BEGA 50577.4 Indoor Recessed Ceiling Luminaire Instruction Manual

June 12, 2024
BEGA

50 577.4

Recessed ceiling luminaire for indoor use

BEGA 50577 4 Indoor Recessed Ceiling Luminaire -

Instructions for use

Application
Recessed ceiling luminaire · indoor luminaire with symmetrical wide beam light distribution and a remote non-dimmable power supply unit. For installation in suspended ceilings of 5-30 mm in interior applications.

Lamp

Module connected wattage 17.6 W
Luminaire connected wattage 20 W
Rated temperature ta = 25 °C
Ambient temperature ta max = 30 °C

50 577.4 K3
Module designation| LED-0838/930
Colour temperature| 3000 K
Colour rendering index| CRI > 90
Module luminous flux| 2670 lm
Luminaire luminous flux| 1135 lm
Luminaire luminous efficiency| 56,8 lm / W

Product description

Recessed LED ceiling luminaire with a remote power supply unit
Luminaire housing made of cast aluminium Ceiling trim ring finish, Colour velvet black Inside hue matt brass Fixing is achieved by using 2 fastening springs Recessed opening ø 141 mm Required installation depth 90 mm Light- diffusing disc External LED power supply unit 220-240 V x 0/50-60 Hz Safety class II Icon
  – Safety mark
****– Conformity mark
Weight: 0.52 kg
This product contains light sources of energy efficiency classes D

Safety

The installation and operation of this luminaire are subject to national safety regulations.
Installation and commissioning may only be carried out by a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547. To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components. You can find them on our website at www.bega.com.

Installation

  Luminaire housing and external LED power supply unit must not be covered by any heat insulating materials.
LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.
Cover the recessed opening with the stop ring of the luminaire housing.
The luminaire housing is then fixed in the recessed opening via two springs.
Installation in suspended ceilings:
A recessed opening of 141 mm with a minimum depth of 90 mm is required.
The minimal thickness of the ceiling panel must be 5 mm and must not be greater than 25 mm.
A ceiling panel with less than 5 mm thickness must be reinforced on the reverse.
The electrical connection must be made on site in the appropriate safety class on the LED power supply unit connecting cable. A distribution box must be used.
Ensure the correct assignment of the connecting cable. Establish the mains connection on the brown (L) and blue (N) wires.
Guide the LED power supply unit through the opening in the ceiling and position it on the suspended ceiling.
Compress the fastening springs of the luminaire housing on both sides and slide the luminaire housing into the recessed opening.
The fastening springs lock into place behind the ceiling panel.

Cleaning · Maintenance

Clean luminaire regularly with solvent-free cleansers from dirt.

Replacing the LED module

The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Close the luminaire.

Spares

LED power supply unit DEV-0349/700
LED module 3000 K LED-0838/930

BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals