EVOHEAT Evo Ultra Series Instruction Manual

June 4, 2024
EVOHEAT

EVOHEAT Evo Ultra Series

EVOHEAT Evo Ultra Series product

Introduction

This manual contains all the necessary information in regard to the installation, troubleshooting, operation and maintenance of this unit. Ensure instructions in this manual are adhered to at all times. Failing to comply with these recommendations will invalidate the warranty. This manual and all others are available for download on our website.
EVOHEAT Evo Ultra Series 01The Evo Ultra is our water to water heat pump that is the perfect solution in applications where chillers and cooling towers are being used for temperature control. When installed in line with the chiller, the Evo Ultra can capture rejected waste from the chiller return lines and utilize this heat to provide FREE HOT WATER!

  •  Bulk hot water up to 80 degrees
  •  Provides fast, stable hot water in climates -7°C to 45°C
  •  Extremely energy efficient
  •  Connect to your cooling tower to benefit from FREE HOT WATER
  •  Market leading protection features
  •  Reduces energy use and green house gases
  •  304 stainless steel cabinet

Unit Specifications

Dimensions

EVO ULTRA 32
EVOHEAT Evo Ultra Series 02
EVOHEAT Evo Ultra Series 03 EVO ULTRA 64EVOHEAT Evo Ultra Series
04
EVOHEAT Evo Ultra Series 05
EVOHEAT Evo Ultra Series 07 EVO ULTRA 129
EVOHEAT Evo Ultra Series 08

Operational Principle

According to Reverse Carnot Cycle theory and the same process as normal water source heat pump units, The Evo Ultra absorbs heat from soil and transfers the heat to water as the soil temperature is generally stable, i.e., the heat source is stable, the units work capability will not change with the ambient temperature.
EVOHEAT Evo Ultra Series 09

 Technical Data
Model Evo Ultra 32 64 129
Heating Heating Capacity kW 32.3 64
kcal/h 27810 55900 111000
Cooling Capacity kW 19.8 40 80
kcal/h 17048 34400 68000
Input Power kW 10 20 40
Input Current A 18.2 35.2 71
Power Supply / / 380V/3N~/50Hz 380V/3N~/50Hz
Compressor Type / EVI Scroll EVI Scroll
Quantity / 1 2 4
Heat Source Side Head Exchanger Type / Tube in Shell HX Tube in Shell HX

Tube in Shell HX
Water flow rate| M3/h| 2.7| 5.6| 11.1
Water pressure drop| kPa| 34| 45| 23
Water (in) connection| /| DN32| DN65| DN65
Water (out) connection| /| DN32| DN65| DN65
Cool Source Side Heat Exchanger| Type| /| Tube in Shell HX| Tube in Shell HX| Tube in Shell HX
Water flow rate| M3/h| 3.5| 6.8| 13.6
Water pressure drop| kPa| 13| 23| 45
Water (in) Connection| /| DN32| DN65| DN65
Water (out) Connection| /| DN32| DN65| DN65
Noise| dB (A)| 55| 56| 58
Unit Dimension (L/W/H)| mm| 1030/640/730| 1172/900/1365| 1600/1130/1500
Unit Weight| kg| 219| 841| 925

Heating:

  • Heat source side: water inlet/outlet temperature: 20°C/15°C
  • User side water inlet/outlet temperature: 65°C/75°C
  • When the units work between 55-85°C, make sure the low-pressure range is between 0.27-0.65MPa and the evaporating temperature is between 7-30°C.
  • The above data is for reference only, specific data is subject to the product nameplate.

Safety Instructions

  •  Installation, repair or relocations must be done by a fully qualified person and not by the customer. If done incorrectly it may cause fire, electric shock, water leakage and other hazards.
  • Maintenance and operation must be carried out according to the recommended time and frequencies, as stated in this manual.
  • To avoid risk of electrical shock, the unit must have a good power connection and earthing.
  •  Use genuine standard spare parts only.
  •  When an abnormality (smell of burning, etc.) occurs, stop the unit and disconnect the power or turn off the breaker. If the unit continues to be operated in an abnormal condition, it may cause a fire or hazards.
  •  Do not insert fingers or objects into the fans or evaporator of the unit.
  • You should have a program to ensure personal safety in the case of a refrigerant leak when the unit is installed in a small room.
  •  For unit cleaning or maintenance, switch off and disconnect the power of the unit.
  • Do not install the unit near flammable gas or spray flammable substances near it.

Installation

Installation Notes
  •  Choose the right product model according to climate, architecture and insulation situation.
  •  Read the product user guide before installation and clearly understand what each label means. Please install, test and maintain the units according to the user guide.
  • Check every attachment in case of omission.
  •  This model can be installed on a concrete base with expansion bolts or installed on the ground or roof by a steel bracket with rubber cushion. Make sure that the units are horizontally placed.
  • The units should be installed at a place convenient for installation and maintenance.
  •  The units should install shock-absorbing devices in case of the shock transferring to the building.
  • Rigid pipelines in the engine room should adopt spring shock-absorbing brackets.
  •  Units should be installed indoors or outdoors with a shelter.
  • Units should be installed somewhere with no radiation or other heat sources.
Transit

Use four slings longer than 8m when moving the units and use the lifting holes on the bottom board. Put a cushion block at the places of contact in case of damage.

Water Pipeline Connection

When connecting the water pipeline, you cannot exchange the user side pipeline with the heat source side pipeline. The unit’s user side and heat source side direction should be in accordance with the direction as marked on the units. Water pipeline resistance out of the units should as minimal as possible. The pipeline must be clean to prevent jamming. Before packing the insulation layer, a leakage test should be conducted. Adopt the same diameter water pipe as mentioned in the user guide for inlet and outlet connection pipe out of the units. Ensure that the pipeline is full of water and has fine moisture measures when the unit is at work. The Expansion water tank should be equipped at the highest part of the water pipeline. The water surface of the expansion water tank should be 0.5m or higher than the highest point of water pipeline.
Choose the insulation water tank with suitable volume according to the units heating and cooling capacity and ensure the insulation of pipeline out of the water tank.
If the units have no water pump equipped, please choose the proper water pump according to the units water flow volume on the user guide, making sure the water flow volume satisfies the units requirement. There should be hose connection equipment between the water pump and units. If the water pump is installed outdoors, there should be water-proof and anti-freezing equipment. An automatic exhaust air valve should be equipped at the highest point of the water pipeline in case of air detention in the pipe; Drainage valve should be equipped at the lowest point of the water pipeline, so it can be convenient for maintenance and drainage. A Y-type filter should be installed at the circular water pump inlet port of the user side and heat source side in case that impurities may damage the units. The Y-type filter should be detachable for cleansing and maintenance. Softened water can be better for circular water. The connection of the water inlet and outlet should be flexible to reduce vibration.  Drain out the water in the pipeline when you will not use the units for a long time in case of freezing. Do not change the set return water temperature and water tank insulation temperature.
Thermometer and water pressure gauge should be equipped at the units water inlet and outlet port for checking. User side water should be tap water and the hardness should be less than 20. If not, install an electric hydro treater at the tap water side.

Power Supply Connection
  •  Open the front panel and open the power supply access.
  • The power supply must go through the wire access and be connected to the power supply terminals in the controlling box. Then connect the 3-signal wire plugs of the wire controller and main controller.
  •  If an external water pump is required, please insert the power supply wire into the wire access and connect it to the water pump terminals.
  • If an additional auxiliary heater is needed to be controlled by the heat pump controller, the relay (or power) of the aux-heater must be connected to the relevant output of the controller.
Trial Operation

Inspection before trial running

  •  Check the indoor unit, make sure that the pipe connection is done correctly, and the relevant valves are open.
  •  Check the water loop to ensure that the water inside of the expansion tank is filled to an appropriate level, the water supply is working and that the water loop is full of water & free of trapped air. Make sure there is good insulation for the water pipe.
  •  Check the electrical wiring. Make sure that the power voltage is normal, the screws are fastened, the wiring is made in line with the diagram and that the earthing is connected.
  • Check that the heat pump includes all the screws and components, and that they are in good order. When powering the unit on, review the indicator on the controller to see if there is any indication of failure. The gas gauge can be connected to the check valve to see the high pressure (or low pressure) of the system during trial running.

Trial Operation

  • Start the heat pump by pressing the ON/OFF key on the controller. Check whether the water pump is running, if it runs normally there will be 0.2MPa on the water pressure meter.
  •  When the water pump has ran for a minute, the compressor will start. Listen for any strange sounds from the compressor, if an abnormal sound occurs please stop the unit and check the compressor. If the compressor runs well, please look for the pressure meter of the refrigerant.
  •  Check whether the power input and running current is in line with the manual. If not, please stop and check.
  •  Adjust the valved on the water loop to make sure that the hot (cool) water supply to each door is good and meets the requirements of heating (or cooling).
  •  Review whether the outlet water temperature is stable.
  •  The parameters of the controller are set by the factory, the user cannot change these themselves.

Operation

Main Controller Interface

EVOHEAT Evo Ultra Series 11

Button Name Function
ON/OFF Press this button to start up/shut off the unit, cancel current

operation or go back to previous interface.
| HELP| Press this button to check button function of system state.
| MODE| Press this button to change the current mode, page up or confirm current operation.
| CLOCK| Press this button to set the clock or turn the timer on/off.
| UP| Press this key to select the upwards option or increase the parameter value.
| DOWN| Press this key to select the downwards option or decrease the parameter value.

Functions of the Controller

Using the HELP Button
You can use at any interface and it will explain the buttons & functions of the current interface. To exit the help interface, simply press the ON/OFF button.
EXAMPLE: Press HELP at the Main Interface
EVOHEAT Evo Ultra Series 18 Starting & Shutting Down
To turn on/off the unit, press the ON/OFF button for 1 second. The screen will display as following for each state:
EVOHEAT Evo Ultra Series 19 Switching Modes
At the main interface, you can switch between the modes of cooling, economic heating, heating & rapid heating by pressing  . Example: Switch from Cooling mode to Economic Heating
EVOHEAT Evo Ultra Series 20 Note:
The operation of mode is invalid if the unit you purchase is heating only or cooling only.
System State Checking
At any interface you can enter the system working state by pressing TWICE, then using the UP and Down arrow keys to highlight the required parameter, then press to enter. To exit, press the ON/OFF button
EVOHEAT Evo Ultra Series 21 Changing Temperature
At the main interface, press the UP or DOWN key to adjust the temperature setting as desired. Once complete, press the  button to save the settings and exit. Press the ON/OFF button to exit without saving settings. Refer to the Parameter Table to set relevant temperature.
EVOHEAT Evo Ultra Series 22 Clock Setting
At the main interface press to enter the clock setting interface. Select the parameter you wish to change and press to make the parameter begin flashing which indicates it can be changed. Press the UP or DOWN keys to change the parameter value, then press to save. Press the ON/OFF button to return to the main menu.
EVOHEAT Evo Ultra Series 23 Note:
If there is no operation after 10 seconds, it will return to the main menu and changes will automatically be saved. To change the date, the same process is followed.
Timer Settings
Four timer periods can be set according to your needs. From the main interface, press to enter the timer setting, press DOWN to select Timer, then press to enter the timer setting interface. The process is much the same as adjusting the Clock settings. To cancel and return to the previous menu, press the ON/OFF button.
Timer
Each timer has an ON value when the unit will turn on an OFF value when the unit will turn off (00:00-00:00).
These timers are required for the Daily Timers & Temperature Timers to work.
Example: TIMER1 Unit is on at 7:30am – and off at 10pm
EVOHEAT Evo Ultra Series 24 Daily Timer
The Daily Timer allows you to apply your timers to particular days of the week.

  • OFF means that the unit will not run on that day.
  •  ON means the system will be running for a whole day.
  •  Applying one timer will have the unit run from A-B.
  • Applying two timers will mean the unit runs from A-B, then C-D.

Example:
Setting the operation on Friday to run two different timers.
If the Timer2 were 8am-10am & Timer 3 were 1pm-5pm, the unit would operate or stop accordingly.
EVOHEAT Evo Ultra Series 25 Keyboard Lock
To lock the controller after adjusting settings, at the main interface hold the ON/OFF button for 5 seconds. The keyboard will be locked and display a lock symbol on the screen. To unlock the screen, hold the ON/OFF button for 5 seconds. Note: If the unit is in alarm state, the keyboard lock is automatically removed.
EVOHEAT Evo Ultra Series 26 Malfunction Display
If a fault occurs, there will be a malfunction code showing on the controller screen. Refer to the Malfunction Table (9.9) to find out the failure cause and solutions.
EVOHEAT Evo Ultra Series 27

Troubleshooting

Fault Table
Malfunction Display Reason Resolution
Power On
Normal Working
Inlet temp. sensor failure P01 The temp. sensor is short circuit or broken

Check or change the temp sensor
Outlet temp. sensor failure| P02| The temp. sensor is short circuit or broken| Check or change the temp sensor
Ambient temp. failure| P04| The temp. sensor is short circuit or broken| Check or change the temp sensor
System 1/2/3/4 Coil temp. failure| P15(system1), P25(system2),

P35(system3), P45(system4)

| The temp. sensor is short circuit or broken| Check or change the temp

sensor

System 1/2/3/4 absorb temp. failure| P17(system1), P27(system2), P37(system3), P47(system4)| The temp. sensor is short circuit or broken| Check or change the temp sensor
System 1/2/3/4 anti- freeze temp. failure| P19(system1), P29(system2), P39(system3), P49(system4)| The temp. sensor is short circuit or broken| Check or change the temp sensor
Using side system 1/2/3/4 Anti-freeze temp. failure| P191(system1), P291(system2), P391(system3), P491(system4)| The temp. sensor is short circuit or broken| Check or change the temp sensor
System 1/2/3/4 coil inlet temp. failure| P151(system1), P251(system2),

P351(system3), P451(system4)

| The temp. sensor is short

circuit or broken

| Check or change the temp sensor
System 1/2/3/4 high pressure protection| E11(system1), E21(system2), P31(system3), E41(system4)| The high-pressure switch is broken| Check the pressure switch and cold circuit
System 1/2/3/4 low pressure protection| E12(system1), E22(system2),
E32(system3), E42(system4)| The low-pressure switch is broken| Check the pressure switch and cold circuit
Water flow failure| E03| No water/little water in water system| Check the pipe waterflow and water pump
Electric-heater overheat protection| E04| Electrical-heat is overheat| Check or change electrical-heat
Water inlet and outlet temp. too big| E06| Water flow is not enough and low differential pressure| Check the pipe waterflow and whether water system is jammed or not
System 1/2/3/4 anti- freeze protection| E06| Water flow is not enough and low differential pressure| Check the pipe waterflow and whether water system is jammed or not
System 1/2/3/4 source side anti-freeze protection| E17(system1), E27(system2), E37(system3), E47(system4)| Water flow is not enough| Check the pipe waterflow and whether water system is jammed or not
System 1/2/3/4 using side anti-freeze protection| E171(system1), E271(system2), E371(system3), E471(system4)| Water flow is not enough| Check the pipe waterflow and whether water system is jammed or not
Anti—freeze protect level 1| E19| The ambient temp. is low| /
Anti—freeze protect level 2| E29| The ambient temp. is low| /
System protection| E05| The protection system is failure| Check each protection point of the system
Communication Failure| E08| Communication failure between wire controller and mainboard| Check the wire connection between remote wire controller and main board

BHB10 Fault Table
Malfunction Display Cause Solution
System 1 exhaust temp. failure P181 The sensor is open or short circuited

Check or change the sensor
System 2 exhaust temp. failure| P281| The sensor is open or short circuited| Check or change the sensor
Ambient temp. sensor failure| P04| The sensor is open or short circuited| Check or change the sensor
System 1 anti-freeze temp. failure| E171| The sensor is open or short circuited| Check or change the sensor
System 2 anti-freeze temp. failure| E271| The sensor is open or short circuited| Check or change the sensor
System 1 economizer inlet temp. failure| P101| The sensor is open or short circuited| Check or change the sensor
System 2 economizer inlet temp. failure| P201| The sensor is open or short circuited| Check or change the sensor
System 1 economizer outlet temp. failure| P102| The sensor is open or short circuited| Check or change the sensor
System 2 economizer outlet temp. failure| P202| The sensor is open or short circuited| Check or change the sensor
System anti-freeze protection| P19| Water flow volume not enough| Check the flow volume, see if water is jammed or not
System 2 anti-freeze protection| P29| Water flow volume not enough| Check the flow volume, see if water is jammed or not
Communication failure| E08| Communication failure between remote wire controller and main board| Check the wire connection between remote wire controller and main board
System 1 current protection| E151| Current through compressor too heavy| Check through the power supply for compressor or short circuit
System 2 current protection| E251| Current through compressor too heavy| Check through the power supply for compressor or short circuit
System 1 exhaust high temp. protection| P182| Compressor exhaust temp. too

high

| Check through the refrigerant system
System 2 exhaust high temp. protection| P282| Compressor exhaust temp. too high| Check through the refrigerant system

INDICATOR DISPLAY

Fault

|

Indicator

---|---

System 1

| 1 Flashes 1 OFF
System 2|

2 Flash 1 OFF

Ambient Temp.

|

3 Flash 1 OFF

Possible Failures & Solutions

Failure

| Possible Causes for the Failure|

Solutions

---|---|---
Heat pump cannot be started| Wrong power supply| Shut off the power and check power supply
Power supply cable loose| Check power cable and make right connection
Circuit breaker open| Check for the cause and replace the fuse or circuit breaker
Water pump is running with high noise or without heater| Lack of water in the piping| Check the water supply and charge water to the piping
Too much air in the water loop| Discharge the air in the water loop
Water valves closed| Open the valves in the water loop
Dirt and blockage on the water filter| Clean the water filter
Heat pump capacity is low, compressor does not stop| Lack of refrigerant| Check for the gas leakage and recharge the refrigerant
Bad insulation on water pipe| Make good insulation on water pipe
Low heat exchange rate on air side exchanger| Clean the air side heat exchanger
Lack of water flow| Clean the water filter
High compressor exhaust| Too much refrigerant| Discharge the redundant gas
Low heat exchange rate on air side exchanger| Clean the air side heat exchanger
Low pressure problem of the system| Lack of gas| Check the gas leakage and recharge freon
Block on filter or capillary| Replace filter or capillary
Lack of water flow| Clean the water filter and discharge the air in water loop
Compressor do not run| Power supply failure| Check off the power supply
Compressor contactor broken| Replace compressor contractor
Power cable loose| Tighten the power cable
Protection on compressor| Check the compressor exhaust temp
Wrong setting on return water temp| Reset the return water temp
Lack of water flow| Clean the water filter and discharge the air in water loop
High noise of compressor| Liquid refrigerant goes into compressor| Bad evaporation, check the cause for bad evaporation and fix
Compressor failure| Use new compressor
Fan do not run| Failure on fan relay| Replace the fan relay
Fan motor broken| Replace fan motor
The compressor runs but heat pump has no heating or cooling capacity| No gas in the heat pump| Check system leakage and recharge refrigerant
Heat exchanger broken| Find out the cause and replace the heat exchanger
Compressor failure| Replace compressor
Low outlet water temperature| Low water flow rate| Clean the water filter and discharge the air in water loop
Low setting for the desired water temp| Reset the desired water temperature
Low water flow protection| Lack of water in the system| Clean the water filter and discharge the air in water loop
Failure on flow switch| Replace the flow switch

Appendix

Parameter List

Meaning

| Default| Remarks
---|---|---
Set-point of cooling target temp.| 12?|

Adjustable

Set-point of heating target temp.

| 60°C| Adjustable
Set-point of auto mode target temp.| 27°C|

Adjustable

Cable Specifications

Single Phase Unit

Nameplate max. current| Phase Line| GND Line| Breaker| Creepage Protector| Signal Line
---|---|---|---|---|---

No More than 10A

| 2 x 1.5mm2| 1.5mm2| 20A| 30mA less than 0.1 sec| n x 0.5mm 2
10~16A| 2 x 2.5mm2| 2.5mm2|

32A

16~25A

| 2 x 4mm2| 4mm2| 40A
25~32A| 2 x 6mm2| 6mm2|

40A

32~40A

| 2 x 10mm2| 10mm2| 63A
40~63A| 2 x 16mm2| 16mm2|

80A

63~75A

| 2 x 25mm2| 25mm2| 100A
75~101A| 2 x 25mm2| 25mm2|

125A

101~123A

| 2 x 35mm2| 35mm2| 160A
123~148A| 2 x 50mm2| 50mm2|

225A

148~186A

| 2 x 70mm2| 70mm2| 250A
186~224A| 2 x 95mm2| 95mm2|

280A

Three Phase Unit

Nameplate max. current

| Phase Line| GND Line| Zero Line| Breaker| Creepage Protector|

Signal Line

---|---|---|---|---|---|---

No More than 10A

| 3 x 1.5mm2| 1.5mm2| 1.5mm2| 20A|

30mA less than 0.1 sec

|

n x 0.5mm2

10~16A| 3 x 2.5mm2| 2.5mm2| 2.5mm2|

32A

16~25A

| 3 x 4mm2| 4mm2| 4mm2| 40A
25~32A| 3 x 6mm2| 6mm2| 6mm2|

40A

32~40A

| 3 x 10mm2| 10mm2| 10mm2| 63A
40~63A| 3 x 16mm2| 10mm2| 16mm2|

80A

63~75A

| 3 x 25mm2| 16mm2| 25mm2| 100A
75~101A| 3 x 25mm2| 16mm2| 25mm2|

125A

101~123A

| 3 x 35mm2| 16mm2| 35mm2| 160A
123~148A| 3 x 50mm2| 25mm2| 50mm2|

225A

148~186A

|

3 x 70mm2

| 35mm2| 70mm2| 250A
186~224A| 3 x 95mm2| 50mm2| 95mm2|

280A

  • The above specification is applicable for 3-core cable wire made of copper and is applicable for air laying cable wire.
  • The above max. current is the carrying capacity at ambient temperature 25C;
  • If the unit is installed outdoors, use a UV resistant cable.
  • The above specification is for reference only. For specific wire and breaker models please check the corresponding factory standard and actual installation requirement
PCB Connection

EVOHEAT Evo Ultra Series 28
EVOHEAT Evo Ultra Series 28

|

| Meaning| | |

Meaning

---|---|---|---|---|---

1

| AC-L| Live line|

22

| DI 08| Electric heater overload protection input

2

| AN-N| Null line|

23

| DI 09| COMP 1 overload protection switch input

3

| RO 01| Compressor 1 output (220VAC)|

24

| DI 10| COMP 2 overload protection switch input

4

| RO 02| Compressor 2 output (220VAC)|

25

| DI 11| system protection input

5

| RO 03| FM High speed output (220VAC)|

26

| DI 12| Emergency switch input

6

| RO 04| FM low speed output (220VAC)|

27

| AI 01| Water input temperature input

7

| RO 05| Water pump output (220VAC)|

28

| AI 02| Water output temperature input

8

| RO 06| 4-way valve output (220VAC)|

29

| AI 03| System 1 coil temperature input

9

| RO 07| Electric heater output (220VAC)|

30

| AI 04| System 2 coil temperature input

10

| RO 08| Spray valve output (220VAC)|

31

| AI 05| Ambient temperature input

11

| RO 09| Alarm/anti-freezing heater output (220VAC)|

32

| AI 06| System 1 antifreeze temperature input

12

| DI/DO 1| Mode indicator output|

33

| AI 07| System 2 antifreeze temperature input

13

| DI/ DO 2| Flow volume input|

34

| AI 08| System 1 suction temperature input

14

| DI 01| Emergency switch input|

35

| AI 09| System 2 suction temperature input

15

| DI 02| System 1. High pressure protection input|

36

| AI 10| No Use

16

| DI 03| System 1. Low pressure protection input|

37

| AI 11 (50K)| System 1 exhaust temperature input

17

| DI 04| System 2. High pressure protection input|

38

| AI 12 (50K)| System 2 exhaust temperature input

18

| DI 05| System 2. Low pressure protection input|

39

| CN1| System 2 electric expansion valve output

19

| NET GND 12V| Connect to the remote controller|

40

| CN6| System 1 electric expansion valve output

20

| DI 06| Phase sequence protection/input|

41

| CN4| Program download port

21

| DI 07| Water flow switch protection input|

42

| CN5| RS485 port

EVOHEAT Evo Ultra Series 30

No.

| Symbol|

Meaning

---|---|---

1

|

RO01

| System 1 magnetic valve outlet (220-230VAC)

2

|

RO02

| System 2 magnetic valve outlet (220-230VAC)

3

|

RO03

| System 1 alert outlet (220-230VAC)

4

|

RO04

| System 2 alert outlet (220-230VAC)

5

|

CC01

| System 1 magnetic valve inlet (220-230VAC)
6|

CC02

| System 2 magnetic valve inlet (220-230VAC)

7

| CC03|

System 1 alert inlet (220-230VAC)

8|

CC04

| System 2 alert inlet (220-230VAC)

9

|

NET GND 12V

| Wire controller

10

|

DI01 GND

| Mode/communication

11

|

AI01 GND

| System 1 anti-freeze temp. (input)

12

|

AI02 GND

| System 2 anti-freeze temp. (input)

13

|

AI03 GND

| System 1 economizer inlet temp. failure (input)

14

|

AI04 GND

| System 1 economizer outlet temp. failure (input)

15

|

AI05 GND

| System 2 economizer inlet temp. failure (input)

16

|

AI06 GND

| System 2 economizer outlet temp. failure (input)

17

|

AI07 GND

| System 1 exhaust temp. (input)

18

|

AI08 GND

| System 2 exhaust temp. (input)

19

|

AI09 GND

| Ambient temp. (input)

Automatic Water Filling Valve

When the automatic filled-water valve is installed, the arrowhead orientation of inlet water must accord with the orientation of the valve.
Automatic filled-water has been adjusted in advance to 1.5ba.
If readjusting the pressure of inlet water, operate as follows:

  • Open the Screw Cap ( C )
  •  If reducing the pressure of water supply, unscrew the pressure to adjust the screw (B)
  •  If increasing the pressure of water supply, screw down the pressure to adjust the screw (B)

When the system needs to be filled with water at first, rest the handle (A) of filled-water. Then the handle (A) can return (close) when the system is full of water.
Automatic filled-water valve needs periodic cleaning. When you must close the tap, unscrew the plug (D), remove the inside filter net. Reassemble after cleaning.
NOTE:
There are two connections for water pressure meters in the central section of automatic filled-water, where the water pressure meter can be connected directly and display the set pressure. The screw cap ( C ) must be tweaked after adjusting the filled-water pressure.
EVOHEAT Evo Ultra Series 31

Maintenance

DO I NEED TO GET MY UNIT SERVICED?
It is recommended that you get your Evo Heat unit serviced once a year by your local certified air conditioning or refrigeration technician. If your unit is located in a coastal area, more frequent maintenance may be necessary.
During the service, they will check the operational pressures of the refrigeration system and give the unit and fins a good clean to ensure maximum performance.
DO WE HAVE RECOMMENDED SERVICE AGENTS?
Evo Heat have a large database of recommended service agents. Please contact Evo Heat tech support on 1300 859 933 for your local service agent details.
SHOULD I CHECK MY UNIT REGULARLY?
We recommend you check your unit regularly to avoid potential issues and damage to your heat pump.

  • Always remember to check the water system filling equipment and air exhaust equipment in case of water interruption or air entering the system; Make sure to clean the water filter in case of blockages. The system will check the water pump every 72hrs at standby status.
  • Wash the water circuit system in the unit every 6 months; Remember to check the working status of every component and check whether the working pressure is in normal range or not. If anything is abnormal, repair or replace. Remember to check the power and wire connection. If anything is abnormal, repair or replace.
  • If the unit is not to be used for an extended period of time, drain the water in the water pump and water circuit from the bottom water exit so it does not freeze. If you want to start the unit again, fill water to the system and conduct a complete inspection before start-up.
  • If you are not using the unit continuously, please do not turn off the power in case of spare parts freezing. Evo Heat will not take any responsibility if any damage occurs because of this mis-operation.

Warranty

  1. Warranty terms are from date of purchase.
  2. This warranty excludes any defect or injury caused by or resulting from misuse, abuse, neglect, accidental damage, improper voltage, vermin infestation, incompetent installation, any fault not attributable to faulty manufacture or parts, any modifications which affect the reliability or performance of the unit.
  3.  This warranty does not cover the following:
    • Natural Disasters (hail, lightening, flood, fire etc.)
    • Rust or damage to paintwork caused by a corrosive atmosphere
    • When serviced by an unauthorized person without the permission of Evo Industries
    • When a unit is installed by an unqualified person
    • Where a unit is incorrectly installed
    • When failure occurs due to improper or faulty installation
    • Failure due to improper maintenance (refer Operating Instructions)
    • No Fault Found’ service calls where the perceived problem is explained within the
    • Costs associated with delivery, handling, freighting, or damage to the product in transit.
  4. If warranty service is required you should:
    • contact Evo Industries Australia on 1300 859 933 or via our Contact page on our web site
    • provide a copy of your receipt as proof of purchase
    • have completed the online warranty registration or provide a completed warranty card.
  5. Onsite technical service is available within the normal operating area of your Evo Industries authorized Service Centre. Service outside this area will incur a traveling fee.
  6. Unless otherwise specified to the purchaser, the benefits conferred by this express warranty and additional to all other conditions, warranties, rights and remedies expressed or implied by the Trade Practices Act 1974 and similar consumer protection provisions contained in legislation of the States and Territories and all other obligations and liabilities on the part of the manufacturer or supplier and nothing contained herein shall restrict or modify such rights, remedies, obligations or liabilities.
Warranty Registration

Evo Heat highly recommend customers to complete their warranty details online to ensure efficient warranty claim processing.
To register your warranty, scan our QR Code or head to our website and fill in the Warranty Registration Form: https://evoheat.com.au/warranty- registration/

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals