Ceiling and wall luminaire
33 509
IP 65
Instructions for use
Application
Ceiling and wall luminaire with high protection class for a variety of
lighting tasks.
A luminaire made of aluminium alloy and crystal glass.
Product description
Luminaire made of aluminium alloy, aluminium and stainless steel BEGA Unidure
® coating technology
Crystal glass with white matt finish Silicone gasket
2 mounting holes ø 4.5 mm
Distance apart 200 mm
2 cable entries for through-wiring of mains supply cable ø 7-10.5 mm, max. 5 G
1.5@
Connection terminal 2.5@
Earth conductor connection
BEGA Ultimate Driver ®
LED power supply unit
220-240 V x 0/50-60 Hz
DC 176-264 V
DALI-controllable
Basic insulation is provided between the mains and control cables
BEGA Thermal Control ®
Temporary thermal regulation to protect temperature-sensitive components
without switching off the luminaire
Safety class I
Protection class IP 65
Dust-tight and protection against water jets
Impact strength IK07
Protection against mechanical
impacts < 2 joule
– Safety mark
– Conformity mark
Weight: 3.5 kg
This product contains light sources of energy efficiency classes C, D
Safety
The installation and operation of this luminaire are subject to national
safety regulations. Installation and commissioning may only be carried out by
a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation. If subsequent modifications are made to the luminaire, the
person responsible for these modifications shall be considered the
manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we
recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.
Lamp
Module connected wattage| 10.4 W
Luminaire connected wattage| 11.7 W
Rated temperature| ta = 25 °C
Ambient temperature| ta max = 60 °C
33 509 K3
Module designation| LED-0381/930
Colour temperature| 3000 K
Colour rendering index| CRI > 90
Module luminous flux| 1755 lm
Luminaire luminous flux| 936 lm
Luminaire luminous efficiency| 80 lm / W
33 509 K4
Module designation| LED-0381/940
Colour temperature| 4000 K
Colour rendering index| CRI > 90
Module luminous flux| 1860 lm
Luminaire luminous flux| 993 lm
Luminaire luminous efficiency| 84,9 lm / W
Installation
Undo locking screw and turn cover ring as far as it will go. Remove cover ring
and glass from the luminaire base.
LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during
installation or relamping.
Disassemble LED module.
Loosen LED-connection (plug connection).
Lead the mains supply cable through the cable entry into the luminaire back
housing.
Note position of application of the luminaire “arrow down”.
Fix luminaire base with enclosed or any other suitable fixing material onto
the mounting surface.
Be sure to use the gasket rings supplied.
Make the earth conductor connection and the electrical connection.
For digital control please use the connecting terminal DA, DA.
In case this terminal is not used the luminaire will be operated at full light
output.
In order to guarantee the maximum service life of the electrical components,
the enclosed desiccant pouch must be placed in the luminaire.
Remove the desiccant pouch from the foil packaging and place it in the
position marked by the red information label immediately before finally
closing the luminaire.
Push LED plug into coupler as fa as it will go.
Assemble LED module.
Tighten the screws evenly. Please observe that the LED board is not damaged
mechanically.
Make sure that gasket is positioned correctly.
Insert glass into the shield frame in such a way that the flattened sides of
the glass are in the region of the casting bars. Then turn glass inbetween the
bars.
Place cover ring with glass onto the luminaire base and turn it clockwise as
far as it will go.
Tighten locking screw.
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt and deposits.
Do not use high pressure cleaners.
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to
those of the modules originally fitted.
The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Inspect and, if necessary, replace the luminaire gaskets.
Defective glass must be replaced.
Close the luminaire.
Spares
Spare glass| 11 002 976 11
LED power supply unit| DEV-0340/350
LED module 3000 K| LED-0381/930
LED module 4000 K| LED-0381/940
Gasket| 83 001 382
BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden