opening ø 125 mm Required installation depth
95 mm 1 connecting cable with strain relief and plug onnector system for BEGA
power supply unit, on/off or DALI
Safety class III
– Conformity mark
Weight: 0.55 kg
This product contains light sources of energy efficiency class(es) E
Safety
The installation and operation of this luminaire are subject to national
safety regulations.
Installation and commissioning may only be carried out by a qualified
electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation. If subsequent modifications are made to the luminaire, the
person responsible for these modifications shall be considered the
manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we
recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.
Lamp
Module connected wattage | 8.1 W |
---|---|
Luminaire connected wattage | 9.8 W |
Rated temperature | ta = 25 °C |
Ambient temperature | ta max = 55 °C |
When installed in heat-insulating material | ta max = 35 °C |
50 684.6 K3
Module designation | LED-0800/930 |
---|---|
Colour temperature | 3000 K |
Colour rendering index | CRI > 90 |
Module luminous flux | 1255 lm |
Luminaire luminous flux | 807 lm |
Luminaire luminous efficiency | 82,3 lm / W |
Notice prior to installation:
Additional filler is required for the flush
installation of the recessed housing in the
suspended ceiling.
Installation
A separate power supply unit is required to operate the luminaire.
For connection to external LED-power supply unit – accessory 13 143 or 13 168
– the luminaire is equipped with a 2-pin connector.
Note operating instructions of the LED-power supply units.
LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during
installation or relamping.
The recessed housing is fixed in the recessed opening by screwing it to the
ceiling from below.
Installation in suspended ceilings:
A recessed opening of 125 mm with a minimum depth of 95 mm is required.
The lateral clearance between the recessed housing and parts of the building
must be at least 50 mm.
Make the appropriate cutout in the suspended ceiling. The ceiling cutout must
have an all-round chamfer of 45°, depending on the thickness of the ceiling
panel.Remove the ceiling mounting plate
by turning it upwards and out of the thread of the adjusting sleeve, move it
through the ceiling cutout and place it on the suspended ceiling.
Secure the ceiling mounting plate with screws (Ø 3.5 to 4 mm) suitable for
gypsum plasterboard panels from below through the suspended ceiling.
When doing so, hold the ceiling mounting plate through the ceiling
cutout.Turn the adjusting sleeve into the
thread of the previously fitted ceiling mounting plate until it is exactly
flush with the ceiling.
IMPORTANT:
Make sure to use this centre-plate in order to guarantee the correct
installation of the luminaire in the ceiling!
Fill the 45° chamfer of the ceiling cutout with standard filler and smooth it
so that it is flush.
Allow the filler to set completely! Press the centre-plate about 5 mm upwards
into the adjusting sleeve and then pull it down carefully to remove it from
the adjusting sleeve.![BEGA 50 684.6 Recessed Ceiling Downlight for Indoor Use
- Fig 3](https://manuals.plus/wp-content/uploads/2023/07/BEGA-50-684.6
-Recessed-Ceiling-Downlight-for-Indoor-Use-Fig-3.png)Connect to the LED power
supply unit.
Route the LED power supply unit through the installation housing and place it in the suspended ceiling.
Connect the 2-pin plug connector between luminaire and external LED power supply unit.
Press together the two internal fixing sliders inside the luminaire housing.
Push the luminaire housing to the end of the installation housing and then release the fixing sliders.
This mechanism ensures that the luminaire housing sits securely inside the installation housing.
Place the reflector with silicone lens on the ceiling trim ring. Twist the ceiling trim ring complete with the attached reflector to the right to fix the assembly inside the luminaire housing.
Light technique
Symmetrical wide beam light distribution
Half beam angle 33°
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to
those of the modules originally fitted. The module can be replaced by
qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Close the luminaire.
Accessories
Power supply units for LED luminaires 220-240 V · 0/50-60 Hz with strain
relief and plug connector system.
13 143 Power supply unit on/off 13 168 Power supply unit DALI The power supply
units are only suitable for the operation of one LED luminaire.
For the accessories a separate instructions for use can be provided upon
request.
Spares
Centre-plate | 06 000 418 |
---|---|
Trim ring | 20 000 043 B1 |
LED module 3000 K | LED-0800/930 |
Reflector | 75 002 765 |
BEGA Gantenbrink-Leuchten KG
Postfach 31 60
58689 Menden
info@bega.com
www.bega.com
Documents / Resources
| BEGA
50 684.6 Recessed Ceiling Downlight for Indoor
Use
[pdf] Instruction Manual
50684.6, 50684.6K3, Recessed Ceiling Downlight for Indoor Use, 50 684.6
Recessed Ceiling Downlight for Indoor Use, 50 684.6 Recessed Ceiling
Downlight, Recessed Ceiling Downlight, Ceiling Downlight, Downlight
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>