BEGA 50717.2 LED Recessed Ceiling Luminaire for Indoor Use Instruction Manual

June 12, 2024
BEGA

BEGA 50717.2 LED Recessed Ceiling Luminaire for Indoor Use

BEGA-50717-2 LED-Recessed-Ceiling-Luminaire-for-Indoor-Use-
PRODUCT

Instructions for use

Application

  • Recessed ceiling luminaire · indoor luminaire with hand-blown opal glass, satin matt and aluminium alloy housing.
  • For installation into ceilings with a shallow depth in interior areas.

DIMENSION

BEGA-50717-2 LED-Recessed-Ceiling-Luminaire-for-Indoor-Use-FIG-
\(1\)

Product Description

  • Recessed ceiling luminaire »ACCENTA«
  • Die-cast aluminium housing
  • Hand-blown opal glass, satin matt, with screw neck
  • Ceiling frame ring made of stainless steel
  • Recessed opening ø 68 mm
  • Required installation depth 60 mm
  • Fixing is achieved by using 2 adjustable wedge-shaped claws
  • External LED power supply unit
  • 220-240 V x 0/50-60 Hz
  • DC 176-280 V
  • DALI controllable
  • A basic isolation exists between power cable and control line
  • Safety class II 2
  • Safety mark
  • Conformity mark
  • Weight: 0.38 kg
  • This product contains light sources of energy efficiency class(es) D

Safety

  • The installation and operation of this luminaire are subject to national safety regulations.
  • Installation and commissioning may only be carried out by a qualified electrician.
  • The manufacturer accepts no liability for damage caused by improper use or installation.
  • If subsequent modifications are made to the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection

  • The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
  • To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
  • You can find them on our website at www.bega.com.

FEATURES

Lamp

  • Module connected wattage 5.8 W
  • Luminaire connected wattage 7.7 W
  • Rated temperature ta = 25 °C
  • Ambient temperature ta max = 40 °C

50 717.2 K27

  • Module designation LED-0922/927
  • Colour temperature 2700 K
  • Colour rendering index CRI > 90
  • Module luminous flux 920 lm
  • Luminaire luminous flux 632 lm
  • Luminaire luminous efficiency 82,1 lm / W

50 717.2 K3

  • Module designation LED-0922/930
  • Colour temperature 3000 K
  • Colour rendering index CRI > 90
  • Module luminous flux 940 lm
  • Luminaire luminous flux 650 lm
  • Luminaire luminous efficiency 84,4 lm / W

Installation

  • LED are high-quality electronic components!
  • Please avoid touching the light output opening of the LED directly during installation or relamping.
  • The recessed opening will be covered by the frame of the luminaire.
  • Fixing of the luminaire is achieved by using 2 adjustable wedge-shaped claws

Installation into false ceilings

  • A recessed opening of ø 68 mm is necessary to accept the luminaire housing. Free space depth min. 60 mm (see sketch).
  • The claws catch the panel from the reverse side. If minimum thickness of the panel is less than 3 mm it must be reinforced from the reverse side. Maximum thickness of the panel must be no more than 20 mm.
  • The electrical connection must be made on site in the appropriate safety class on the LED power supply unit connecting cable. A distribution box must be used.
  • Ensure the correct assignment of the connecting cable. Establish the mains connection on the brown (L) and blue (N) wires.
  • The connection of the control cables is achieved by means of the both leads marked with – DALI.
  • In case these leads are not used the luminaire will be operated at full light output.
  • Push external LED-power supply unit and luminaire housing into ceiling cut-out.
  • Luminaire housing and external LEDpower supply unit must not be installed in heat-insulating material.
  • Hand-tight screws of claw fasteners evenly.
  • Lead enclosed ceiling frame ring over the screw-neck of the glass and push it down the gasket.
  • Make sure that gasket is positioned correctly.
  • Insert glass with frame ring by turning it clockwise into luminaire housing

Cleaning Maintenance

  • Clean luminaire regularly with solvent-free cleansers from dirt.
  • Defective glass must be replaced.

Replacement of the LED module

  • The designation of the LED module is noted on a label in the luminaire.
  • The light colour and light output of BEGA replacement modules correspond to those of the modules originally fitted. The module can be replaced by qualified persons using standard tools.
  • Disconnect from main supply.
  • Unscrew glass with ceiling frame ring from luminaire housing by turning it counterclockwise.
  • Please follow the installation instructions for the LED module.
  • Check gasket. Screw in glass with ceiling frame ring by turning it clockwise beyond the stop.
  • Defective glass must be replaced

Spares

  • Spare glass 11 003 011 40R G
  • LED power supply unit DEV-0434/350
  • LED module 2700 K LED-0922/927
  • LED module 3000 K LED-0922/930
  • Trim ring 72 009 562 L
  • Gasket 83 001 412

BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden
[email protected]
www.bega.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

BEGA User Manuals

Related Manuals