BIOGENESIS 3-6-12 Kg Gas HFC Automatic Device Mare Instruction Manual
- June 12, 2024
- BIOGENESIS
Table of Contents
- BIOGENESIS 3-6-12 Kg Gas HFC Automatic Device Mare
- Product Information
- Product Usage Instructions
- AUTOMATIC DEVICE “MARE SERIES” 3-6-12 Kg Gas HFC
- AVAILABLE VERSIONS
- TECHNICAL SPECIFICATIONS
- PACKAGING
- MAINTENANCE AND INSTALLATION
- SPARE PARTS
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
BIOGENESIS 3-6-12 Kg Gas HFC Automatic Device Mare
Product Information
The Automatic Device Mare Series is a gas-based fire extinguishing system manufactured by Biogenesis S.r.l. This device is available in three different versions: 3 Kg, 6 Kg, and 12 Kg. It is designed for use in new installations and requires specific components (2164, 2165, 2163) to be operational. The device is made of alloy steel with epoxypolyester powder painting in Red Ral 3000 color.
The device is certified according to the directive for pressure equipment PED 2014/68/EU and RINA certified with ISO 9094:2015. It is a quality product suitable for use in fire incidents involving electrical voltages up to a distance of 1 meter.
The device comes with various optional features such as a manual actuator with a handle, pyrotechnic cartridge for electric activation, and a pressure switch. The pressure switch is normally open, but when installed on the device, it becomes normally closed.
Product Usage Instructions
- Installation: Install the system in a vertical position using the supplied bracket. Place the gas distribution pipe and fix the nozzles according to your choice of dispensing points.
- Operating System: Remove the safety pin to make the operating system functional.
- Maintenance: It is recommended to perform maintenance every 6 months by checking the pressure. Replace the extinguishing agent every 72 months and conduct a test after 144 months from the production date.
- Spare Parts: The device comes with various spare parts that can be replaced if needed. These include valve o-ring, pressure gauge, manual actuator in control box (with a 5m cable), cylinder brackets, PVC dip tubes, brass dispensing nozzle, pyrotechnic cartridge, label, and pressure switch.
Note: The packaging quantities and measurements are subject to changes, and the image provided is for illustrative purposes only.
AUTOMATIC DEVICE “MARE SERIES” 3-6-12 Kg Gas HFC
In new installations, the devices for to be operative need at least of this
components: 2164; 2165; 2163
See example of installation at next page
Note: items supplied only on request
-
CYLINDER
Alloy steel, epoxypolyestere powder painting, Red Ral 3000. -
EXTINGUISHING AGENT Gas HFC 227 ea.
-
PROPELLANT Nitrogen (N2).
-
VALVE
Automatic M. 30×1.5, set 93 °C.
(with bulb in standard equipment) Supplied with pressure switch set at 11 bar. -
USE
A B fire rating (solid materials, flammable liquids). -
ACTIVATION
- Automatic when bulb temperature is reached. On request (see optional):
- with manual actuator with handle;
- with pyrotechnic cartridge for electric activation.
-
BRACKET
Wall-mounted in standard equipment.
Note for pressure switch:
The pressurized device is “normally open”. The pressure switch alone, not
installed on the device, is “normally closed”.
Gas HFC Automatic Device, Mare Series, available charge 3, 6, 12 Kg ,
temperature range from -30°C to +60°C, certified according to the directive
for pressure equipment PED 2014/68/EU. RINA certified, ISO 9094:2015. Quality
Product certification guaranteed by Bureau Veritas Italia.
Suitable for use on fire involving electrical voltages up to 1.000 V, at a
distance of 1 mt.
AVAILABLE VERSIONS
| GAS HFC QUANTITY| DIMENSIONS (without bracket) H x
L max x Ø cylinder (mm)| M3/Kg| C % (concentration
gas in volume)| DISTRIBUTION TUBE LENGTH| NUMBER OF
NOZZLE| DISCHARGE TIME| COVERAGE AREA
---|---|---|---|---|---|---|---|---
| Kg 3| 440 +/- 5 x 140 +/- 3 x 130 +/- 1| 0,1373| 7,611| recommended 5 m|
Based on choice of dispensing points of installation| 20 sec.| 5 c.m.
| Kg 6| 490 +/- 5 x 160 +/- 3 x 160 +/- 3| 0,1373| 7,611| recommended 5 m| 35
sec.| 10 c.m.
| Kg 12| 590 +/- 5 x 190 +/- 3 x 190 +/- 3| 0,1373| 7,611| recommended 8 m| 60
sec.| 20 c.m.
TECHNICAL SPECIFICATIONS
FIRE RATING | A B |
---|---|
EXTINGUISHING AGENT | Gas HFC 227 ea |
PROPELLANT | Nitrogen (N2), 15 Bar at 20 °C |
TEMPERATURE RANGE | -30°C / +60°C |
CYLINDER PRESSURE TEST | PT 27 bar |
VALVE TIGHTENING TORQUE | Between 40 and 50 Nm |
CYLINDER MATERIAL | Alloy steel |
EXTERNAL/INTERNAL TREATMENT | Sandblast and epoxypolyestere powder painting, |
Red Ral 3000 colour
PACKAGING
STANDARD : single packaging
Note: the packaging quantities and measurements are indicative and can be
subject at changes
MAINTENANCE AND INSTALLATION
Install the system in vertical position using the supplied bracket. Place the
gas distribution pipe and fix the nozzles. Remove the safety pin to make
operating system.
Recommended maintenance : every 6 months check pressure; every 72 months
replace extinguishing agent; test after 144 months of production date.
EXAMPLE OF AUTOMATIC DEVICE INSTALLATION
SPARE PARTS
N.| DESCRIPTION|
---|---|---
1| Valve M. 30×1.5 with thermosensible bulb for activation at 93°C|
2| Valve o-ring|
3| Pressure gauge|
4 – OPTIONAL| Manual actuator in control box(cable 5 m)|
5| Cylinder 3 Kg
Cylinder 6 Kg
Cylinder 12 Kg|
6| Iron bracket 3 Kg Iron bracket 6 Kg Iron bracket 12 Kg|
7| PVC dip tube 3 Kg PVC dip tube 6 Kg PVC dip tube 12 Kg|
8 – OPTIONAL| Brass dispensing nozzle M 3/8”|
9 – OPTIONAL| Aluminum distribution tube Ø 10, PVC coated|
10 – OPTIONAL| Fitting F 3/8” for distribution tube|
OPTIONAL| Pyrotechnic cartridge|
11| Label|
| Pressure switch 1/8” for valve, set at 11 bar|
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>