EVOHEAT Evo Ultra Commercial Hot Water Heat Pump User Manual

June 12, 2024
EVOHEAT

EVOHEAT Evo Ultra Commercial Hot Water Heat Pump

EVOHEAT-Evo-Ultra-Commercial-Hot-Water-Heat-Pump-PRODUCT-
IMG

Introduction

  • This manual contains information relating to the installation, troubleshooting, operation, and maintenance of this EvoHeat unit. Instructions in this manual must always be followed. Failure to comply with these recommendations will invalidate the warranty.
  • Should you have any questions or require technical support, call the EvoHeat office on 1300 859 933 to speak to our team.
  • The data and information contained in this manual is correct at the time of publishing and is subject to change without notice. For the most up to date manual, contact EvoHeat directly.
  • The Evo Ultra is a water to water heat pump that is the perfect solution in applications where chillers and cooling towers are being used for temperature control. When installed in line with the chiller, the Evo Ultra can capture rejected waste from the chiller return lines and utilise this heat to provide FREE HOT WATER!

TECHNICAL DATA

|  | Evo Ultra 64| Evo Ultra 129| Evo Ultra 240|
---|---|---|---|---|---

Evaporator Side

| Heating Capacity| kW| 67.1| 134.2| 222|
Cooling Capacity| kW| 50.9| 101.9| 160|
20°C/15°C|
Condenser Side| Power Input| kW| 15.8| 31.6| 59.5|
45°C/55°C|
C.O.P|  | 4.24| 4.24| 3.7|

Evaporator Side

| Heating Capacity| kW| 58.6| 115.6| 190|
Cooling Capacity|  | 40| 75.6| 114.5|
20°C/15°C|
Condenser Side| Power Input| kW| 19.6| 41.7| 78.5|
65°C/75°C|
C.O.P|  | 3| 2.77| 2.42|
Voltage/Phase|  | 380-415/3/50| 380-415/3/50| 380-415/3/50|
Max. Running Current| A| 50| 90| 180|
Max. Power Input| kW| 26| 46| 98|
Noise| dB(A)| 68| 69| 71|
Compressor Type|  | Copeland Scroll ZW Series R134a EVI Scroll|
Compressor No.|  | 2| 4| 4|
Evaporator Water Flow| m 3 /h| 7| 20| 28|
Condenser Water Flow| m 3 /h| 5.1| 18.2| 38|
Refrigerant Type|  | R134a| R134a| R134a|
Max. Outlet Water Temp.| ° C| 80| 80| 80|
Net Weight| kg| 441| 866| 1050|
Net Dimensions (L/W/H)| mm| 1172 / 900 / 1365| 1600 / 1130 / 1500| 2030 / 1250 / 1610|

  • Heating: Heat source side: water inlet/outlet temperature: 20°C/15°C User side water inlet/outlet temperature: 65°C/75°C
  • When the units work between 55-85°C, make sure the low-pressure range is between 0.27-0.65MPa and the evaporating temperature is between 7-30°C. The above data is for reference only, specific data is subject to the product nameplate

Unit Dimensions

EVOHEAT-Evo-Ultra-Commercial-Hot-Water-Heat-Pump-FIG-1

Unit: mm| A (L)| B (W)| C (H)| D| E| F| G| H
---|---|---|---|---|---|---|---|---
Evo Ultra 64| 1172| 900| 1365| 850| 850| 812| 750| 680
Evo Ultra 129| 1600| 1130| 1500| 1080| 1050| 1000| 800| 410
Evo Ultra 240| 2030| 1250| 1610| 1986| 1490| 350| 245|

Safety Instructions

Installation, repair, or relocations must only be done by a fully qualified technician. If done incorrectly there is a number of hazards that can occur including fire, electric shock, water leakage and injury.

  • A circuit breaker must be installed for the unit.
  • Ensure the unit has a good power connection and earthing to avoid the risk of electrical shocks.
  • Maintenance and operation must be carried out according to the recommended time and frequencies, as stated in this manual.
  • The unit must be stored in a room without any continuously operating ignition sources (for example: open flames, an operating gas appliance)
  • Do not pierce or burn the unit.
  • If the supply cord is damaged, it must be replaced by a qualified service agent.
  • This appliance must be installed in accordance with national wiring regulations.
  • Before obtaining access to terminals all supply circuits must be disconnected.
  • The unit is equipped with an over-load protection system. After a previous stoppage, the unit will not start for at least 3 minutes.
  • For unit cleaning or maintenance, switch off and disconnect the power of the unit.
  • Do not install the unit near flammable gas or spray flammable substances near it.
  • Ensure the heat pump is installed on a strong and stable platform.
  • If the supply cord is damaged, it must be replaced.
  • Use genuine standard spare parts only.

WARNING

  • THIS PRODUCT CONTAINS A BUTTON BATTERY
  • If swallowed, a lithium button battery can cause severe or fatal injuries within 2 hours.
  • Keep batteries out of reach of children.
  • If you think batteries may have been swallowed or placed inside any part of the body, seek immediate medical attention.

Installation

System Installation

  • This model can be installed on a concrete base with expansion bolts or installed on the ground or roof by a steel bracket with rubber cushion. Make sure that the units are horizontally placed.
  • The units should be installed at a place convenient for installation and maintenance.
  • The units should install shock-absorbing devices in case of the shock transferring to the building.
  • For transit, use four slings longer than 8m when moving the units and use the lifting holes on the bottom board. Put a cushion block at the places of contact in case of damage.

Plumbing

  • When connecting the water pipeline, you cannot exchange the user side pipeline with the heat source side pipeline. The unit’s user side and heat source side direction should be in accordance with the direction as marked on the units. Water pipeline resistance out of the units should as minimal as possible.
  • The pipeline must be clean to prevent jamming. Before packing the insulation layer, a leakage test should be conducted.
  • Adopt the same diameter water pipe as mentioned in the user guide for inlet and outlet connection pipe out of the units. Ensure that the pipeline is full of water and has fine moisture measures when the unit is at work.
  • The Expansion water tank should be equipped at the highest part of the water pipeline. The water surface of the expansion water tank should be 0.5m or higher than the highest point of water pipeline.
  • Choose the insulation water tank with suitable volume according to the units heating and cooling capacity and ensure the insulation of pipeline out of the water tank.
  • If the units have no water pump equipped, please choose the proper water pump according to the units water flow volume on the user guide, making sure the water flow volume satisfies the units requirement. There should be hose connection equipment between the water pump and units. If the water pump is installed outdoors, there should be water-proof and anti-freezing equipment.
  • An automatic exhaust air valve should be equipped at the highest point of the water pipeline in case of air detention in the pipe; Drainage valve should be equipped at the lowest point of the water pipeline, so it can be convenient for maintenance and drainage.
  • A Y-type filter should be installed at the circular water pump inlet port of the user side and heat source side in case that impurities may damage the units. The Y-type filter should be detachable for cleansing and maintenance.
  • Softened water can be better for circular water.
  • The connection of the water inlet and outlet should be flexible to reduce vibration.
  • Drain out the water in the pipeline when you will not use the units for a long time in case of freezing.
  • Do not change the set return water temperature and water tank insulation temperature.
  • Thermometer and water pressure gauge should be equipped at the units water inlet and outlet port for checking.
  • User side water should be tap water and the hardness should be less than 20. If not, install an electric hydro treater at the tap water side.

Electrical Connection

IMPORTANT: Always use a qualified Electrician to perform any electrical work. A licensed electrician must read the information before connecting.
Ensure the power cable and circuit breaker are of a suitable size for the heater being installed. Also check that there is adequate voltage and current available at the heater connection to run the unit.

  • Open the front panel and open the power supply access.
  • The power supply must go through the wire access and be connected to the power supply terminals in the controlling box. Then connect the 3-signal wire plugs of the wire controller and main controller.
  • If an external water pump is required, please insert the power supply wire into the wire access and connect it to the water pump terminals.
  • If an additional auxiliary heater is needed to be controlled by the heat pump controller, the relay (or power) of the aux-heater must be connected to the relevant output of the controller.

Initial Start-up

Pre-Start Inspection

  • Check the indoor unit, make sure that the pipe connection is done correctly, and the relevant valves are open.
  • Check the water loop to ensure that the water inside of the expansion tank is filled to an appropriate level, the water supply is working and that the water loop is full of water & free of trapped air. Make sure there is good insulation for the water pipe.
  • Check the electrical wiring. Make sure that the power voltage is normal, the screws are fastened, the wiring is made in line with the diagram and that the earthing is connected.
  • Check that the heat pump includes all the screws and components, and that they are in good order. When powering the unit on, review the indicator on the controller to see if there is any indication of failure. The gas gauge can be connected to the check valve to see the high pressure (or low pressure) of the system during trial running.

Trial Operation

  • Start the heat pump by pressing the ON/OFF key on the controller. Check whether the water pump is running, if it runs normally there will be 0.2MPa on the water pressure meter.
  • When the water pump has ran for a minute, the compressor will start. Listen for any strange sounds from the compressor, if an abnormal sound occurs please stop the unit and check the compressor. If the compressor runs well, please look for the pressure meter of the refrigerant.
  • Check whether the power input and running current is in line with the manual. If not, please stop and check.
  • Adjust the valved on the water loop to make sure that the hot (cool) water supply to each door is good and meets the requirements of heating (or cooling).
  • Review whether the outlet water temperature is stable.
  • The parameters of the controller are set by the factory, the user cannot change these themselves.

Operation

The Controller

Power Turn the unit on or off
Setpoint Set the target temperature
Mode Select heating or cooling mode
Lock Lock or unlock the screen

Timer

| Enter the timer setting menu (Temp Timer, Power Timer)
Setting| Enter function menu (Status, Parameter, Failures & Time)
| The target temperature of inlet water
| Unit’s set date & time
Display Circle| Blue: Cooling mode, Red: Heating Mode, Grey: Off

Icons will appear at the top right of the screen indicating certain functions that are enabled, or if there has been an error with the system.

  • Temp Timer Function
  • Power Timer Mode
  • Screen Lock
  • Failure Alarm (The icon will blink until the failure is resolved)

Operating Functions

On/Off
From the main menu, simply press the ‘Power’ button to turn the unit on or off.

Mode Selection

  • From the main menu, pressing the ‘Mode’ button will allow you to select either heating or cooling mode. The status bar (bottom of the screen) will display the unit’s current operating state.
  • The display circle will appear as red for heating, or blue for cooling. If the unit is off, it will simply be grey.

Setting the Target Temperature

  • To adjust the target temperature value, first choose a running mode (heating or cooling), then press the ‘Setpoint’ button to enter the parameter setting screen.
  • Enter the required parameter according to the effective range which is displayed at the bottom of the screen.

Locking the Screen

  • From the main menu, press the ‘Lock’ button to lock the controller screen and prevent unauthorised people accessing the controls.
  • When the screen is locked a small lock symbol will appear on the top right of the main menu.
  • To unlock the screen, press the ‘Lock’ button again and enter the password 22 which will unlock the screen and remove the lock symbol.

Setting a Timer

EVOHEAT-Evo-Ultra-Commercial-Hot-Water-Heat-Pump-FIG-7

  • After pressing the ‘Timer button from the main interface, select from Temp Timer or Power Timer.

Temperature Timers

  • This function enabled time-sharing temperature control, which is two segments of staggered peak temperature control, and allows the target temperature of two segments of different time periods to be set according to different modes.
  • Press (23) to select from cooling or heating mode, then enter the start time, ending time and the target temperature setpoint value (24). Press (25) to enable or disable the settings.

Power Timer

  • This function allows you to set the opening time of the unit for each day of the week.
  • Press (26) to select the day of the week, then (27) to select AM or PM, after this press (28) to select the time, and finally select (29) to enable or turn off the setting.

Settings

EVOHEAT-Evo-Ultra-Commercial-Hot-Water-Heat-Pump-FIG-8

  • After pressing the ‘Setting’ button on the main menu, you can select from a range of functions.

Status

  • Press Status (30) to choose from Running Status or Unit Status.
  • Running Status See below image.

Unit Status

  • Enter the password 22 to inquire the unit status parameter. Press one of the 4 buttons to inquire relevant parameters.

EVOHEAT-Evo-Ultra-Commercial-Hot-Water-Heat-Pump-FIG-9

Parameters

  • After pressing the parameter button (31) from the settings menu, enter the password 22 to jump to the Installer Parameter interface for inquiring about relevant parameters.

EVOHEAT-Evo-Ultra-Commercial-Hot-Water-Heat-Pump-
FIG-10

Failure

  • When a failure is present, the red failure alarm will be flashing on the main menu. First press ‘Settings’ then ‘Failure’ to view the failure records.
  • Once maintenance has been completed, press the ‘clear’ button the delete the failure history.

Time

  • To change the system’s date & time, click on the input field and enter the correct values. Press ‘save’ in the top right corner to save the settings.

EVOHEAT-Evo-Ultra-Commercial-Hot-Water-Heat-Pump-
FIG-11

Temperature Curve
Press (34) to view the inlet/outlet temperature curve.

  • This curve function records the water inlet outlet temperature.
  • Temperature data is collected every 5 minutes, and the 12 sets of temperature data are saved every hour. Timekeeping is made from the latest data saving. If the power is disrupted before all 12 data sets have been collected the data will not be saved.
  • Only curve for the electricity status is recorded, the outage status will not be saved.
  • The value of the abscissa indicates the time from the point on the curve to the current time point. The leftmost point on the first page (0 on the abscissa is the latest temperature record).
  • Temperature curve record is provided with power off memory function; in the case of a disturbed curve recording and display, when the unit is next powered on the wire controller will automatically clear the history curve record and the curve recording function will restore to a normal state.

Electric Heating
In the settings menu, the Electric Heating option will display as ‘OFF Electric Heating’. Make sure that the unit is firstly in heating mode, then press the electric heating button to head to its interface. Click the button to turn it on to activate the electric auxiliary heating mode. Turn off the function my tapping the button again.

EVOHEAT-Evo-Ultra-Commercial-Hot-Water-Heat-Pump-
FIG-12

Display Calibration

  • Enter the Unit status menu in the following orderMain Interface Setting Status Unit Status
  • The password it will ask for is: 22
  • Click the screen in the bottom left corner over 10 times within 4 seconds to bring up the display calibration interface.
  • Click the blank squares to check whether there are bad spots on the screen. Green spots are normal.
  • To exit, click the screen in the bottom right corner.

EVOHEAT-Evo-Ultra-Commercial-Hot-Water-Heat-Pump-
FIG-13

Troubleshooting

Fault Table

Protection/failure Codes Causes Removal methods
Communication Fault E08 Abnormal communication between the wired controller
and the main board Inspect whether the wired controller, the main board, and

the connection are reliable
The wired controller doesn’t Match the mainboard| E084|  |


DC Fan 1 Communication Fault

| ****

E081

| Communication of the speed regulation module 1 with the main

board is abnormal

| Check the speed regulation module 1 and the main board to see if connections are normal and reliable.
Syst1: High Pressure Prot.| E11| The high-voltage switch of the system is disconnected| Inspect System 1 voltage switch and refrigerating circuit for any failure
Syst2: High Pressure Prot.| E21| The high-voltage switch of the system is disconnected| Inspect System 2 voltage switch and refrigerating circuit for any failure
Syst1: Low-Pressure Prot.| E12| The low-voltage switch of the system is disconnected| Inspect System 1 voltage switch and refrigerating circuit for any failure
Syst2: Low-Pressure Prot.| E22| The low-voltage switch of the system is disconnected| Inspect System 2 voltage switch and refrigerating circuit for any failure


Water Flow Switch Prot.

| ****

E032

| The water system has little or no water| Inspect whether the water flow of the water pipe conforms to related requirements and check the water pump for any damages
Electric Heater Overheating| E04| The electric heating overheat protection switch is disconnected| Inspect whether the electric heating is under operation conditions of over 150℃ for a long time
Level 1Winter Antifreezing Prot.| E19| Excessively low environment temperature|
Level 2 Winter Antifreezing Prot.| E29| Excessively low environment temperature|
Syst1: User Side Antifreezing Prot.| ****

E171

| The water flow of the system is insufficient| Inspect whether the water flow of the water pipe conforms to related requirements and check the

water pump for any blockage

Syst2: User Side Antifreezing Prot.| ****

E271

| The water flow of the system is insufficient| Inspect whether the water flow of the water pipe conforms to related requirements and check the water pump for any blockage
Water(Out) High Temp Prot.| E09| Excessively high water outlet temperature|
Fan 1 Overload Prot.| E103| Fan 1 thermal overload| Check if fan 1 is running normally
Fan 2 Overload Prot.| E203| Fan 2 thermal overload| Check if fan 2 is running normally
Syst1: Exhaust Air High Temp Prot.| P182| The system compressor is overloaded| Inspect whether the operation of the System 1 compressor is normal
Syst2: Exhaust Air High Temp Prot.| P282| The system compressor is overloaded| Inspect whether the operation of the System 2 compressor is normal
Water (In/Out) Temp Excess Diff Prot.| ****

E06

| The water flow of the system is insufficient, and the pressure difference of the water system is small| Inspect whether the water flow of the water pipe conforms to related requirements and check the water pump for any blockage
Water(Out) Low Temp Prot.| E05| Excessively low water outlet temperature|


DC Fan 2 Communication Fault

| ****

E082

| Communication of the speed regulation module

2 with the main board is abnormal

| Check the speed regulation module 2 and the main board and if their connections are normal and reliable.
Fan 1 Overcurrent Speed Limit| E103| DC Fan 1 running current too large| Check if fan 1 is running normally
Fan 2 Overcurrent Speed Limit| E203| DC Fan 2 running current too large| Check if fan 2 is running normally
Syst1: High Pressure Prot. 3+| E11| The high-voltage switch of the system is disconnected| Inspect System 1 voltage switch and refrigerating circuit for any failure
Syst2: High Pressure Prot. 3+| E21| The high-voltage switch of the system is disconnected| Inspect System 2 voltage switch and refrigerating circuit for any failure
Syst1: Low-Pressure Prot. 3+| E12| The low-voltage switch of the system is disconnected| Inspect System 1 voltage switch and refrigerating circuit for any failure
Syst2: Low-Pressure Prot. 3+| E22| The low-voltage switch of the system is disconnected| Inspect System 2 voltage switch and refrigerating circuit for any failure
Protection/fault| Codes| Causes| Removal methods
---|---|---|---


Water Flow Switch Prot. 3+

| ****

E032

| The water system has no or only water| Inspect whether the water flow of the water pipe conforms to related requirements and check the

water pump for any damages

Electric Heater Overheating 3+| E04| The electric heating overheat protection switch is disconnected| Inspect whether the electric heating is under operation conditions of over 150℃ for a long time
Syst1: User Side Antifreezing Prot. 3+| ****

E171

| The water flow of the system is insufficient| Inspect whether the water flow of the water pipe conforms to related requirements and check the

water pump for any blockage

Syst2: User Side Antifreezing Prot. 3+| ****

E271

| The water flow of the system is insufficient| Inspect whether the water flow of the water pipe

conforms to related requirements and checks the water pump for any blockage

Water(Out) High Temp Prot. 3+| E09| Excessively high water outlet temperature|
Syst1: Exhaust Air High Temp Prot. 3+| P182| The system compressor is overloaded| Inspect whether the operation of the System 1 compressor is normal
Syst2: Exhaust Air High Temp Prot. 3+| P282| The system compressor is overloaded| Inspect whether the operation of the System 2 compressor is normal


Water (In/Out) Temp Excess Diff Prot. 3+

| ****

E06

| The water flow of the system is insufficient, and the pressure difference of the water system is

small

| Inspect whether the water flow of the water pipe conforms to related requirements and check the water pump for any blockage
Water(Out) Low Temp Prot. 3+| E05| Excessively low water outlet temperature|
Fan 1 Fault Prot.| E012| DC Fan 1 fault| Check if fan 1 is running normally
Fan 2 Fault Prot.| E022| DC Fan 2 fault| Check if fan 2 is running normally
Water (In) Sensor Fault| P01| Temperature sensor open or short-circuited| Check and replace the inlet water temperature sensor
Water (Out) Sensor Fault| P02| Temperature sensor open or short-circuited| Check and replace the outlet water temperature sensor
Syst1: Coil Sensor Fault| P15| Temperature sensor open or short-circuited| Check and replace the system 1 coil 1 temperature sensor
A.T. Sensor Fault| P04| Temperature sensor open or short-circuited| Check and replace the ambient temperature sensor
Syst1: Suction Temp Sensor Fault| P17| Temperature sensor open or short- circuited| Check and replace the system 1 suction temperature sensor
Syst1: Antifreezing Temp Sensor 1 Fault| P191| Temperature sensor open or short-circuited| Check and replace the system 1 antifreeze 1 temperature sensor
Syst2:Coil Sensor Fault| P25| Temperature sensor open or short-circuited| Check and replace the system 2 coil 1 temperature sensor
Syst1: Antifreezing Temp Sensor 2 Fault| P192| Temperature sensor open or short-circuited| Check and replace the system 1 antifreeze 2 temperature sensor
Syst2: Antifreezing Temp Sensor 2 Fault| P292| Temperature sensor open or short-circuited| Check and replace the system 2 antifreeze 2 temperature sensor
Syst1: EVI(In) Temp Sensor Fault| P101| Temperature sensor open or short- circuited| Check and replace the system 1 EVI inlet temperature sensor
Syst1: EVI(Out) Temp Sensor Fault| P102| Temperature sensor open or short- circuited| Check and replace the system 1 EVI outlet temperature sensor
Syst1: Exhaust Air Temp Sensor Fault| P181| Temperature sensor open or short- circuited| Check and replace the system 1 exhaust temperature sensor
Syst1: Low-Pressure Sensor Fault| PP11| The sensor is open or short-circuited| Check and replace system 1 low-pressure sensor
Syst2: Suction Temp Sensor Fault| P27| Temperature sensor open or short- circuited| Check and replace the system 2 suction temperature sensor
Syst2: Antifreezing Temp Sensor 1 Fault| P291| Temperature sensor open or short-circuited| Check and replace the system 2 antifreeze 1 temperature sensor
Syst1: High-Pressure Sensor Fault| PP12| The sensor is open or short- circuited| Check and replace the system 1 high-pressure sensor
Syst2: High-Pressure Sensor Fault| PP22| The sensor is open or short- circuited| Check and replace the system 2 high-pressure sensor
Protection/fault| Codes| Causes| Removal methods
---|---|---|---
Syst2: Exhaust Air Temp Sensor Fault| P281| The temperature sensor is open or short-circuited| Check and replace the system 2 exhaust temperature sensor
Syst2: Low-Pressure Sensor Fault| PP21| The sensor is open or short-circuited| Check and replace System 2 low-voltage sensor
Syst2: EVI(In) Temp Sensor Fault| P201| The temperature sensor is open or short-circuited| Check and replace System 2 EVI inlet temperature sensor
Syst2: EVI(Out) Temp Sensor Fault| P202| The temperature sensor is open or short-circuited| Check and replace System 2 EVI outlet temperature sensor
Low A.T. Power-Off Prot.| TP| Excessively low environment temperature|
Syst1: Coil Temp Sensor Fault 2| P154| The temperature sensor is open or short-circuited| Check and replace the system 1 coil 2 temperature sensor
Syst2: Coil Temp Sensor Fault 2| P254| The temperature sensor is open or short-circuited| Check and replace the system 2 coil 2 temperature sensor
Syst1: Comp. Overcurrent Prot.| E101| System 1 compressor running current too large| Check if the current is too high
Syst2: Comp. Overcurrent Prot.| E201| System 2 compressor running current is too large| Check if the current is too high
Syst1: Comp. Overcurrent Prot. 3+| E101| System 1 compressor running current is too large| Check if the current is too high
Syst2: Comp. Overcurrent Prot. 3+| E201| System 2 compressor running current is too large| Check if the current is too high
Syst1: Comp. Start Fault| E132| System 1 compressor failed to start|
Syst2: Comp. Start Fault| E232| System 2 compressor failed to start|
Syst1: Comp. Stop Fault| E133| System 1 compressor failed to stop|
Syst2: Comp. Stop Fault| E233| System 2 compressor failed to stop|
Power Down Memory| EE1| Loss of power when power on| Automatic recovery after 3 minutes of power on

Appendix

Cable Specifications

Single Phase Unit

Nameplate maximum current| Phase line| Earth Line| MCB| Creepage Protector| Signal Line
No more than 10A| 2 x 1.5mm2| 1.5mm2| 20A| ****







30mA less than 0.1 sec

| ****







n x 0.5mm2

10~16A| 2 x 2.5mm2| 2.5mm2| 32A
16~25A| 2 x 4mm2| 4mm2| 40A
25~32A| 2 x 6mm2| 6mm2| 40A
32~40A| 2 x 10mm2| 10mm2| 63A
40~63A| 2 x 16mm2| 16mm2| 80A
63~75A| 2 x 25mm2| 25mm2| 100A
75~101A| 2 x 25mm2| 25mm2| 125A
101~123A| 2 x 35mm2| 35mm2| 160A
123~148A| 2 x 50mm2| 50mm2| 225A
148~186A| 2 x 70mm2| 70mm2| 250A
186~224A| 2 x 95mm2| 95mm2| 280A
 | Three Phase Unit
---|---
Nameplate maximum current| Phase line| Earth Line| MCB| Creepage Protector| Signal Line
No more than 10A| 3 x 1.5mm2| 1.5mm2| 20A| ****







30mA less than 0.1 sec

| ****







n x 0.5mm2

10~16A| 3 x 2.5mm2| 2.5mm2| 32A
16~25A| 3 x 4mm2| 4mm2| 40A
25~32A| 3 x 6mm2| 6mm2| 40A
32~40A| 3 x 10mm2| 10mm2| 63A
40~63A| 3 x 16mm2| 10mm2| 80A
63~75A| 3 x 25mm2| 16mm2| 100A
75~101A| 3 x 25mm2| 16mm2| 125A
101~123A| 3 x 35mm2| 16mm2| 160A
123~148A| 3 x 50mm2| 25mm2| 225A
148~186A| 2 x 70mm2| 35mm2| 250A
186~224A| 2 x 95mm2| 50mm2| 280A

  • If the unit is installed outdoors, use a UV resistant cable.
  • The above specification is for reference only. For specific wire and breaker models please check the corresponding factory standard and actual installation requirement

Wiring Diagram

EVOHEAT-Evo-Ultra-Commercial-Hot-Water-Heat-Pump-
FIG-14

Maintenance

DO I NEED TO GET MY UNIT SERVICED?

  • It is recommended that you get your EvoHeat unit serviced once a year by your local certified air conditioning or refrigeration technician. If your unit is located in a coastal area, more frequent maintenance may be necessary. During the service, they will check the operational pressures of the refrigeration system and give the unit and fins a good clean to ensure maximum performance.

DO WE HAVE RECOMMENDED SERVICE AGENTS?

  • EvoHeat have a large database of recommended service agents. Please contact EvoHeat tech support on 1300 859 933 for your local service agent details.

SHOULD I CHECK MY UNIT REGULARLY?

  • We recommend you check your unit regularly to avoid potential issues and damage to your heat pump.
  • Check the water inlet/outlets often for leaks. You should avoid the condition of no water or air entering into the system, as this will influence unit’s performance and reliability.
  • You should clear the pool/spa filter regularly to avoid damage to the unit as a result of the dirty of clogged filter.
  • The area around the unit should be dry, clean and well-ventilated. Make sure there is nothing blocking the airflow of the heater e.g. Leaf litter.

WHAT SHOULD I BE CHECKING REGULARLY?

  • Discharge all water in the water pump and water system, so that freezing of the water in the pump or water system does not occur. You should discharge the water at the bottom of water pump if the unit will not be used for an extended period. You should check the unit thoroughly and fill the system with water fully before using it for the first time after a period of time.
  • Check the power supply and cable connection often, should the unit begin to operate abnormally, switch it off and contact the qualified technician.

Warranty

Refer to the EvoHeat website for warranty details

  1. Warranty terms are from date of purchase.
  2. This warranty excludes any defect or injury caused by or resulting from misuse, abuse, neglect, accidental damage, improper voltage, vermin infestation, incompetent installation, any fault not attributable to faulty manufacture or parts, any modifications which affect the reliability or performance of the unit.
  3. This warranty does not cover the following:
    • Natural Disasters (hail, lightening, flood, fire etc.)
    • Rust or damage to paintwork caused by a corrosive atmosphere
    • When serviced by an unauthorized person without the permission of Evo Industries
    • When a unit is installed by an unqualified person
    • Where a unit is incorrectly installed
    • When failure occurs due to improper or faulty installation
    • Failure due to improper maintenance (refer Operating Instructions)
    • ‘No Fault Found’ service calls where the perceived problem is explained within the operation instructions.
    • Costs associated with delivery, handling, freighting, or damage to the product in transit.
  4. If warranty service is required, you should:
    • contact Evo Industries Australia on 1300 859 933 or via our Contact page on our web site
    • provide a copy of your receipt as proof of purchase
    • have completed the online Warranty Registration Form
  5. Onsite technical service is available within the normal operating area of your Evo Authorised Service Agents. Service outside this area will incur a traveling fee.
  6. Unless otherwise specified to the purchaser, the benefits conferred by this express warranty and additional to all other conditions, warranties, rights and remedies expressed or implied by the Trade Practices Act 1974 and similar consumer protection provisions contained in legislation of the States and Territories and all other obligations and liabilities on the part of the manufacturer or supplier and nothing contained herein shall restrict or modify such rights, remedies, obligations or liabilities.