Steinel IS 140-2 Z-Wave Motion Sensor STEEIS1402SW Manual
- June 8, 2024
- STEINEL
Table of Contents
- Steinel
- IS 140-2 Z-Wave Motion Sensor
- SKU: STEEIS1402SW
- Quickstart
- Important safety information
- What is Z-Wave?
- Product Description
- Prepare for Installation / Reset
- Installation
- Inclusion/Exclusion
- Product Usage
- Quick trouble shooting
- Association – one device controls an other device
- Configuration Parameters
- Parameter 1: TIME
- Parameter 2: LIGHT
- Parameter 5: SENSITIVITY
- Parameter 8: GLOBAL_LIGHT
- Parameter 9: SLAVE_MODE
- Parameter 10: OFF_BEHAVIOUR
- Parameter 11: ON_BEHAVIOUR
- Parameter 12: ON_TIME_OVER
- Parameter 13: ON_OFF_BEHAVIOR
- Parameter 14: OFF_ON_BEHAVIOUR
- Parameter 15: SEQUENCY_TIME
- Parameter 16: MOTION_DISABLE
- Technical Data
- Supported Command Classes
- Controlled Command Classes
- Explanation of Z-Wave specific terms
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Steinel
IS 140-2 Z-Wave Motion Sensor
SKU: STEEIS1402SW
Quickstart
This is a ****
Alarm Sensor
for
Europe.
To run this device please connect it to your mains power supply.
To put the device into inclusion mode, turn the device‘s control dial (E) to “Set” and back to “0” within 5 seconds.
Important safety information
Please read this manual carefully. Failure to follow the recommendations in
this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any
loss or damage resulting from failure to comply with the instructions in this
manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal
instructions.
Do not dispose of electronic equipment or batteries in a fire or near open heat sources.
What is Z-Wave?
Z-Wave is the international wireless protocol for communication in the Smart
Home. This
device is suited for use in the region mentioned in the Quickstart section.
Z-Wave ensures a reliable communication by reconfirming every message ( two-
way
communication) and every mains powered node can act as a repeater for other
nodes
( meshed network ) in case the receiver is not in direct wireless range of
the
transmitter.
This device and every other certified Z-Wave device can be used together
with any other
certified Z-Wave device regardless of brand and origin as long as both are
suited for the
same frequency range.
If a device supports secure communication it will communicate with other
devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to
maintain
backward compatibility.
For more information about Z-Wave technology, devices, white papers etc.
please refer
to www.z-wave.info.
Product Description
Are you toying with the idea of fitting a motion detector to your building? The infrared controlled IS 140-2 motion detector gives you all the benefits of a modern detector. Needless to say, we always use the very latest technology for our bestsellers too. For instance, we have given the product in its current generation even more class: larger adjustment angle, even longer reach and even better detection performance. Treat your home to intelligent sensor technology.
Prepare for Installation / Reset
Please read the user manual before installing the product.
In order to include (add) a Z-Wave device to a network it must be in factory
default
state. Please make sure to reset the device into factory default. You can do
this by
performing an Exclusion operation as described below in the manual. Every
Z-Wave
controller is able to perform this operation however it is recommended to use
the primary
controller of the previous network to make sure the very device is excluded
properly
from this network.
Reset to factory default
This device also allows to be reset without any involvement of a Z-Wave
controller. This
procedure should only be used when the primary controller is inoperable.
- Turn the device‘s control dial (E) to “Set” and move it to “Reset” within 5 seconds.
- The status LED (F) briefly flashes to show that the light has been reset.
- The device is now no longer included in the Z-Wave system and has been returned to factory settings.
Safety Warning for Mains Powered Devices
ATTENTION: only authorized technicians under consideration of the country-
specific
installation guidelines/norms may do works with mains power. Prior to the
assembly of
the product, the voltage network has to be switched off and ensured against
re-switching.
Installation
Electrical installation
• Switch OFF power supply” (Fig. 3.5)
Connecting the mains supply lead” The mains leads consists of at least a” 3-core cable:
L = Phase conductor” (usually black or brown)
N = Neutral conductor” (usually blue)
PE = Protective-earth conductor” (usually green/yellow)
If you are in any doubt, identify the” conductors using a voltage tester;” then disconnect from the power” supply again. Loop through any” protective- earth conductor.
Important: incorrectly wired connections” will produce a short circuit” later on in the product or your fuse” box. In this case, you must identify” the individual leads and reconnect” them. An appropriate power switch” for switching ON and OFF can be installed” in the supply lead. The electric” circuit must be protected by a 10 A” circuit breaker.” Connection diagram (Fig. 3.5)
Mounting
• Check all components for” damage.
• Do not use the product if it is” damaged.
• Select an appropriate mounting” location, taking the reach and” motion detection into consideration” (Fig. 4.1). The most reliable” way of detecting movement is to” install the sensor aimed across” the direction in which a person” would walk and by ensuring that
no obstacles (such as trees, walls” etc.) obstruct the line of sensor” vision.
(Fig. 4.2 / 4.3)” Mounting procedure”
• Switch OFF power supply.
• Detach enclosure from wall” mount . (Fig. 4.5)
• Mark drill holes. (Fig. 4.6)
• Drill holes and fit wall plugs.” (Fig. 4.7)
• Fit sealing plug. (Fig. 4.8)”
– Concealed power supply lead” (Fig. 4.9)
– Concealed power supply lead” with spacers (Fig. 4.10)
• Drill condensation water drainage” hole with a 5 mm drill bit.” (Fig. 4.11)
• Connect conductors.” (Fig. 4.12 / 4.13)
• Fit enclosure onto wall mount.” (Fig. 4.14)
• Screw in retaining screws.” (Fig. 4.15)
• Switch ON power supply.” (Fig. 4.15)
Inclusion/Exclusion
On factory default the device does not belong to any Z-Wave network. The
device needs
to be added to an existing wireless network to communicate with the
devices of this network.
This process is called Inclusion.
Devices can also be removed from a network. This process is called
Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network.
This
controller is turned into exclusion respective inclusion mode. Inclusion and
Exclusion is
then performed doing a special manual action right on the device.
Inclusion
To put the device into inclusion mode, turn the device‘s control dial (E) to “Set” and back to “0” within 5 seconds.
Exclusion
Exclusion = Remove To start the motion detector‘s exclusion mode, turn the device‘s control dial (E) to “Set” and back to “0” within 5 seconds.
Product Usage
The motion detector will also work” without being integrated into a” Z-Wave network. In this case, the” time setting is permanently set to” 3 minutes. When putting the motion” detector into operation, it will switch” OFF after the 10-second calibration” phase and is then activated for sensor” mode. The motion detector can” now be integrated into the Z-Wave” network.” The settings can be made via the” control dials or via Z-Wave network.” The settings last selected will always” be in effect regardless of whether” they were made via the control dials” or via Z-Wave network.
Factory settings
Twilight level (C): 2000 lux
Time setting: 3 min
Twilight setting (Fig. 5.1/C)
can be infinitely varied
Control dial set to moon =” twilight operation, approx. 2 lux
Control dial set to sun =” daylight operation, approx. 2000 lux
Note: To adjust the detection zone in” daylight, the control dial must be set” to sun = daylight operation.
Reach setting/adjustment
The detection zone can be optimised” to suit requirements.
Sensor unit
–– Sensor unit swivels through 180″°.” (Fig. 5.2)
–– Sensor unit tilts through 90″°.” (Fig. 5.5)
Adhesive shrouds (Fig. 5.3)” The film shroud can be used for” masking out any number of lens segments to limit reach as required.” Inadvertent triggering is ruled out or” the sensor can be targeted to watch” over danger spots. (Fig. 5.4)
Quick trouble shooting
Here are a few hints for network installation if things dont work as expected.
- Make sure a device is in factory reset state before including. In doubt exclude before include.
- If inclusion still fails, check if both devices use the same frequency.
- Remove all dead devices from associations. Otherwise you will see severe delays.
- Never use sleeping battery devices without a central controller.
- Dont poll FLIRS devices.
- Make sure to have enough mains powered device to benefit from the meshing
Association – one device controls an other device
Z-Wave devices control other Z-Wave devices. The relationship between one
device
controlling another device is called association. In order to control a
different
device, the controlling device needs to maintain a list of devices that will
receive
controlling commands. These lists are called association groups and they are
always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’
Command.
Association Groups:
Group NumberMaximum NodesDescription
1 | 1 | Lifeline |
---|---|---|
2 | 5 | Relay Switch |
3 | 5 | Motin begin/end – Relay Switch |
4 | 16 | Ambient light- Multilevel Sensor Report |
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock
further
enhanced features.
IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus
56.
In case of a two byte value the same logic applies: Values greater than 32768
may
needed to be given as negative values too.
Parameter 1: TIME
Duration of light after motion detection.
Size: 2 Byte, Default Value: 180
SettingDescription
5 – 900 | seconds |
---|
Parameter 2: LIGHT
Light threshold [ lx ]Value can be controlled via potentiometer –
potentiometer value isused as the default value and any potentiometer movement
rewritesthe current setting.
Size: 2 Byte, Default Value: 2000
SettingDescription
0 | run Learn ambient light sequence (the level is set automatically) |
---|---|
2 – 1999 | lux |
2000 | 2000 – is used as daylight ( always night mode) |
Parameter 5: SENSITIVITY
Motion Sensor (PIR) Sensitivity [%]Value can be controlled via potentiometer
– potentiometer value isused as the default value and any potentiometer
movement rewritesthe current setting
Size: 1 Byte, Default Value: 100
SettingDescription
2 – 100 | % |
---|
Parameter 8: GLOBAL_LIGHT
_Use External Ambient Light ValueWhen GLOBALLIGHT mode is ON – device
overrides its own lightsensor values and uses Light report values from any
Z-Wave lightsensor instead – this has to be configured appropriately to send
lightautomatically.If the last remote light level value is older than 30
minutes, the internallight value is used again until the next external value
is received.
Size: 1 Byte, Default Value: 1
SettingDescription
0 | OFF function |
---|---|
1 | ON function |
Parameter 9: SLAVE_MODE
_Can disable sensor controllu201cStupidu201d mode (bit 2 = 1): – has higher
priority then slave mode. – lamp is permanently on (usefull for simple power
wall switch controlling).Slave mode ( bit 0 = 1 ):- only if included in Z-Wave
network- usefull for controlling via third-party sensor- relay is directly
controlled via Z-Wave, internal sensors are not used for controlling
it.Central unit checking ( bit 1 = 1 ):( usefull especialy for controlling via
gateway ) When Slave bit is 0:- lamp signalises fail of lifeline connection (
if this bit is zero fail of lifeline connection is not signalised ) When slave
bit is 1:- device checks presence of Z-Wave device in lifeline group ( gateway
). If it is not present for 2 minutes ( testing repeatedly every 30 seconds )
device switches to normal mode in the same way as after the end of local
disabled mode ( ONBEHAVIOUR )- The device checks every 1 minute for recovery
of Lifeline connection.- if no lifeline specified – it works in normal modeBe
careful with this option, lamp stops using itu2019s own motion sensor in Slave
and Stupid mode.
Size: 1 Byte, Default Value: 2
SettingDescription
0 | Normal mode |
---|---|
1 | Slave mode without gateway checking |
2 | Normal mode with lifeline error signalisation |
3 | Slave mode with gateway checking |
4 | Stupid mode – lamp permanetly on |
Parameter 10: OFF_BEHAVIOUR
Behaviour after BASIC OFF ( and similar commands ).If a transition ( even
with zero change ) with a non-default duration isto be processed, the
transition cannot be interrupted by any motionevent in any case.for values
1-209 – Lamp is switched off and remains so until after a specified timeout
once a new motion event (local or remote) is received.
Size: 2 Byte, Default Value: 10
SettingDescription
0| Lamp is switched off and remains so until any new motion event (local or
remote) is received.
---|---
1 – 100| timeout: 1 second (1) to 100 seconds (100) in 1-second resolution
101 – 200| timeout: 1 minute (101) to 100 minutes (200) 1-minute resolution
201 – 209| timeout: 1 hour (201) to 9 hours (209) in 1-hour resolution
255| Lamp is switched off for TIME (cfg 1). It does not wait for a motion
event and works normally via current motion evaluation
Parameter 11: ON_BEHAVIOUR
Behaviour after BASIC ON (and similar commands).If a transition (even with
zero change) with a non-default duration is to be processed, the transition
cannot be interrupted by any motion event in any case.for values 1-209 – Lamp
is switched on and remains so until after a specified timeout once a new
motion event (local or remote) is received. It then works normally via current
motion evaluation.
Size: 2 Byte, Default Value: 255
SettingDescription
0| Lamp is switched on and remains so until any new motion event (local or
remote) is received. It then works normally via current motion evaluation.
Notice – during the day, this mode cannot be ended remotely due to motion
events not being transmitted – only via local motion sensor if enabled.
---|---
1 – 100| timeout: 1 second (1) to 100 seconds (100) in 1-second resolution
101 – 200| timeout: 1 minute (101) to 100 minutes (200) 1-minute resolution
201 – 209| timeout: 1 hour (201) to 9 hours (209) in 1-hour resolution
255| Lamp is switched on for TIME (cfg 1). It does not wait for a motion event
and works normally via current motion evaluation.
Parameter 12: ON_TIME_OVER
_Time limit to stop waiting for motion after timeout of ON_BEHAVIOURor
OFF_ONBEHAVIOUR ( 0-209 ) to prevent staying ON forever whenis no motion.
Size: 2 Byte, Default Value: 204
SettingDescription
0 | o additional waiting for motion. |
---|---|
1 – 100 | timeout: 1 second (1) to 100 seconds (100) in 1-second resolution |
101 – 200 | timeout: 1 minute (101) to 100 minutes (200) 1-minute resolution |
201 – 209 | timeout: 1 hour (201) to 9 hours (209) in 1-hour resolution |
255 | Never stop waiting before motion. |
Parameter 13: ON_OFF_BEHAVIOR
_Behaviour after after a rapid sequence of BASIC ON and BASIC OFF
commands.The intention is to use a much longer timeout value than the time
after a single ON command which should then be followed by a short timeout
value.The behaviour is almost the same as for parameter 10 (OFF_LOCALDISABLE)
for values 1-209 – Lamp is switched off and remains so until after a specified
timeout once a new motion event (local or remote) is received.
Size: 2 Byte, Default Value: 204
SettingDescription
0| Lamp is switched off and remains so until any new motion event (local or
remote) is received.
---|---
1 – 100| timeout: 1 second (1) to 100 seconds (100) in 1-second resolution
101 – 200| timeout: 1 minute (101) to 100 minutes (200) 1-minute resolution
201 – 209| timeout: 1 hour (201) to 9 hours (209) in 1-hour resolution
255| device ignores ON – OFF sequence and uses OFF behavior
Parameter 14: OFF_ON_BEHAVIOUR
Behaviour after after a rapid sequence of BASIC OFF and BASIC ONcommands.The
intention is to use a much longer timeout value than the time aftera single
OFF command which should then be followed by a shorttimeout value.The
behaviour is amost the same as for parameter 11for values 1-209 – Lamp is
switched on and remains so until after a specified timeout once a new motion
event (local or remote) is received. It then works normally via current motion
evaluation.
Size: 2 Byte, Default Value: 204
SettingDescription
0| Lamp is switched on and remains so until any new motion event (local or
remote) is received. It then works normally via current motion evaluation.
Notice – during the day, this mode cannot be ended remotely due to motion
events not being transmitted – only via local motion sensor if enabled.
---|---
1 – 100| timeout: 1 second (1) to 100 seconds (100) in 1-second resolution.
101 – 200| timeout: 1 minute (101) to 100 minutes (200) 1-minute resolution
201 – 209| timeout: 1 hour (201) to 9 hours (209) in 1-hour resolution
255| device ignores OFF – ON sequence and uses ON behaviour
Parameter 15: SEQUENCY_TIME
Time in [ 100 miliseconds ] of maximum delay between BASIC ONand BASIC OFF (
and vice versa ) to consider this as a sequence. It istypically 1 second, but
can be exceptionally longer due to retransmissionsand overload – in this case,
a longer interval can be allowed ( upto 5 seconds ).
Size: 1 Byte, Default Value: 255
SettingDescription
10 – 50 | tenth of second |
---|
Parameter 16: MOTION_DISABLE
Motion disable timeout after BASIC SET to motion endpoint when theinternal
motion sensor is not used for evaluating the behaviour of thelamp and groups 2
and 3. Events are, however, still transmitted to theLifeline, and the lamp can
be controlled via remote motion sensors.for values 1-209 – Internal motion
sensor is disabled for specified timeout after BASIC SET 0x00 to Motion
endpoint.
Size: 2 Byte, Default Value: 0
SettingDescription
0| BASIC SET to Motion sensor endpoint ignored, BASIC to root is mapped to
relay endpoint, motion sensor still enabled
---|---
1 – 100| timeout: 1 second (1) to 100 seconds (100) in 1-second resolution
101 – 200| timeout: 1 minute (101) to 100 minutes (200) 1-minute resolution
201 – 209| timeout: 1 hour (201) to 9 hours (209) in 1-hour resolution
255| BASIC SET to Motion sensor endpoint ignored, BASIC to root is mapped to
relay endpoint, motion sensor still disabled
Technical Data
Dimensions | 86 x 70 x 95 mm |
---|---|
Weight | 170 gr |
Hardware Platform | ZM5202 |
EAN | 4007841029807 |
IP Class | IP 54 |
Voltage | 230 V |
Load | 100 W |
Device Type | Notification Sensor |
Network Operation | Always On Slave |
Firmware Version | 00.26 |
Z-Wave Version | 04.26 |
Certification ID | ZC10-17045540 |
Z-Wave Product Id | 0x0271.0x0002.0x1a72 |
Supported Notification Types | Home SecuritySystem |
IP (Ingress Protection) Rated | ok |
Firmware Updatable | Updatable by Consumer by RF |
Neutral Wire Required | ok |
Sensors | LuminanceMotion/No Motion (Binary) |
Outdoor Use | ok |
Electric Load Type | |
Frequency | Europe – 868,4 Mhz |
Maximum transmission power | 5 mW |
Supported Command Classes
- Basic
- Switch Binary
- Switch All
- Sensor Multilevel
- Association Grp Info
- Device Reset Locally
- Zwaveplus Info
- Multi Channel
- Configuration
- Alarm
- Manufacturer Specific
- Powerlevel
- Node Naming
- Firmware Update Md
- Association
- Version
- Multi Channel Association
- Sensor Configuration
Controlled Command Classes
- Basic
Explanation of Z-Wave specific terms
-
Controller — is a Z-Wave device with capabilities to manage the network.
Controllers are typically Gateways,Remote Controls or battery operated wall controllers. -
Slave — is a Z-Wave device without capabilities to manage the network.
Slaves can be sensors, actuators and even remote controls. -
Primary Controller — is the central organizer of the network. It must be
a controller. There can be only one primary controller in a Z-Wave network. -
Inclusion — is the process of adding new Z-Wave devices into a network.
-
Exclusion — is the process of removing Z-Wave devices from the network.
-
Association — is a control relationship between a controlling device and
a controlled device. -
Wakeup Notification — is a special wireless message issued by a Z-Wave
device to announces that is able to communicate. -
Node Information Frame — is a special wireless message issued by a
Z-Wave device to announce its capabilities and functions.