BEGA 50717.2 LED Recessed Ceiling Luminaire for Indoor Use Instruction Manual
- June 12, 2024
- BEGA
Table of Contents
BEGA 50717.2 LED Recessed Ceiling Luminaire for Indoor Use
Instructions for use
Application
- Recessed ceiling luminaire · indoor luminaire with hand-blown opal glass, satin matt and aluminium alloy housing.
- For installation into ceilings with a shallow depth in interior areas.
DIMENSION
Product Description
- Recessed ceiling luminaire »ACCENTA«
- Die-cast aluminium housing
- Hand-blown opal glass, satin matt, with screw neck
- Ceiling frame ring made of stainless steel
- Recessed opening ø 68 mm
- Required installation depth 60 mm
- Fixing is achieved by using 2 adjustable wedge-shaped claws
- External LED power supply unit
- 220-240 V x 0/50-60 Hz
- DC 176-280 V
- DALI controllable
- A basic isolation exists between power cable and control line
- Safety class II 2
- Safety mark
- Conformity mark
- Weight: 0.38 kg
- This product contains light sources of energy efficiency class(es) D
Safety
- The installation and operation of this luminaire are subject to national safety regulations.
- Installation and commissioning may only be carried out by a qualified electrician.
- The manufacturer accepts no liability for damage caused by improper use or installation.
- If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.
Overvoltage protection
- The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
- To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
- You can find them on our website at www.bega.com.
FEATURES
Lamp
- Module connected wattage 5.8 W
- Luminaire connected wattage 7.7 W
- Rated temperature ta = 25 °C
- Ambient temperature ta max = 40 °C
50 717.2 K27
- Module designation LED-0922/927
- Colour temperature 2700 K
- Colour rendering index CRI > 90
- Module luminous flux 920 lm
- Luminaire luminous flux 632 lm
- Luminaire luminous efficiency 82,1 lm / W
50 717.2 K3
- Module designation LED-0922/930
- Colour temperature 3000 K
- Colour rendering index CRI > 90
- Module luminous flux 940 lm
- Luminaire luminous flux 650 lm
- Luminaire luminous efficiency 84,4 lm / W
Installation
- LED are high-quality electronic components!
- Please avoid touching the light output opening of the LED directly during installation or relamping.
- The recessed opening will be covered by the frame of the luminaire.
- Fixing of the luminaire is achieved by using 2 adjustable wedge-shaped claws
Installation into false ceilings
- A recessed opening of ø 68 mm is necessary to accept the luminaire housing. Free space depth min. 60 mm (see sketch).
- The claws catch the panel from the reverse side. If minimum thickness of the panel is less than 3 mm it must be reinforced from the reverse side. Maximum thickness of the panel must be no more than 20 mm.
- The electrical connection must be made on site in the appropriate safety class on the LED power supply unit connecting cable. A distribution box must be used.
- Ensure the correct assignment of the connecting cable. Establish the mains connection on the brown (L) and blue (N) wires.
- The connection of the control cables is achieved by means of the both leads marked with – DALI.
- In case these leads are not used the luminaire will be operated at full light output.
- Push external LED-power supply unit and luminaire housing into ceiling cut-out.
- Luminaire housing and external LEDpower supply unit must not be installed in heat-insulating material.
- Hand-tight screws of claw fasteners evenly.
- Lead enclosed ceiling frame ring over the screw-neck of the glass and push it down the gasket.
- Make sure that gasket is positioned correctly.
- Insert glass with frame ring by turning it clockwise into luminaire housing
Cleaning Maintenance
- Clean luminaire regularly with solvent-free cleansers from dirt.
- Defective glass must be replaced.
Replacement of the LED module
- The designation of the LED module is noted on a label in the luminaire.
- The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
- Disconnect from main supply.
- Unscrew glass with ceiling frame ring from luminaire housing by turning it counterclockwise.
- Please follow the installation instructions for the LED module.
- Check gasket. Screw in glass with ceiling frame ring by turning it clockwise beyond the stop.
- Defective glass must be replaced
Spares
- Spare glass 11 003 011 40R G
- LED power supply unit DEV-0434/350
- LED module 2700 K LED-0922/927
- LED module 3000 K LED-0922/930
- Trim ring 72 009 562 L
- Gasket 83 001 412
BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden
info@bega.com
www.bega.com
References
Read User Manual Online (PDF format)
Loading......