Features
- Ultra slim design with 52.5mm(3SU) width
- Universal input 85-264VAC(277VAC operational)
- No load power consumption<0.3W
- Isolation class II
- Pass LPS (Limited power source)
- DC output voltage adjustable
- Protections: Short circuit / Overload / Over voltage
- Cooling by free air convection (working temperature:-30-+70°C)
- DIN rail TS-35/7.5 or 15 mountable
- Overvoltage category III
- LED indicator for power on
- 3 years warranty
Description
HDR-60 is one economical ultra slim 60W DIN rail power supply series, adapt
to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed
52.5mm(3SU) in width, which allows space saving inside the cabinets. The
entire series adopts the full range AC input from 85VAC to 264VAC (277VAC
operational) and conforms to BS EN/EN61000-3-2, the norm the European Union
regulates for harmonic current.
HDR-60 is designed with plastic housing that it can effectively prevent users
from electric hazards. With working efficiency up to 91%, the entire series
can operate at the ambient temperature between -30’C and 70’C under air
convection. The complete protection functions and relevant certificates for
home automations and industrial control apparatus (IEC62368-1, UL508,
UL62368-1, BS EN/EN61558-2-16) make HDR-60 a very competitive power supply
solution for household and industrial applications.
Model Encoding
Applications
- Household control system
- Building automation
- Industrial control system
- Factory automation
- Electro-mechanical apparatus
SPECIFICATION
MODEL| HDR-60-5| HDR-60-12| HDR-60-15| HDR-60-24|
HDR-60-48
---|---|---|---|---|---
**OUTPUT| DC VOLTAGE| 5V| 12V| 15V| 24V| 48V
RATED CURRENT| 6.5A| 4.5A| 4A| 2.5A| 1.25A
CURRENT RANGE| 0 ~ 6.5A| 0 ~ 4.5A| 0 ~ 4A| 0 ~ 2.5A| 0 ~ 1.25A
RATED POWER| 32.5W| 54W| 60W| 60W| 60W
RIPPLE & NOISE (max.) **Note.2| 80mVp-p| 120mVp-p| 120mVp-p| 150mVp-p|
240mVp-p
VOLTAGE ADJ. RANGE| 5.0 ~ 5.5V| 10.8 ~ 13.8V| 13.5 ~ 18V| 21.6 ~ 29V|
43.2 ~ 55.2V
VOLTAGE TOLERANCE Note.3| ±2.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LINE REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
LOAD REGULATION| ±1.0%| ±1.0%| ±1.0%| ±1.0%| ±1.0%
SETUP, RISE TIME| 500ms, 50ms/230VAC 500ms, 50ms/115VAC at full load
HOLD UP TIME (Typ.)| 30ms/230VAC 12ms/115VAC at full load
**INPUT| VOLTAGE RANGE| 85 ~ 264VAC (277VAC operational 20 ~
370VDC (390VDC operational )
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 85%| 88%| 89%| 90%| 91%
AC CURRENT (Typ.)| 1.2A/115VAC 0.8A/230VAC
INRUSH CURRENT (Typ.)| COLD START 30A/115VAC 60A/230VAC
****PROTECTION| **
OVERLOAD
| 105 ~ 160% rated output power
Hiccup mode when output voltage <50%, recovers automatically after fault
condition is removed Constant current limiting within 50% ~100% rated output
voltage, recovers automatically after fault condition is removed
OVERVOLTAGE
| 5.75 ~ 6.75V| 14.2 ~ 16.2V| 18.8 ~ 22.5V| 30 ~ 36V| 56.5 ~ 64.8V
Protection type : Shut down o/p voltage, re-power on to recover
**ENVIRONMENT| WORKING TEMP.| -30 ~ +70℃ (Refer to “Derating
Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃) RH non-condensing
VIBRATION| 10 ~ 500Hz, 2G 10min./1cycle, the period for 60min. each
along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
OPERATING ALTITUDE| 2000 meters
OVERVOLTAGE CATEGORY| Ⅲ; According to EN61558, EN50178,EN60664-1,
EN62477-1; altitude up to 2000 meters
WITHSTAND VOLTAGE| I/P-O/P:4KVAC
ISOLATION RESISTANCE| I/P-O/P:100M Ohms / 500VDC / 25℃/ 70% RH
****EMC EMISSION| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032(CISPR32), CNS13438| Class B
Radiated| BS EN/EN55032(CISPR32), CNS13438| Class B
Harmonic Current| BS EN/EN61000-3-2| Class A
****SAFETY & **EMC
(Note 4 )| SAFETY STANDARDS| UL62368-1, UL508, TUV BS
EN/EN61558-2-16, BS EN/EN61558-1, IEC62368-1, EAC TP TC 004, BSMI CNS14336-1,
IS13252(Part1)/IEC60950-1 approved; Design refer to BS EN/EN62368-1
| Voltage Flicker| BS EN/EN61000-3-3| ——-
**EMC IMMUNITY| BS EN/EN55024, BS EN/EN55035, BS EN/EN61000-6-2, BS
EN/EN61204-3
Parameter| Standard| Test Level /Note**
ESD| BS EN/EN61000-4-2| Level 3, 8KV air; Level 2, 4KV contact, criteria A
Radiated Susceptibility| BS EN/EN61000-4-3| Level 3, criteria A
EFT/Burest| BS EN/EN61000-4-4| Level 3, criteria A
Surge| BS EN/EN61000-4-5| Level 4,2KV/L-N, criteria A
Conducted| BS EN/EN61000-4-6| Level 3, criteria A
Magnetic Field| BS EN/EN61000-4-8| Level 4, criteria A
Voltage Dips and interruptions| BS EN/EN61000-4-11| >95% dip 0.5 periods, 30%
dip 25 periods,
>95% interruptions 250 periods
OTHERS
| MTBF| 927.6K hrs min. MIL-HDBK-217F (25℃)
DIMENSION| 52.59054.5mm (WHD)
PACKING| 190g;60pcs/12.4Kg/0.97CUFT
**NOTE**| 1. All parameters NOT specially mentioned are measured at
230VAC input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted
pair-wire terminated with a 0.1μf & 47μf parallel capacitor.
3. Tolerance: includes set up tolerance, line regulation and load regulation.
4. The power supply is considered as an independent unit, but the final
equipment still need to re-confirm that the whole system complies with the EMC
directives. For guidance on how to perform these EMC tests, please refer to
“EMl testing of component power supplies.” (as available on
http://www.meanwell.com)
5. The ambient temperature derating of 3.5℃/1000m with fanless models and of
5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
※ Product Liability Disclaimer:For detailed information, please refer to
https://www.meanwell.com/serviceDisclaimer.aspx
Block Diagram
Derating Curve
Output Derating VS Input Voltage
Mechanical Specification
Terminal Pin No. Assignment
Pin No. | Assignment | Pin No. | Assignment |
---|---|---|---|
1,2 | -V | 5 | AC/L |
3,4 | +V | 6 | AC/N |
Installation Manual
Please refer to: http://www.meanwell.com/manual.html