MEAN WELL HDR-60 Series 60W DIN R Ultra Slim Step Shape Rail Instruction Manual

June 4, 2024
MEAN WELL

Series 60W DIN R Ultra Slim Step Shape Rail
Instruction Manual 

MEAN WELL HDR 60 Series 60W DIN R Ultra Slim Step Shape
Rail

https://www.meanwell.com/Upload/PDF/HDR%20DIN%20rail%20power%20supply.pdf

MEAN WELL HDR 60 Series 60W DIN R Ultra Slim Step Shape Rail - icon
1| MEAN WELL HDR 60 Series
60W DIN R Ultra Slim Step Shape Rail - icon 2
---|---

Features

  • Ultra slim design with 52.5mm(3SU) width
  • Universal input 85-264VAC(277VAC operational)
  • No load power consumption<0.3W
  • Isolation class II
  • Pass LPS (Limited power source)
  • DC output voltage adjustable
  • Protections: Short circuit / Overload / Over voltage
  • Cooling by free air convection (working temperature:-30-+70°C)
  • DIN rail TS-35/7.5 or 15 mountable
  • Overvoltage category III
  • LED indicator for power on
  • 3 years warranty

Description
HDR-60 is one economical ultra slim 60W DIN rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 52.5mm(3SU) in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input from 85VAC to 264VAC (277VAC operational) and conforms to BS EN/EN61000-3-2, the norm the European Union regulates for harmonic current.
HDR-60 is designed with plastic housing that it can effectively prevent users from electric hazards. With working efficiency up to 91%, the entire series can operate at the ambient temperature between -30’C and 70’C under air convection. The complete protection functions and relevant certificates for home automations and industrial control apparatus (IEC62368-1, UL508, UL62368-1, BS EN/EN61558-2-16) make HDR-60 a very competitive power supply solution for household and industrial applications.
Model Encoding

Applications

  • Household control system
  • Building automation
  • Industrial control system
  • Factory automation
  • Electro-mechanical apparatus

SPECIFICATION

MODEL| HDR-60-5| HDR-60-12| HDR-60-15| HDR-60-24| HDR-60-48
---|---|---|---|---|---
**OUTPUT| DC VOLTAGE| 5V| 12V| 15V| 24V| 48V
RATED CURRENT| 6.5A| 4.5A| 4A| 2.5A| 1.25A
CURRENT RANGE| 0 ~ 6.5A| 0 ~ 4.5A| 0 ~ 4A| 0 ~ 2.5A| 0 ~ 1.25A
RATED POWER| 32.5W| 54W| 60W| 60W| 60W
RIPPLE & NOISE (max.) **Note.2| 80mVp-p| 120mVp-p| 120mVp-p| 150mVp-p| 240mVp-p
VOLTAGE ADJ. RANGE| 5.0 ~ 5.5V| 10.8 ~ 13.8V| 13.5 ~ 18V| 21.6 ~ 29V| 43.2 ~ 55.2V
VOLTAGE TOLERANCE Note.3| ±2.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LOAD REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
SETUP, RISE TIME| 500ms, 50ms/230VAC 500ms, 50ms/115VAC at full load
HOLD UP TIME (Typ.)| 30ms/230VAC     12ms/115VAC at full load
**INPUT| VOLTAGE RANGE| 85 ~ 264VAC (277VAC operational  20 ~ 370VDC (390VDC operational )
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 85%| 88%| 89%| 90%| 91%
AC CURRENT (Typ.)| 1.2A/115VAC      0.8A/230VAC
INRUSH CURRENT (Typ.)| COLD START 30A/115VAC 60A/230VAC
****
PROTECTION| **

OVERLOAD

| 105 ~ 160% rated output power
Hiccup mode when output voltage <50%, recovers automatically after fault condition is removed Constant current limiting within 50% ~100% rated output voltage, recovers automatically after fault condition is removed


OVERVOLTAGE

| 5.75 ~ 6.75V| 14.2 ~ 16.2V| 18.8 ~ 22.5V| 30 ~ 36V| 56.5 ~ 64.8V
Protection type : Shut down o/p voltage, re-power on to recover
**ENVIRONMENT| WORKING TEMP.| -30 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃) RH non-condensing
VIBRATION| 10 ~ 500Hz, 2G 10min./1cycle, the period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
OPERATING ALTITUDE| 2000 meters
OVERVOLTAGE CATEGORY| Ⅲ; According to EN61558, EN50178,EN60664-1, EN62477-1; altitude up to 2000 meters
WITHSTAND VOLTAGE| I/P-O/P:4KVAC
ISOLATION RESISTANCE| I/P-O/P:100M Ohms / 500VDC / 25℃/ 70% RH
****
EMC EMISSION| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032(CISPR32), CNS13438| Class B
Radiated| BS EN/EN55032(CISPR32), CNS13438| Class B
Harmonic Current| BS EN/EN61000-3-2| Class A
****
SAFETY & **EMC
(Note 4 )| SAFETY STANDARDS| UL62368-1, UL508, TUV BS EN/EN61558-2-16, BS EN/EN61558-1, IEC62368-1, EAC TP TC 004, BSMI CNS14336-1, IS13252(Part1)/IEC60950-1 approved; Design refer to BS EN/EN62368-1
| Voltage Flicker| BS EN/EN61000-3-3| ——-
**EMC IMMUNITY| BS EN/EN55024, BS EN/EN55035, BS EN/EN61000-6-2, BS EN/EN61204-3
Parameter| Standard| Test Level /Note**
ESD| BS EN/EN61000-4-2| Level 3, 8KV air; Level 2, 4KV contact, criteria A
Radiated Susceptibility| BS EN/EN61000-4-3| Level 3, criteria A
EFT/Burest| BS EN/EN61000-4-4| Level 3, criteria A
Surge| BS EN/EN61000-4-5| Level 4,2KV/L-N, criteria A
Conducted| BS EN/EN61000-4-6| Level 3, criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4, criteria A
Voltage Dips and interruptions| BS EN/EN61000-4-11| >95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods


OTHERS

| MTBF| 927.6K hrs min.      MIL-HDBK-217F (25℃)
DIMENSION| 52.59054.5mm (WHD)
PACKING| 190g;60pcs/12.4Kg/0.97CUFT
**NOTE**| 1.  All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2.  Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1μf & 47μf parallel capacitor.
3.  Tolerance: includes set up tolerance, line regulation and load regulation.
4.  The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to “EMl testing of component power supplies.” (as available on http://www.meanwell.com)
5.  The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
※ Product Liability Disclaimer:For detailed information, please refer to https://www.meanwell.com/serviceDisclaimer.aspx

Block Diagram

MEAN WELL HDR 60 Series 60W DIN R Ultra Slim Step Shape Rail - Block
Diagram

Derating Curve

MEAN WELL HDR 60 Series 60W DIN R Ultra Slim Step Shape Rail - Derating
Curve

Output Derating VS Input Voltage

MEAN WELL HDR 60 Series 60W DIN R Ultra Slim Step Shape Rail - Output
Derating VS Input Voltage

Mechanical Specification

MEAN WELL HDR 60 Series 60W DIN R Ultra Slim Step Shape Rail - Mechanical
Specification

Terminal Pin No. Assignment

Pin No. Assignment Pin No. Assignment
1,2  -V 5 AC/L
3,4  +V 6 AC/N

Installation Manual
Please refer to: http://www.meanwell.com/manual.html

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>