BEGA 50 210 Wall Luminaire Instruction Manual

June 12, 2024
BEGA

BEGA 50 210 Wall Luminaire

Product Information

Product Name Luminaire
Safety The installation and operation of this luminaire are subject to

national safety regulations. Installation and commissioning may
only be carried out by a qualified electrician. The manufacturer
accepts no liability for damage caused by improper use or
installation. If subsequent modifications are made to the
luminaire, the person responsible for these modifications shall be
considered the manufacturer.
Overvoltage Protection| The electronic components installed in the luminaire are
protected against overvoltage in accordance with DIN EN 61547. To
achieve an additional protection against e.g. transients, etc. we
recommend separate overvoltage protection components. You can find
them on our website at www.bega.com.
Lamp| Lamp connected wattage: 14.8 W
Module Designation| 2x LED-0662/930
Colour Temperature| 3000 K
Colour Rendering Index| 1R3a2>0
Module Luminous Flux| 90 lm
Luminaire Luminous Flux| 953 lm
Luminaire Luminous Efficiency| 64.4 lm / W

Product Usage Instructions

  1. For installation and commissioning, only qualified electricians should be involved.
  2. To ensure safety, follow national safety regulations.
  3. If modifications are made to the luminaire, the person responsible for these modifications will be considered the manufacturer.
  4. To protect against overvoltage, the luminaire is equipped with electronic components in accordance with DIN EN 61547. Additional overvoltage protection components can be purchased separately from our website.
  5. When replacing the LED module, disconnect the system and open the luminaire. Follow the LED module installation instructions provided. Defective glass must be replaced. Close the luminaire after installation.

Wall luminaire for indoor use

BEGA-50-210-Wall-Luminaire-01

Instructions for use

Application
Free-radiating wall luminaire · indoor luminaire with crystal glass and metal bracket. For all lighting tasks in interior applications.
They are ideal for places where a soft and uniform lighting distribution is required.

Product description

  • Metal housing, finish colour white
  • Crystal glass, inside white
  • 2 mounting holes ø 4.5 mm
  • Distance apart 219 mm
  • 2 cable entries for through-wiring for mains cable up to ø 10.5 mm max. 3 × 1.5@ Connection terminal 2.5@
  • Earth conductor connection
  • LED-Module for mains voltage  220-230 V y 50/60 Hz
  • BEGA Thermal Switch®
  • Temporary thermal shutdown to protect temperature-sensitive components
  • Safety class I
  • BEGA-51 012.6-Ceiling-Luminaire -03 – Safety mark
  • CE – Conformity mark
  • Weight: 2.1 kg

This product contains light sources of energy efficiency class(es) G

Safety
The installation and operation of this luminaire are subject to national safety regulations. Installation and commissioning may only be carried out by a qualified electrician.
The manufacturer accepts no liability for damage caused by improper use or installation. If subsequent modifications are made to
the luminaire, the person responsible for these modifications shall be considered the manufacturer.

Overvoltage protection
The electronic components installed in the luminaire are protected against overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we recommend separate overvoltage protection components.
You can find them on our website at www.bega.com.

Lamp

  • Luminaire connected wattage 14.8 W
  • Rated temperature ta = 25 °C
  • Ambient temperature ta max = 30 °C

50 210 K3

  • Module designation 2x LED-0662/930
  • Colour temperature 3000 K
  • Colour rendering index Ra > 90
  • Module luminous flux 1320 lm
  • Luminaire luminous flux 953 lm
  • Luminaire luminous efficiency 64,4 lm / W

Installation

LED are high-quality electronic components! Please avoid touching the light output opening of the LED directly during installation or relamping.

BEGA-50-210-Wall-Luminaire-02
Loosen the captive screw.
Before taking off the glass make sure that the captive screw protrudes from the glass. Lead mains supply cable through the cable entry into the luminaire base.
Fix luminaire base with enclosed or any other suitable fixing material onto the mounting surface.
It is imperative to use the enclosed gaskets. Note position of application “arrow down”. Make earth conductor connection.
Push silicone sleeves over the lines and make electrical connection.
Incline the glass smoothly and insert it on the pin of the luminaire base. Tighten the captive screw.
Note: For installation in vertical position make sure that the glass is carried until the screw is tightened.

Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt.

Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to those
of the modules originally fitted. The module can be replaced by a qualified electrician or a comparably qualified person using standard tools.
Disconnect the system and open the luminaire. Please follow the installation instructions for the LED module.
Defective glass must be replaced.
Close the luminaire.

Spares

  • Spare glass 11 002 786 11M RG
  • LED module 3000 K LED-0662/930

BEGA Gantenbrink-Leuchten KG · Postfach 31 60 · 58689 Menden · info@bega.com · www.bega.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals