EVOHEAT Evo270-1 Hot Water Heat Pump Instruction Manual
- June 12, 2024
- EVOHEAT
Table of Contents
INSTALLATION & OPERATION MANUAL
Evo270-1 Hot Water Heat Pump
Evo270-1 Hot Water Heat Pump
Introduction
This manual contains information relating to the installation, troubleshooting, operation, and maintenance of this EvoHeat unit. Instructions in this manual must always be followed. Failure to comply with these recommendations will invalidate the warranty. Should you have any questions or require technical support, call the EvoHeat office on 1300 859 933 to speak to our team.
TECHNICAL DATA | Evo270-1 |
---|---|
Storage Capacity | L |
Max Temperature Setting | ˚C |
Power Input | kW |
Heating Output | kW |
C.O.P at 20˚C Air | 4.27 |
Noise Rating | dB(A) |
Running Current | A |
Power Supply | |
Water Inlet/Outlet Size | mm |
Auxiliary Heating | kW |
Operating Temperature Range | ˚C |
Hot Water Recovery | L/hr |
With Hydro Boost | L/hr |
Net Weight | kg |
The
EVO 270-1 is the next evolution in water heating with advanced energy
efficiency technologies and built-in smart features to ensure you’re provided
with clean, safe, and economical hot water all year round.
Conforms to AS 3498-2020 Australia and New Zealand
Measurement conditions: Instant heating: Ambient air temperature 20°C/15°C,
water inlet 15°C, water outlet 55°C, highest setting temperature: 75°C
Working Temp Range
- Ambient temperature is -5°C ~ 43°C (Heat Pump)
- The max temperature of water tank is 70
Operating parameters: The range of the operating water pressures: 0.15~0.7MPa
Dimensions
Evo270-1 | A | B | C | D | E | DIAMETER |
---|---|---|---|---|---|---|
1992 | 1443 | 593 | 1211 | 1111 | 640 |
DO NOT DRILL
Do not drill any fixings or attachments into the outer casing of the tank.
Drilling into the outer casing of the tank may damage the heating coil and
WILL VOID WARRANTY.
INITIAL STARTUP
-
Press and hold for one second to power on the unit.
-
To set the time:
a. Press once so the hour digit starts flashing,
b. Use to adjust the hour and press to confirm,
c. Repeat for the minute, day, month and year,
d. Press at any stage to cancel. -
Press until is displayed. This will activate “Eco Heating” (Heat Pump only) mode and will provide the most efficient heating.
-
During periods of unusually high hot water demand (such as additional occupants staying with you), you can activate “High Requirement” mode by pressing until is displayed.
-
In any event where there is a failure within the system, the Electric Element (Hydroboost Mode) can be engaged with “one push activation” of the button until is displayed. This will provide emergency water heating until service can be attended.
-
For adjustment of timers or activating vacation mode, please refer to our online tutorials at: www.evoheat.com.au/tech-support
Safety Instructions
Ensure that all safety instructions and recommendations are always adhered to. Failure to comply with these recommendations could void the warranty and cause injury or death.
- Installation, repair, or relocations must only be done by a fully qualified technician.
- The Evo270-1 must be installed to conform to all relevant Australian Standards and Industry Codes including but not limited to: Electrical & Electrical Safety, Plumbing & Hot Water Storage, Heat Pump Installation & Operation
- A circuit breaker must be installed for the unit.
- Ensure the unit has a good power connection and earthing to avoid the risk of electrical shocks.
- Ensure that there are no leaks on both the plumbing and drainage fittings.
- The unit must not be installed near flammable gas or have flammable aerosols sprayed in the vicinity.
- The base that the unit is installed on must be level and stable.
- If the supply cord is damaged, it must be replaced by a qualified service agent.
- This appliance must be installed in accordance with national wiring regulations.
- Installation must also comply with any local, state or federal codes at the installation site. Failure to comply can void your warranty, damage your unit or possible cause injury or death. Plumbing must comply with AS/NZS3500.4
- Before obtaining access to terminals all supply circuits must be disconnected.
- A P&T valve MUST be installed in the tank. When the tank pressure reaches 0.85MPa or when the tank temperature reaches 99°C, the P&T valve will open automatically so as to reduce the pressure or temperature decrease.
- In the event of the unit malfunctioning, shut off the power supply and contact your supplier or EvoHeat.
- In order to use the unit correctly, run the unit at environment temperature -5°C – 43°C
- The unit contains sophisticated electronic devices, do not use unsafe water sources such as lake or groundwater.
- The unit produces hot water and will also have hot fittings, therefore should not be touched to avoid injury.
- Do not drill any fixings or attachments into the outer casing of the tank. Drilling into the outer casing of the tank may damage the heating coil and WILL VOID WARRANTY.
- If the unit stops and you restart the unit or turn it on manually, the unit will not start to run again for approximately 3 minutes. This is a protection feature to safeguard the compressor.
- The handle of the P&T safety valve should be tested once every six months to remove the calcium carbonate deposits and guarantee there is no blockage in the device.
- Once installation is complete, check that all connections are secure before the power is turned on.
- The installer is to explain to the end user how to operate and maintain the unit in accordance with this instruction manual.
- Evo Industries Australia Pty Ltd will not be held responsible for any damages or injuries caused by the incorrect installation of this hot water system.
- A maintenance programme must be carried out as recommended in this manual to ensure ongoing reliability.
To reduce the risk of excessive pressures and temperatures in this water
heater, install temperature and pressure protective equipment required by
local codes and no less than a combination temperature and pressure relief
valve certified by a nationally recognized testing laboratory that maintains
periodic inspection of production of listed equipment or materials, as meeting
the requirements for Relief Valves and Automatic Gas Shutoff Devices for Hot
Water Supply Systems, ANSIZ21.22. This valve must be marked with a maximum set
pressure not to exceed the marked maximum working pressure of the water
heater. Install the valve into an opening provided and marked for this purpose
in the water heater, and orient it or provide tubing so that any discharge
from the valve exits only within 6 inches above, or at any distance below, the
structural floor, and does not contact any live electrical part. The discharge
opening must not be blocked or reduced in size under any circumstances.
Hydrogen gas is produced in a hot water system served by this heater that has
not been used for a long period of time (2 weeks or more). Hydrogen gas is
extremely flammable. To reduce the risk of injury under these conditions, it
is recommended that the hot water faucet be opened for several minutes at the
kitchen sink before using any electrical appliance.
The appliance is fitted with means for disconnection from the supply mains
having a contact separation in all poles that provide full disconnection under
overvoltage category lll conditions, and these means must be incorporated in
the fixed wiring in accordance with the wiring rules.
WARNING
THIS PRODUCT CONTAINS A BUTTON BATTERY
If swallowed, a lithium button battery can cause severe or fatal injuries
within 2 hours.
Keep batteries out of reach of children.
If you think batteries may have been swallowed or placed inside any part of
the body, seek immediate medical attention.
Installation
5.1 System Installation
Upon receiving the unit, check the packaging for any obvious signs of damage.
Inform EvoHeat immediately if there is any evidence of rough handling.
Do not drill any fixings or attachments into the outer casing of the tank.
Drilling into the outer casing of the tank may damage the heating coil and
WILL VOID WARRANTY.
The P&T valve attached with the unit must be installed. Failure to do so will
cause damage to the unit and possible personal injury.
Drain the water tank through the drain valve at the bottom part of the unit.
Do not use stainless steel fittings to connect directly with other metals to
prevent galvanic corrosion.
Note: A pressure releasing valve is to be fitted within the installation.
Spec of P&T valve: Pressure: 0.85MP Temperature: 99°C Water Inlet or Outlet Pipes: The specification of the
water inlet and outlet thread is BSP3/4 (internal thread). Pipes must be heat-
resistant and durable. Piping for the P &T Valve:
The spec of the valve connecting thread is BSP3/4 (internal thread). After
installation, confirm that the drainpipe outlet is exposed in the air. When
the flexible drainpipe is joined to the pressure relief orifice of this valve,
ensure that the flexible drainpipe is pointing downwards and exposed in the
air.
5.2 Handing & Transportation
The unit should be stored and/or transported in its shipping container in an
upright position and without water charge.
For transport over short distances, and provided due care is exercised, an
inclination angle of up to 30 degrees is permitted. During transport and
storage, ambient temperatures of -10 to +60 degrees Celsius are permissible.
Forklift Transportation
The unit must remain mounted on the pallet and lifted at minimal speed. Due to
its top heaviness, the unit must be secured against tipping over and placed on
a level surface.
Manual Transportation
Ensure that the maximum permissible inclination angle of 60 degrees is not
exceeded. If transport in an inclined position cannot be avoided, the unit
should be left to rest at least one hour after it has been moved into final
position before operation.
5.3 Location of Installation
The Evo270-1 is designed for external installation, however, where possible
installing the unit under the house eaves or in a sheltered environment may
help prolong the life of the system.
Heat pumps operate most efficiently with warmer air temperatures, and the
outlet air from the unit will always be colder than the inlet air. Therefore,
it is advisable to install the unit so it receives the warmest air
temperatures possible and that the cold air is not able to recirculate back
into the unit.
5.3.1 Indoor Installation
- The unit may be able to be installed in an unventilated room exceeding 25m³ in volume.
- Venting of cold air is advised to prevent the air temperature dropping and lowering the efficiency of the unit.
- Think of the unit as a 3kW air conditioner for the effect it will have on a closed room.
TO COOL A ROOM
Install the unit so the outlet from the heat pump is blowing INTO the room.
The room MUST have some form of air outlet otherwise the performance of the
unit will suffer significantly.
TO MAINTAIN NORMAL ROOM TEMPERATURE
Install the unit so the outlet from the heat pump is blowing OUTSIDE the room.
The room MUST have some form of air inlet otherwise the performance of the
unit will suffer significantly.
5.4 Airflow Clearances The Evo270-1 must be installed with sufficient clearances to allow airflow to circulate through the unit, it is advised to keep a minimum gap between walls/fences etc of:
- 300mm on the air inlet side
- 500mm on the air outlet side
- 100mm overhead & rear clearance
Without sufficient airflow, discharged cold air will recirculate into the unit
and consequently lower the heating efficiency.
If the installation location does not comply with these suggested clearances,
contact EvoHeat’s Tech Support to discuss possible solutions.
5.5 Cable Connection
The power cable for power supply of the unit is stored in the back of the
unit. The unit requires an isolating switch as required by local laws. If the
power cord is damaged, it must be replaced by a qualified electrician.
5.6 Filling the Tank
Open a hot water tap inside the house. Open the cold-water inlet valve into
the Evo270-1 to fill the tank. When water begins flowing out of the hot water
tap inside the premises, turn off the hot water tap.
5.7 Initial Start-Up
PRE-INSPECTION
Check the water supply to the tank and pipe connections for possible leaks.
Check that the following devices are installed and operating correctly:
- Drainpipes
- P&T Valve
- Filter on inlet
- Water softening and pressure reducing devices if required.
Check that all power connections are secure before switching on.
Check that the installation space is adequate.
TRIAL OPERATION
Switch on the unit by using the controller.
If any unusual noises occur, switch the power off and consult your provider.
The parameters have been pre-set to a temperature of 60 degrees. Check that
the unit is operating by looking for an increase in water temperature over
time.
Operation
6.1 The Controller
| ON/OFF| Turn the unit on or off.
---|---|---
| UP| Select options to increase values
| DOWN| Select options to decrease values
| CLOCK| Set the clock or the timer.
| HYDROBOOST| Turn on/off the electric heater
| MODE| Switch unit running modes or save setting parameters
| TOUCH TIMING| Touch timing settings
| HEATING MODE| The unit will start according to the water temperature and
target temperature. The electric heater will not start immediately. After 200
minutes, the unit will judge if it has reached target temperature. If not, the
electric heater will start.
---|---|---
| ECO HEATING MODE| The heat pump system will start according to the water
temperature and target temperature. The electric heater always will be off.
| INTELLIGENT MODE| The unit will automatically judge the operation mode
according to the ambient temperature.
| HIGH REQUIREMENT MODE| The difference between heating mode and high
requirement mode is the delay time of electric heater. In the high demand
mode, the electric heater will start without delay, which can help the user to
heat water quickly in a short time.
| VACATION MODE| Enable Vacation mode
---|---|---
| FAN| Fan is on
| HYDROBOOST| The Hydroboost setting is on
| DEFROST| The unit is defrosting
| LOCK| Keyboard is locked
SET| PARAMETERSETTING| Parameter is adjustable
| SET TEMP REACHED| Set temperature has been reached and the unit will shut
off automatically
DOWN| LOWER TANK TEMP| Temperature of the lower tank
min| MINUTE| Minute value is being set
s| SECOND| Second value is being set
| WI-FI| State of Wi-Fi connection
*Only available as an optional upgrade
6.2 Operating Functions
EvoHeat have developed a YouTube Channel with video walkthroughs of the
different controller functions.
Scan the QR code or head to our channel to view the videos we have available
https://www.youtube.com/@evoheatpumps
6.2.1 Startup & Shutdown
Press and hold for 0.5 seconds in the standby screen of the controller to turn
the unit on. The main display will now show the water outlet temperature.
Press and hold for 0.5 seconds in the running screen of the controller to turn
the unit off. The main display will now show “OFF”.
The unit will dim the screen and display the standby screen when the
controller has not been touched for a minute. Touch the power button to wake
it.
Note: The ON/OFF button can only be used to turn the unit on/off in
standby or on the running screen of the controller. 6.2.2 Switching Modes
We recommend running the unit in Eco Heating mode where possible for maximum
energy efficiency.
From the running screen, press to select one of the modes: Heating, Eco
Heating, Intelligent, High requirement, Vacation. 6.2.3 Locking the
Controller
To both lock and unlock the controller, press and hold the button for 5
seconds.
When the controller is locked, a lock symbol will appear on the bottom right.
6.2.4 Setting & Checking the Target Temperature
In the standby or running interface, press or once to check the target
temperature of the outlet water.
Press or again to change the target temperature.
After making changes to the desired temperature, press to confirm or to
cancel, then return to the previous screen.
If the keypad is left idle for 5 seconds, the controller will exit the menu
automatically and apply any changes that were made.
Example: The target temperature is 40°C, the actual outlet water
temperature is 18°C. 6.2.5 Hydroboost Setting
Also known as the Electric heater, the Hydroboost setting allows higher levels
of hot water to be produced. When there are high hot water usage requirements
(such as guests staying), this function may come in useful.
The Hydroboost setting can be turned on when the unit is in heating or in
standby mode.
Press once to turn on Hydroboost on or off.
When activated, will light up on the main display.
6.2.6 Force Defrost
In the extremely unlikely circumstance of the unit icing up (for example, if
the unit was installed inside with no ventilation), this function can be
applied.
When the unit is off, press and hold for 10 seconds to enable the forced
defrosting function. The defrosting symbol will light up. Press for 10 seconds
again to exit the forced defrosting function.
6.2.7 Fan/Ventilation Function
This function may come in useful if the system is installed inside and the fan
settings need to be adjusted to suit ducting or external ventilation.
The fan speed (High Speed, Low Speed or Off) can be controlled by the fan mode
on the controller.
Fan mode symbols:
High Speed
Low speed
No Fan Icon: off
Note: When H02 is set to 0, there is no ventilation function.
Note: when the compressor is on, the fan will always run at high speed.
When the parameter HO2 is set to 1, press the for 2s.
Once you hear a beep you can set the ventilation mode. Press for 2s, this will
change the fan speed.
Continue to press for 2s until you reach your preferred speed.
6.2.8 System Date & Time
In the standby or running interface, press once, the hour digit will flash
indicating it is being altered.
Press the or to change the hour setting, then press to confirm. Repeat this to
change the minute value. 6.2.9 Setting & Cancelling Timers
Timers can be set in standard mode, economic mode, auto mode & fast heating
mode. They can be set by using buttons or using the touch timing circle. The
unit will run during the lit time periods and stop in the dim areas.
Touch Method | Button Method |
---|
• Press and hold for 2 seconds (the timer display will flash)
• When the timer display flashes, choose yourstart-up time (A) and end time
(B).
• Press to save the setting and exit back to the main interface.| • Press and
hold for 2 seconds (the timer display will flash)
• When the timer display flashes, choose the start-up time (C) and end time
(D) by pressing or and .
• Press to save the setting and exit back to the main interface.
Example: Setting the unit to run from 7-11am & 4pm-6pm using Touch mode.
To cancel a timer once it has been set,
hold down the CLOCK button for 2 seconds until the timer display begins
flashing (as you would set the timer).
Press the POWER button while the timer is flashing to cancel it. The yellow
timing periods will disappear when the timer has been cancelled.
6.2.10 Vacation Mode
Vacation Mode allows you to turn the unit off to conserve power for an
extended period of time, and restart operation on a date you specify. This
ensures you have hot water waiting for you upon your return.
Ensure the unit is ‘OFF’ before setting vacation mode. The date you set in
this mode will determine what date the unit starts back up.
After selecting vacation mode, press and hold for 2 seconds, the ‘month’ value
will begin to flash in the display area. Press the UP or DOWN arrows to
display the desired month, then press to confirm and move to altering the
‘day’ value.
The ‘day’ value will flash when it is selected, use the arrow keys to select
your desired start day, then press to save all changes and exit back to the
main interface.
Note: Format is mm/dd
Example: The unit will start up on September the 28th. 6.2.11 Sanitech System
The Sanitech feature’s purpose is to keep the water free of bacteria such as
Legionella by heating the tank water to 70°C for one 30-minute period every
week at midnight.
An instance when you may want to alter the Sanitech function is if you have
solar and would prefer the Sanitech to run during the day, for example at
12pm, rather than midnight.
If you would like to change this function, contact EvoHeat’s service
department for guidance. Incorrectly attempting to adjust these settings
yourself could significantly disrupt the unit’s operation.
Troubleshooting
Malfunction | Fault Display | Reason | Elimination Methods |
---|---|---|---|
Bottom water temp. failure | P01 | The water bottom temp. sensor is open or | |
short circuit. | Check or change the water bottom temp. sensor | ||
Top tank water temp.failure | P02 | The water top tank temp. sensor is open or | |
short circuit | Check or change the water top tank temp. sensor | ||
Ambient temp. failure | PO4 | The ambient temp. sensor is open or short circuit |
Check or change the ambient temp. sensor
Coil temp. failure| P05| The pipe temp. sensor is open or short circuit| Check
or change the pipe temp. sensor
Refrigerant absorb temp. failure| P07| The evaporator temp. sensor is open or
short circuit| Check or change the evaporator temp. sensor
Anti-freeze temp. failure| P09| The anti-freeze temp. sensor is open or short
circuit| Check or change the anti-freeze temp. sensor
Solar temp. failure| P034| The solar temp sensor is open or short circuit|
Check or change the solar temp sensor
High pressure protection| E01| The exhaust pressure is high, high pressure
switch action| Check high pressure switch and cooling return circuit
Low pressure protection| E02| The suction pressure is low, low pressure switch
action| Check low pressure switch and cooling return circuit
Water flow failure| E03| No water or little water in water system| Water,
check for flow volume pump failure
Electric-heater overheat protection| E04| Water flow volume not enough, water
system pressure difference is small| Water, check if the flow volume system is
jammed
Anti-freeze protection| E05| Water flow volume not enough, water system
pressure difference is small| Water, check if the flow volume system is jammed
Communication failure| E06| Wired remote control with master signal failure|
Check the connection line between the wired remote control and mother board
Winter defrost protection| E07| Ambient temperature is too low|
Appendix
8.1 Wiring Diagram 8.2 Wi-Fi Module Connection (Optional)
Note: If you do not have a Wi-Fi module to install, simply push the cord
entirely behind the front panel.
The optional Wi-fi Control upgrade can be purchased to allow you to remotely
control your EvoHeat hot water heat pump from your phone.
Newly installed units will have a small cable that protruding out from behind
the front panel with a small waterproof cover.
If you are installing the Wi-Fi module, simply connect the cable of the Wi-Fi
module to the one that protrudes.
Once the Wi-Fi module has been connected, ensure that the connection part of
the cable is placed behind the front cover.
The module must be placed with the cord coming downwards to protect it from
water. 8.3 Use of the P &T Valve
The P&T valve is used to prevent the temperature or pressure becoming too high
inside the tank. When the temperature or pressure reaches the set value, the
valve will open automatically to force the pressure or temperature to decrease
The handle of the safety valve should be tested once every six months to
remove the calcium carbonate deposits and guarantee there is no blockage in
the device. Take care to avoid burns as the temperature of the discharging
water is very high.
Vent pipes should be thermally insulated to prevent safety risks caused by
freezing pipes in winter.
P&T valve: Model: PTR-20, action temperature: 99˚C, action pressure:0.85MPa
WARNING: Failing to operate the relief valve easing gear at least once every six months may result in the water heater exploding. Continuous leakage of water from the valve may indicate a problem with the water heater.
8.4 Using the Overheating Protector
The overheating protector is used to turn the power off in an emergency or
with power supply issues, preventing the water from being heated too high.
A thermal cut-out could indicate a possibly dangerous situation. Do not reset
the thermal cutout until the unit has been serviced by a qualified technician.
Contact EvoHeat for a service if this occurs before attempting to reset.
Remove the screws and open the cover
To return the unit to its normal operation status by resetting manually:
a) To access the overheat protector, remove the front dark grey controller
panel.
b) Remove the 3 screws on the front panel and push the front cover upwards.
c) Remove the remaining screws which cover the overheat protector panel.
Press the red button to reset
8.5 Draining the Water Tank
- Close the cold-water inlet valve into the Evo270-1.
- Open a hot water tap inside the premises.
- Undo the drain plug on the base of the unit to drain the water from the system.
The water from the hot water tap and the drain plug will be hot. Be careful of burns and scalds. Wear protective clothing.
8.6 Earthing Methodology
Maintenance
Your Evo270-1 will operate most efficiently if regularly inspected as part of
your home maintenance schedule.
MINOR ANNUAL MAINTENANCE
It is recommended that the minor maintenance be performed every 12 months by
the dwelling occupant.
The minor maintenance includes:
- Operate the easing lever on the temperature pressure relief valve. It is very important you raise and lower the lever gently. Exercise care to avoid any splashing of water, as water discharged from the drain line will be hot. Stand clear of the drain lines point of discharge when operating the valve’s lever.
- Operate the easing level on the expansion control valve (if fitted). It is very important you raise and lower the lever gently.
- Conduct a visual inspection of all plumbing and electrical connections.
- Check the condensate drain line to ensure it is not blocked.
- Check that air vents are not blocked or obstructed, and if necessary clean with a damp cloth or air blower.
- Conduct a general external clean of the unit with a damp cloth.
MAJOR FIVE-YEAR SERVICE
It is recommended a major five (5) year service be conducted on the Evo270-1.
Warning: Servicing of a water heater must only be carried out by
qualified EvoHeat personnel.
Phone EvoHeat Service on 1300 859 933 for our closest Accredited Service
Agent.
Note: The five-year service and routine replacement of any components
such as the anode and relief valve(s) are not included in the EvoHeat
warranty. Only genuine replacement parts should be used on this water heater.
The major service includes the following actions:
- Replace the temperature limiting valve.
- Replace the temperature pressure relief valve.
- Inspect the anode and if required, replace the anode. If the anode is not replaced, it should be replaced within three years of this service.
- Check the heating cycle of the unit.
- Visually check the unit for any potential problems.
- Inspect the plumbing and electrical all connections.
- Check the condensate on drain line to ensure it is not blocked.
Note: The water heater may need to be drained during this service. After the completion of the service, the water heater will take some time to reheat the water. Depending upon the power supply connect on, hot water may not be available until the next day.
Warranty
Refer to the EvoHeat website for warranty details
- Australia: https://evoheat.com.au/warranty-terms/
- South East Asia: http://evoheat.com.sg/warranty/
-
Warranty terms are from date of purchase.
-
This warranty excludes any defect or injury caused by or resulting from misuse, abuse, neglect, accidental damage, improper voltage, vermin infestation, incompetent installation, any fault not attributable to faulty manufacture or parts, any modifications which affect the reliability or performance of the unit.
-
This warranty does not cover the following:
a. Natural Disasters (hail, lightening, flood, fire etc.)
b. Rust or damage to paintwork caused by a corrosive atmosphere
c. When serviced by an unauthorized person without the permission of Evo Industries
d. When a unit is installed by an unqualified person
e. Where a unit is incorrectly installed
f. When failure occurs due to improper or faulty installation
g. Failure due to improper maintenance (refer Operating Instructions)
h. ‘No Fault Found’ service calls where the perceived problem is explained within the
i. Costs associated with delivery, handling, freighting, or damage to the product in transit. -
If warranty service is required, you should:
a. contact Evo Industries Australia on 1300 859 933 or via our Contact page on our web site
b. provide a copy of your receipt as proof of purchase
c. have completed the online Warranty Registration Form -
Onsite technical service is available within the normal operating area of your Evo Authorised Service Agents.
Service outside this area will incur a traveling fee. -
Unless otherwise specified to the purchaser, the benefits conferred by this express warranty and additional to all other conditions, warranties, rights and remedies expressed or implied by the Trade Practices Act 1974 and similar consumer protection provisions contained in legislation of the States and Territories and all other obligations and liabilities on the part of the manufacturer or supplier and nothing contained herein shall restrict or modify such rights, remedies, obligations or liabilities.
REGISTER YOUR WARRANTY
EvoHeat highly recommend customers complete their warranty details online to
ensure efficient warranty claim processing.
To register your warranty, scan our QR Code or head to our website and fill in
the Warranty Registration Form: https://evoheat.com.au/warranty-
registration/
THE HEAT PUMP EXPERTS